Shut off all fans on the discharge pressure switch.
Ignores the time between deactivations.
Shuts off all compressors from the suction pressure
switches in the same group. Respects the time between
shutdowns.
Low pressure
High pressure
AL0x01
AL0x02
Alarm
Effect
Description
Shuts off all compressors from the suction pressure
switches in the same group. Ignores the time between
shutdowns.
Critical high pressure
AL0x03
AL0x08
AL0x09
AL0x10
AL0x11
High subcooling
Backup pressure sensor fault
Main pressure sensor fault
Main temperature sensor fault
Actuates according to the configuration of menu 1.5
Actuates according to the configuration of menu 1.5
Actuates according to the configuration of menu 1.5
Indicative alarm
AL0x07
Low subcooling
Shuts off the fans respecting the time between
shutdowns
High temperature
Shuts off all fans on the discharge pressure switch.
Ignore the time between shutdowns
Shuts off all compressors from the suction pressure
switches in the same group. Respects the time between
shutdowns
Shuts off all compressors from the suction pressure
switches in the same group. Respects the time between
shutdowns
Critical high temperature
Low temperature
AL0x05
AL0x06
AL0x04
17.4.3 Discharge alarms:
The
RCK-862
plus
can control up to 3 discharge pressure switches. The address of each pressure switch in the alarm
nomenclature is represented by the letter ‘’x’’. Where ‘’x’’ can be 4, 5 or 6 and represents discharge pressure switches 1,2 or 3, respectively.
Example:
AL0x01
4 - Referring to Discharge 1
5 - Referring to Discharge 2
6 - Referring to Discharge 3
17.ALARMS
Alarm
Effect
Description
External alarm 6
External alarm 7
External alarm 9
External alarm 8
External alarm 10
External alarm 5
AL0x35
AL0x36
AL0x38
AL0x37
AL0x39
AL0x34
Indicative alarm
Indicative alarm
Indicative alarm
Indicative alarm
Indicative alarm
Indicative alarm
External fault 3
External fault 5
External fault 7
External fault 9
External fault 2
External fault 4
External fault 6
External fault 8
External fault 10
AL0x42
AL0x44
AL0x46
AL0x48
AL0x41
AL0x43
AL0x45
AL0x47
AL0x49
Disconnect all compressors from the suction pressure
switch. Ignores the time between shutdown
Disconnect all compressors from the suction pressure
switch. Ignores the time between shutdown
Disconnect all compressors from the suction pressure
switch. Ignores the time between shutdown
Disconnect all compressors from the suction pressure
switch. Ignores the time between shutdown
Disconnect all compressors from the suction pressure
switch. Ignores the time between shutdown
Disconnect all compressors from the suction pressure
switch. Ignores the time between shutdown
Disconnect all compressors from the suction pressure
switch. Ignores the time between shutdown
Disconnect all compressors from the suction pressure
switch. Ignores the time between shutdown
Disconnect all compressors from the suction pressure
switch. Ignores the time between shutdown
Disconnect all compressors from the suction pressure
switch. Ignores the time between shutdown
External fault 1
AL0x40