19.PARAMETER TABLE
1.4.4.2
Interval between attempts:
Time interval between two subsequent attempts of automatic reset.
1.4.4.3
Reset period:
This feature allows you to adjust the time for the number of automatic reset attempts (
1.4.4.1
). If all automatic resets have already been carried out
within the time set in this feature and another fault occurs, the
RCK-862
plus
controller only resumes operation with a manual reset.
1.4.5
Alarm outputs:
It allows configuring up to 6 alarm outputs with specific features.
1.4.5.x
Output x:
The
RCK-862
plus
has up to six configurable alarm outputs. For each output, a specific alarm on the control lines can be linked and the output can be
configured to cycle on and off or only on in the event of an alarm.
The letter x represents alarm outputs 1 to 6.
1.4.5.x.1
Suction / discharge pressure switch:
Associates the alarm output to one of the lines:
1.4.5.x.2
Output function:
The alarm output is linked with one of the following alarm events:
1.4.5.x.3
Time on:
Time that the output remains actuated in an alarm event.
1.4.5.x.4
Time off:
Time the output remains shutdown in an alarm event. When this time is set to OFF, the output will be activated if there is an alarm condition.
1.4.5.x.5
Contact type:
Output polarity
0 - NO: When the output is actuated, the contact is closed.
1 - NC: When the output is actuated, the contact is open.
Feature
Minimum
Maximum
Unit
Standard
Description
-
-
-
-
1.4.5.x.1
1.4.5.x.2
1.4.5.x.3
1.4.5.x.4
1.4.5.x.6
1.4.5.x.5
999
-
999
6
24
1
0
0
0
0
0
0
0
0
0
0
0
0
sec
sec
Output function
Time off
Digital output
Suction / discharge pressure switch
Time On
Contact type NO-NC
0 = Off
1 = Suction 1
2 = Suction 2
3 = Suction 3
5 = Discharge 2
4 = Discharge 1
6 = Discharge 3
0 = Off
1 = Any alarm
7 = High pressure
18 = Any subcooling alarm
2 = Low pressure
13 = Low overheating
8 = High critical temperature
19 = Pressure sensor fault
3 = High pressure
14 = High overheating
9 = Any temperature alarm
20 = Temperature sensor fault
5 = Any pressure alarm
16 = Low subcooling
11 = Awaiting manual reset
22 = Wet bulb temperature sensor fault
24 = Fault in any sensor
4 = Critical high pressure
15 = Any overheating alarm
10 = Digital input
21 = Dry bulb temperature sensor fault
6 = Low pressure
17 = High subcooling
12 = Critical overheating
23 = Compressor temperature sensor fault