741
S
Flow temp setpoint max
8... 95 °C
1 °C
55 °C
Floor heating system = 50 °C / Higher temperature radiator = 65 °C
750
S
Room influence
1%... 100%
1%
20%
If the installation is fitted with a room thermostat :
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
790
S
Optimum start control max
(Early start to switch to the comfort setting.).
0... 360 min
10 min
120 min
791
S
Optimum stop control max
(Early stop to switch from the comfort setting to the
reduced setting.).
0... 360 min
10 min
120 min
800
S
Reduced setp increase start
-30... 10 °C
1 °C
--
801
S
Reduced setp increase end
-30... 10 °C
1 °C
-5 °C
830
S
Mixer valve boost
0... 50 °C
1 °C
0
834
S
Actuator running time
30... 873 s
1 s
240 s
850
I
Floor curing function (
figure 44
)
Off
-Off : Early interruption of the current programme, programme inactive
-Functional heating
-Heating ready for occupation
-Functional h curing heating
-Curing h Functional heating
-Manually
Manual mode enables you to programme your own concrete slab drying time.The function ends automatically after
25 days.
851
I
Floor curing setp manually
(if line 850 = manual)
0... 95 °C
1 °C
25 °C
This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed.
The concrete slab-drying programme stops automatically after running for 25 days.
856
I
Floor curing day current
0... 32
857
I
Days complete.current
0... 32
900
S
Operating mode changeover
None, Protection mode,
Reduced, Comfort, Automatic
1
Protection
mode
Operating mode at end of concrete slab drying period
50
45
40
35
30
20
5
0
25
55
1
1
5
7
X
10
18
25
15
1
Figure 44 - Diagram of the concrete slab drying programmes
"
Please comply with the
standards and instructions
of the manufacturer of the
building! A good performance
of this function is only possible
with an installation correctly
implemented
(hydraulic,
electricity and adjustments)!
This function can be stopped
by anticipation when setting
the adjustment on "Stop"
Line
Function
Setting range
or display
Setting
increment
Basic
setting
Heating flow temperature °C
Functional h Heating ready for occupation
Heating ready for occupation
Day
Functional
heating
Installation and operating manual "1364 - EN"
- 35 -
Heat pump split single service 3 phase