3 4 Parametering the setting
3 4 1 General
Only the parameters accessible to levels :
U
- End user.
I
- Commissioning level.
S
- Engineer level.
Are described in this document.
The access levels are specified in the second column of
the table by means of the letters
U
,
I
and
S
.
The OEM parameters are not described and require a
manufacturer’s access code.
3 4 2 Setting parameters
-Choose the desired level.
-Scroll the menu list.
-Choose the desired menu.
-Scroll the function lines.
-Choose the desired line.
-Adjust the parameter.
-Check the setting by pressing
OK
.
-To return the menu, press
ESC
.
If no setting is made for 8 minutes, the screen returns
automatically to the basic display.
3 4 3 List of function lines (settings, diagnosis, status)
Line
Function
Setting range
or display
Setting
increment
Base
setting
Date and time
1
U
Hours / Minutes
00:00... 23:59
1
2
U
Day / Month
01.01... 31.12
1
3
U
Year
1900... 2099
1
5
S
Start of summer time (Day / Month)
01.01... 31.12
1
25 03
6
S
End of summer time (Day / Month)
01.01... 31.12
1
25 10
The change of hour will appear at 3:00 am first Sunday after the regulated date.
User interface
20
U
Language
English, Français, Italiano,
Nederlands
English
22
S
Info
Temporary | Permanent
Temporary
26
S
Operation locking
On | Off
Off
27
S
Programming locking
Off | On
Off
28
I
Direct adjustment
Automatic storage...
Storage with confirmation
Storage with
confirmation
Basic
display
OK
Brief press
End user
OK
OK
OK
Time of day and date
Hours / minutes
1
Hours
1...24 h
Operator section
Day / month
2
Minutes
0...60 min
Time prog heating circuit 1
Year
3
Press for
3 seconds
End user
Commissioning
Engineer
OEM
Time of day and date
Hours / minutes
1
Operator section
Day / Month
2
Time prog heating circuit 1
Year
3
Start of summer time
4
01.01...31.12
End of summer time
5
Installation and operating manual "1364 - EN"
Heat pump split single service 3 phase
- 32 -