En-7
(3)
About air conditioner output setting
Setting
SW
Reference Section
Mode setting
SW104-1
See (3-1)
External switch detection conditions
with Mode 0
SW104-3/4
See (3-2)
1
Output setting with Mode 0
Rotary SW (EXIN)
See (3-2)
2
External switch detection conditions
with Mode 1
SW104-3/4
See (3-3)
1
Output setting with Mode 1
Rotary SW (EXIN)
See (3-3)
2
OFF
output setting
SW104-2
See (3-4)
(3-1) Mode setting (SW104-1)
DIP SW
OFF
ON
SW104-1
Mode 0
Mode 1
(
: Factory setting)
Determines how “SCENE setting” is assigned.
Mode 0: Assign 2 scenes to 2 switches.
Mode 1: Assign 4 scenes to 2 switches.
SCENE1
SCENE1
SCENE2
SCENE2
CH1
CH1
CH2
CH2
Mode 0
Mode 1
ON
ON
OFF
OFF
ON
ON
OFF
OFF
SCENE3
SCENE4
(3-2) For Mode 0 (SW104-1)
1
Polarity setting (SW104-3/4)
DIP SW
Setting
OFF
ON
SW104-3
CH1 external switch detec-
tion condition
ON
→
OFF
OFF
→
ON
SW104-4
CH2 external switch detec-
tion condition
ON
→
OFF
OFF
→
ON
(
: Factory setting)
SW104-3 and SW104-4 sets the polarity of CH1 and CH2 respectively.
SCENE1
SCENE1
CH1
CH1
SW104-3: OFF
SW104-3: ON
ON
ON
OFF
OFF
2
Rotary switch setting (EXIN)
Rotary switch setting value
Setting
0
No output
1
Operation stop output
2~9
Forbidden
(
: Factory setting)
When set to 0, there will be no output on the side (ON or OFF) opposite to
which SCENE 1 or SCENE 2 is assigned.
When set to 1, Operation stop is outputted on the side (ON or OFF) opposite
to which SCENE 1 or SCENE 2 is assigned.
SCENE1
No output
Operation stop
SCENE1
CH1
CH1
EXIN Rotary switch: 0
EXIN Rotary switch: 1
ON
ON
OFF
OFF
×
(3-3) For Mode 1 (SW104-1)
1
Polarity setting (SW104-3/4)
DIP SW
Setting
OFF
ON
SW104-3
No function
Fixed to OFF
―
SW104-4
CH2 external
switch
detection condition
ON
→
OFF is SCENE3
OFF
→
ON is SCENE4
OFF
→
ON is SCENE3
ON
→
OFF is SCENE4
(
: Factory setting)
2
Rotary switch setting (EXIN)
Rotary switch
setting value
Setting
SCENE3
SCENE4
0
Operation stop
Operation
Stop
1
Remote controller pro-
hibition all operation
All operation
enabled
All operation
disabled
2*
Operation mode
COOL
HEAT
3~9
Forbidden
(
: Factory setting)
* For VRF heat pump models, the operation mode cannot be switched
between COOL/HEAT when the indoor unit operation is ON.
Refer to (3-4)
Set CH2.
SW104-3 has no function.
SW104-4 determines SCENE3 and SCENE4 assigned to the function se-
lected with Rotary switch (EXIN).
SCENE3
SCENE4
SCENE4
SCENE3
CH2
CH2
SW104-4: OFF
SW104-4: ON
ON
ON
OFF
OFF
Rotary switch (EXIN) selects the function assigned to CH2.
(3-4) OFF output setting (SW104-2)
For VRF heat pump models, the operation mode cannot be switched
between COOL/HEAT when the indoor unit operation is ON. In this case,
operation can be switched between COOL/HEAT by setting OFF output to
“Enabled,” turning operation of the indoor unit to OFF and then changing the
operation mode.
DIP SW
OFF
ON
SW104-2
Disabled
Enabled
(
: Factory setting)
Determines whether or not there is operation stop output before the output
set with the external input switch.
When this is set to “Enabled,” if the external switch changes, there is an
operation stop output, and then the set air-conditioner operation setting is
output 1 minute later.
SCENE1
Operation stop
1 minute
CH
OFF output enabled
9374707157-02_IM.indb 7
9374707157-02_IM.indb 7
12/2/2016 5:22:46 PM
12/2/2016 5:22:46 PM