background image

En-4

 

CAUTION

To peel the sheath from the lead cable, use a dedicated tool that will 
not damage the conductor cable.

When installing a screw on the terminal block, do not cut the cable 
by overtightening the screw. On the other hand, an under tightened 
screw can cause faulty contact, which will lead to a communication 
failure.

6.  INSTALLING THE EXTERNAL SWITCH CONTROLLER

 

WARNING

Always use the accessories and speci

fi

 ed installation work parts. Check 

the state of the installation parts. Not using the speci

fi

 ed parts will cause 

units to fall off, electric shock, 

fi

 re, etc.

Install at a place that can withstand the weight of the unit and install 
positively so that the unit will not topple or fall.

When installing this unit, make sure that there are no children nearby.
Otherwise, injury or electric shock could result.

 

CAUTION

Do not set the DIP switch or rotary switch of this unit except as speci

fi

 ed 

in this installation manual or the instruction manual supplied with the air 
conditioner. Setting the switches other than speci

fi

 ed will cause an ac-

cident or trouble.

Use an insulated screwdriver to set the DIP switches.

Before opening the cover of this unit, completely discharge static electric-
ity charged on your body. Otherwise, failure or malfunction could result.

Do not touch the circuit board and circuit board parts directly with your 
hands.
Otherwise, injury or electric shock could result.

Tightening the mounting screws too tight will damage the body of this 
unit.

6. 1. 

Connecting the cables

(1)  Turn off the power of the connecting unit.
(2)  Insert a screwdriver, etc., into the hole (For open case) and open the 

top cover.

Push

Open

(3)  Connect the external input cable and remote controller cable to their 

respective terminal block properly.

(4)  Securely tighten the cable tie and then con

fi

 rm that the cable will not 

come out.

(5)  Use the 3 screws (M4 × 16 mm) provided to mount this product to the 

behind ceiling, wall, 

fl

 oor or other suitable location.

(6)  Once the wiring of the cables is completed, snap in the 2 hooks on 

the top cover and close the top cover.

2 hooks

(7)  This product has seven holes as shown below. 

Putty up unused holes, as needed.

If a cable or cable tie goes through the hole, 

fi

 ll out the gap with the 

putty.

* The hole for a cable can be widened as necessary. When passing the 

thick cable through the hole, widen it.

9374707157-02_IM.indb   4

9374707157-02_IM.indb   4

12/2/2016   5:22:45 PM

12/2/2016   5:22:45 PM

Summary of Contents for UTY-TERX

Page 1: ...ONTROLLER For authorized service personnel only 安装说明书 安装说明书 外部开关控制器 仅针对授权的专业维修人员 English 中 文 中 文 PART NO 9374707157 02 Original instructions UTY TERX 9374707157 02_IM indb i 9374707157 02_IM indb i 12 2 2016 5 22 43 PM 12 2 2016 5 22 43 PM ...

Page 2: ...ntive measures so that they cannot reach the unit CAUTION This mark indicates procedures which if improp erly performed might possibly result in personal harm to the user or damage to property Pay abundant care when transporting this unit because it is a precision device Improper transportation will cause trouble Do not touch the switches with sharp objects Doing so will cause injury trouble or el...

Page 3: ...er supply cable connection cable and remote controller cable 1 m 40 in away from television and radio to avoid distorted images and noise Otherwise a malfunction could result Perform wiring so that water does not enter this unit along the external wiring Always install a trap to the wiring or take other countermeasures Otherwise it will cause trouble or electric shock or fire Confirm the name of e...

Page 4: ...controller Y1 Y2 Y3 External input EXIN1 EXIN2 0 5 to 0 6 N m 4 4 to 5 3 lbf in 5 to 6 kgf cm 5 1 Wiring method Indoor unit VRF single multi Wired remote controller Wired remote controller cable This product External input cable Card key Window switch Connectable types of indoor unit and remote controller The wired remote controller shown in the table below can be connected The indoor unit that ca...

Page 5: ...e DIP switches Before opening the cover of this unit completely discharge static electric ity charged on your body Otherwise failure or malfunction could result Do not touch the circuit board and circuit board parts directly with your hands Otherwise injury or electric shock could result Tightening the mounting screws too tight will damage the body of this unit 6 1 Connecting the cables 1 Turn off...

Page 6: ...connection method is differ ent depending on each model Modify the remote controller cable as per below description and connect it For the details refer to the installation manual of the indoor unit to be used 1 When connecting to the connector Case 1 For non polar 2 wire Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of...

Page 7: ...le is 50m 164 ft 9 CIRCUIT BOARD SETTING The circuit board has a rotary switch DIP switch and LED as shown below 1 About connections 1 1 2WIRE 3WIRE settings SET3 Remote controller 2WIRE 3WIRE switching SW Default 2WIRE Set matched with the connection method of the remote controller cable to be connected 1 2 Master settings SET 2 1 When setting the SET3 to 3WIRE DIP SW OFF ON SET 2 1 Master Slave ...

Page 8: ... Mode 1 SW104 1 1 Polarity setting SW104 3 4 DIP SW Setting OFF ON SW104 3 No function Fixed to OFF SW104 4 CH2 external switch detection condition ON OFF is SCENE3 OFF ON is SCENE4 OFF ON is SCENE3 ON OFF is SCENE4 Factory setting 2 Rotary switch setting EXIN Rotary switch setting value Setting SCENE3 SCENE4 0 Operation stop Operation Stop 1 Remote controller pro hibition all operation All operat...

Page 9: ... If operation mode is set to No change 2 the operation mode is not changed If this scene is run 1 If operation mode is COOL or DRY the set temperature will be changed to set temperature 1 2 If operation mode is HEAT the set temperature will be changed to set temperature 2 3 If operation mode is AUTO or fan the set temperature is not changed Remote controller prohibition all operation SW108 3 4 SCE...

Page 10: ...speed SW105 3 4 ON OFF Hi Operation mode SW106 1 2 ON OFF COOL All operation SW106 3 4 OFF OFF No change Set tempera ture 1 SW109 1 2 3 4 OFF OFF OFF ON 23 C 74 F Set tempera ture 2 SW110 1 2 3 4 OFF OFF OFF OFF No change 2 Example setting 2 When a window is opened operation stop remote controller opera tion prohibited return to original state when the window is closed For specifications where con...

Page 11: ...h settings method refer to the installation instruction sheet of each unit 3 Turn on the power for the VRF system or multi system or single model 4 Power will be supplied from the system to the convertor This product will be initialized and the power turned on LED1 green and LED2 orange will flash After initial setting is completed operation will be restarted auto matically LED1 green lights This ...