(5) About OFF TIMER

 setting

 

OFF TIMER speci

fi

 cations are as follows.

  

ON

OFF

SCENE1

SCENE2

Set time

Stop

Rotary switch setting (SW103)

Rotary switch setting value

Set time

Do not turn Stop

1

Stop after 1 hour 

*5

2

Stop after 3 hours

3

Stop after 6 hours

4

Stop after 12 hours

5

Stop after 24 hours

6~9

Forbidden

(

:  Factory setting)

*5  When the operation mode is set to “No change 2” and the operation 

mode of the indoor unit is “HEAT,” it will turn Stop after 2 hours.

When Rotary switch (SW103) is set to 1~5 and Mode setting (SW104-1) is 
Mode 1 (ON),  the polarity setting (SW104-3) is set as follows.

DIP SW

Setting

OFF 

ON

SW104-3

CH1 external switch 

detection condition

ON 

 OFF is SCENE1

OFF 

 ON is SCENE2

ON 

 OFF is SCENE2

OFF 

 ON is SCENE1

ON

OFF

SCENE1

SCENE2

Set time

Stop

ON

OFF

SCENE1

SCENE2

Set time

Stop

SW104-3:  OFF

SW104-3:  ON

10. ABOUT SWITCH SETTING

To set multiple settings to the same switch, switch combinations are listed at 
the bottom of the next page. Write down switch setting examples before use.

11. EXAMPLE SETTING

(1) Example setting 1

•  Insert card key and set to COOL, temperature 23°C, Fan speed: Hi, 

 remove card key and set to COOL, temperature 30°C, Fan speed: Lo. 

  (For speci

fi

 cations where inserting the card key 

turns the contact 

 ON, and 

 removing it turns the contact OFF)
 Use the unit by connecting the card key to CH1, and nothing to CH2.

Setting

SW No.

SW setting

Function

Mode

SW104-1

ON

Mode1

OFF output

SW104-2

OFF

Disabled

Polarity

SW104-3

OFF

No function

SW104-4

OFF

ON 

 OFF SCENE3

OFF 

 ON SCENE4

CH2 setting

EXIN

0

Operation stop

SCENE

Setting

SW No.

SW setting

Function

SCENE1

Operation 

stop

SW107-1/2

OFF/OFF

No change

Fan speed

SW107-3/4

ON/ON

Lo

Operation 

mode

SW108-1/2

ON/OFF

COOL

All operation

SW108-3/4

OFF/OFF

No change

Set tempera-

ture 1

SW111-

1/2/3/4

ON/ON/

ON/ON

30°C (88°F)

Set tempera-

ture 2

SW112-

1/2/3/4

OFF/OFF/

OFF/OFF

No change

SCENE2

Operation 

stop

SW105-1/2

OFF/OFF

No change

Fan speed

SW105-3/4

ON/OFF

Hi

Operation 

mode

SW106-1/2

ON/OFF

COOL

All operation

SW106-3/4

OFF/OFF

No change

Set tempera-

ture 1

SW109-

1/2/3/4

OFF/OFF/

OFF/ON

23°C (74°F)

Set tempera-

ture 2

SW110-

1/2/3/4

OFF/OFF/

OFF/OFF

No change

(2) Example setting 2

•  When a window is opened, operation stop + remote controller opera-

tion prohibited, return to original state when the window is closed.

  (For speci

fi

 cations where contact OFF when the window is opened, and 

 contact ON when the window is closed)
 Use the unit by connecting the window switch to CH1, and nothing to CH2.
*  Only possible when non-polar 2 core remote controller is connected, with 

 remote controller prohibition set to “Ineffective”.

Setting

SW No.

SW setting

Function

Mode

SW104-1

ON

Mode1

OFF output

SW104-2

OFF

Disabled

Polarity

SW104-3

OFF

No function

SW104-4

OFF

ON 

 OFF SCENE3

OFF 

 ON SCENE4

CH2 setting

EXIN

0

Operation stop

SCENE

Setting

SW No.

SW setting

Function

SCENE1

Operation stop

SW107-1/2

ON/OFF

Stop

Fan speed

SW107-3/4

OFF/OFF

No change

Operation mode SW108-1/2

OFF/OFF

No change

All operation

SW108-3/4

OFF/ON

Enabled

Set temperature 

1

SW111-

1/2/3/4

OFF/OFF/

OFF/OFF

No change

Set temperature 

2

SW112-

1/2/3/4

OFF/OFF/

OFF/OFF

No change

SCENE2

Operation stop

SW105-1/2

ON/ON

SETBACK

Fan speed

SW105-3/4

OFF/OFF

No change

Operation mode SW106-1/2

OFF/OFF

No change

All operation

SW106-3/4

OFF/OFF

No change

Set temperature 

1

SW109-

1/2/3/4

OFF/OFF/

OFF/OFF

No change

Set temperature 

2

SW110-

1/2/3/4

OFF/OFF/

OFF/OFF

No change

(3) Example setting 3

• When inserting card key
  If the indoor unit operation mode is COOL, operation ON, set 
  temperature 

26°C (80°F)

  If the indoor unit operation mode is HEAT, operation ON, set 
  temperature 

20°C (68°F)

• Removing the card key
  If the indoor unit operation mode is COOL, set temperature 

30°C (88°F)

  If the indoor unit operation mode is HEAT, set temperature 

16°C (60°F)

Then set operation stop after 3 hours

When connecting the card key to CH1, and nothing to CH2
Inserting the card key makes the contact ON, and removing it makes it OFF

9374707157-02_IM.indb   9

9374707157-02_IM.indb   9

12/2/2016   5:22:46 PM

12/2/2016   5:22:46 PM

Summary of Contents for UTY-TERX

Page 1: ...ONTROLLER For authorized service personnel only 安装说明书 安装说明书 外部开关控制器 仅针对授权的专业维修人员 English 中 文 中 文 PART NO 9374707157 02 Original instructions UTY TERX 9374707157 02_IM indb i 9374707157 02_IM indb i 12 2 2016 5 22 43 PM 12 2 2016 5 22 43 PM ...

Page 2: ...ntive measures so that they cannot reach the unit CAUTION This mark indicates procedures which if improp erly performed might possibly result in personal harm to the user or damage to property Pay abundant care when transporting this unit because it is a precision device Improper transportation will cause trouble Do not touch the switches with sharp objects Doing so will cause injury trouble or el...

Page 3: ...er supply cable connection cable and remote controller cable 1 m 40 in away from television and radio to avoid distorted images and noise Otherwise a malfunction could result Perform wiring so that water does not enter this unit along the external wiring Always install a trap to the wiring or take other countermeasures Otherwise it will cause trouble or electric shock or fire Confirm the name of e...

Page 4: ...controller Y1 Y2 Y3 External input EXIN1 EXIN2 0 5 to 0 6 N m 4 4 to 5 3 lbf in 5 to 6 kgf cm 5 1 Wiring method Indoor unit VRF single multi Wired remote controller Wired remote controller cable This product External input cable Card key Window switch Connectable types of indoor unit and remote controller The wired remote controller shown in the table below can be connected The indoor unit that ca...

Page 5: ...e DIP switches Before opening the cover of this unit completely discharge static electric ity charged on your body Otherwise failure or malfunction could result Do not touch the circuit board and circuit board parts directly with your hands Otherwise injury or electric shock could result Tightening the mounting screws too tight will damage the body of this unit 6 1 Connecting the cables 1 Turn off...

Page 6: ...connection method is differ ent depending on each model Modify the remote controller cable as per below description and connect it For the details refer to the installation manual of the indoor unit to be used 1 When connecting to the connector Case 1 For non polar 2 wire Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of...

Page 7: ...le is 50m 164 ft 9 CIRCUIT BOARD SETTING The circuit board has a rotary switch DIP switch and LED as shown below 1 About connections 1 1 2WIRE 3WIRE settings SET3 Remote controller 2WIRE 3WIRE switching SW Default 2WIRE Set matched with the connection method of the remote controller cable to be connected 1 2 Master settings SET 2 1 When setting the SET3 to 3WIRE DIP SW OFF ON SET 2 1 Master Slave ...

Page 8: ... Mode 1 SW104 1 1 Polarity setting SW104 3 4 DIP SW Setting OFF ON SW104 3 No function Fixed to OFF SW104 4 CH2 external switch detection condition ON OFF is SCENE3 OFF ON is SCENE4 OFF ON is SCENE3 ON OFF is SCENE4 Factory setting 2 Rotary switch setting EXIN Rotary switch setting value Setting SCENE3 SCENE4 0 Operation stop Operation Stop 1 Remote controller pro hibition all operation All operat...

Page 9: ... If operation mode is set to No change 2 the operation mode is not changed If this scene is run 1 If operation mode is COOL or DRY the set temperature will be changed to set temperature 1 2 If operation mode is HEAT the set temperature will be changed to set temperature 2 3 If operation mode is AUTO or fan the set temperature is not changed Remote controller prohibition all operation SW108 3 4 SCE...

Page 10: ...speed SW105 3 4 ON OFF Hi Operation mode SW106 1 2 ON OFF COOL All operation SW106 3 4 OFF OFF No change Set tempera ture 1 SW109 1 2 3 4 OFF OFF OFF ON 23 C 74 F Set tempera ture 2 SW110 1 2 3 4 OFF OFF OFF OFF No change 2 Example setting 2 When a window is opened operation stop remote controller opera tion prohibited return to original state when the window is closed For specifications where con...

Page 11: ...h settings method refer to the installation instruction sheet of each unit 3 Turn on the power for the VRF system or multi system or single model 4 Power will be supplied from the system to the convertor This product will be initialized and the power turned on LED1 green and LED2 orange will flash After initial setting is completed operation will be restarted auto matically LED1 green lights This ...

Reviews: