background image

En-6

Case 2:  For polar 3 wire

Modify the cable as per below methods.

Use a tool to cut off the terminal on the end of the remote controller 
cable, and then remove the insulation from the cut end of the cable as 
shown in Fig. 1.
Connect the remote controller cable and connecting cable as shown in 
Fig. 2.
Be sure to insulate the connection between the cables.

Fig. 1

Fig. 2

Remote 

controller cable

White

Red

Red

White

Connector

Black

Black

Insulated con-

nection

Connecting 

cable

Fig. 1

Fig. 2

Connect the remote controller cable to the connecting cable, and insert it 
to the connector.

PCB

Connecting cable

Connector

Terminal block 

to outdoor unit / 

power supply

Remote controller cable

Indoor unit

PCB

When the board has the 2WIRE/3WIRE DIP switch on it, set it to 
3WIRE.
For how to set, see “Case 1:   For non-polar 2 wire”.

(2) 

When connecting to the exclusive terminal block

 

Connect the end of remote controller cable directly to the exclusive 
terminal block. 

If there is the 2WIRE/3WIRE switch on the PC board of the indoor unit, 
set it to match the connection method of the connected remote control-
ler cable.

Example) Connection of non-polar 2 wire

*  Layout of terminal block and 

PC board is varies, depending 

on the type of indoor unit.

Terminal block

Functional earthing 

(If necessary)

Remote controller 

cable

Set to “2WIRE” the 
DIP switch (SW1)

Indoor unit 

PC board

8.  CONNECTION OF EXTERNAL INPUT CABLE

When the switch is connected.

Switch

Switch

This product

Select low current use contacts (usable at DC5V, DC2mA or less).

Short circuit detection resistance (R ON): 

 500 (

Ω

).

Open circuit detection resistance (R OFF): 

 100 (k

Ω

).

A twister pair cable 0.33~1.25 mm² (16~22AWG) should be use.
Maximum length of cable is 50m (164 ft).

9.  CIRCUIT BOARD SETTING

The circuit board has a rotary switch, DIP switch and LED as shown 
below.

(1) 

About connections

 

(1-1) 2WIRE/3WIRE settings (SET3)

Remote controller 2WIRE/3WIRE switching SW

“Default:  2WIRE”

Set matched with the connection method of the remote controller cable to be connected.

(1-2) Master settings (SET 2-1 When setting the SET3 to 3WIRE)

DIP SW

OFF  

ON

SET 2-1

Master

Slave

(

:  Factory setting)

Enabled only when setting the SET3 to 3WIRE
Set when using with a remote controller or other external switch controller.
When using with a remote controller, set the remote controller to “Master” 
and the external switch controller to “Slave”.
When using two external switch controllers, set one to “Master” and the other 
one to “Slave.”

(1-3) Response speed setting (SET 2-2)

DIP SW

OFF  

ON

SET 2-2

Instant

(200ms)

Delay

(1min)

(

:  Factory setting)

Set the time for the signal to be output from the controller after changing the 
external switch.

(2) 

About external switch controller operating prohibition

 

(2-1) Remote controller prohibition setting (SET 2-3)

DIP SW

OFF  

ON

SET 2-3

Remote controller prohibition 

ineffective

Remote controller prohibition 

effective

(

:  Factory setting)

If there is a prohibition from the central control unit, this setting determines 
whether or not there is a prohibition for the external switch controller operation.

(2-2) 

Operation condition setting (

SET 2-4)

DIP SW

OFF  

ON

SET 2-4

Unconditional

When indoor unit operating 

only

(

:  Factory setting)

Determines whether or not operation of the indoor unit is set as an operation 
condition for the external switch controller.

SCENE1

×

Indoor unit

CH1

OFF

ON

Operation condition: when indoor unit operating only

ON

OFF

 Output from “Remote controller prohibition all operation” is generated 
regardless the operation condition setting.

9374707157-02_IM.indb   6

9374707157-02_IM.indb   6

12/2/2016   5:22:46 PM

12/2/2016   5:22:46 PM

Summary of Contents for UTY-TERX

Page 1: ...ONTROLLER For authorized service personnel only 安装说明书 安装说明书 外部开关控制器 仅针对授权的专业维修人员 English 中 文 中 文 PART NO 9374707157 02 Original instructions UTY TERX 9374707157 02_IM indb i 9374707157 02_IM indb i 12 2 2016 5 22 43 PM 12 2 2016 5 22 43 PM ...

Page 2: ...ntive measures so that they cannot reach the unit CAUTION This mark indicates procedures which if improp erly performed might possibly result in personal harm to the user or damage to property Pay abundant care when transporting this unit because it is a precision device Improper transportation will cause trouble Do not touch the switches with sharp objects Doing so will cause injury trouble or el...

Page 3: ...er supply cable connection cable and remote controller cable 1 m 40 in away from television and radio to avoid distorted images and noise Otherwise a malfunction could result Perform wiring so that water does not enter this unit along the external wiring Always install a trap to the wiring or take other countermeasures Otherwise it will cause trouble or electric shock or fire Confirm the name of e...

Page 4: ...controller Y1 Y2 Y3 External input EXIN1 EXIN2 0 5 to 0 6 N m 4 4 to 5 3 lbf in 5 to 6 kgf cm 5 1 Wiring method Indoor unit VRF single multi Wired remote controller Wired remote controller cable This product External input cable Card key Window switch Connectable types of indoor unit and remote controller The wired remote controller shown in the table below can be connected The indoor unit that ca...

Page 5: ...e DIP switches Before opening the cover of this unit completely discharge static electric ity charged on your body Otherwise failure or malfunction could result Do not touch the circuit board and circuit board parts directly with your hands Otherwise injury or electric shock could result Tightening the mounting screws too tight will damage the body of this unit 6 1 Connecting the cables 1 Turn off...

Page 6: ...connection method is differ ent depending on each model Modify the remote controller cable as per below description and connect it For the details refer to the installation manual of the indoor unit to be used 1 When connecting to the connector Case 1 For non polar 2 wire Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of...

Page 7: ...le is 50m 164 ft 9 CIRCUIT BOARD SETTING The circuit board has a rotary switch DIP switch and LED as shown below 1 About connections 1 1 2WIRE 3WIRE settings SET3 Remote controller 2WIRE 3WIRE switching SW Default 2WIRE Set matched with the connection method of the remote controller cable to be connected 1 2 Master settings SET 2 1 When setting the SET3 to 3WIRE DIP SW OFF ON SET 2 1 Master Slave ...

Page 8: ... Mode 1 SW104 1 1 Polarity setting SW104 3 4 DIP SW Setting OFF ON SW104 3 No function Fixed to OFF SW104 4 CH2 external switch detection condition ON OFF is SCENE3 OFF ON is SCENE4 OFF ON is SCENE3 ON OFF is SCENE4 Factory setting 2 Rotary switch setting EXIN Rotary switch setting value Setting SCENE3 SCENE4 0 Operation stop Operation Stop 1 Remote controller pro hibition all operation All operat...

Page 9: ... If operation mode is set to No change 2 the operation mode is not changed If this scene is run 1 If operation mode is COOL or DRY the set temperature will be changed to set temperature 1 2 If operation mode is HEAT the set temperature will be changed to set temperature 2 3 If operation mode is AUTO or fan the set temperature is not changed Remote controller prohibition all operation SW108 3 4 SCE...

Page 10: ...speed SW105 3 4 ON OFF Hi Operation mode SW106 1 2 ON OFF COOL All operation SW106 3 4 OFF OFF No change Set tempera ture 1 SW109 1 2 3 4 OFF OFF OFF ON 23 C 74 F Set tempera ture 2 SW110 1 2 3 4 OFF OFF OFF OFF No change 2 Example setting 2 When a window is opened operation stop remote controller opera tion prohibited return to original state when the window is closed For specifications where con...

Page 11: ...h settings method refer to the installation instruction sheet of each unit 3 Turn on the power for the VRF system or multi system or single model 4 Power will be supplied from the system to the convertor This product will be initialized and the power turned on LED1 green and LED2 orange will flash After initial setting is completed operation will be restarted auto matically LED1 green lights This ...

Reviews: