Returning the Server to Operation
179
Note –
As soon as the power cords are connected, standby power is applied.
Depending on how the firmware is configured, the system might boot at this time.
Related Information
■
“Power On the Server Using the
■
“Power On the Server Using the Front Panel Power Button” on page 180
▼
Power On the Server Using the
poweron
Command
Note –
If you are powering on the server following an emergency shutdown that
was triggered by the top cover interlock switch, you must use the
poweron
command.
●
Type
poweron
at the service processor prompt.
You will see an
->
Alert message on the system console. This message indicates
that the system is reset. You will also see a message indicating that the VCORE has
been margined up to the value specified in the default
.scr
file that was
previously configured. For example:
Related Information
■
“Power On the Server Using the Front Panel Power Button” on page 180
->
poweron
->
start /SYS