1-8. Setting the Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the
room temperature sensor may be required.
Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from
the Standard setting "00"
(manufacturer's recommended value).
Setting Description
Function Number
Setting Value
Standard setting
-1°F (-0.5°C)
-2°F (-1.0°C)
-4°F (-2.0°C)
-3°F (-1.5°C)
-5°F (-2.5°C)
-6°F (-3.0°C)
-7°F (-3.5°C)
-8°F (-4.0°C)
+1°F (+0.5°C)
+2°F (+1.0°C)
+3°F (+1.5°C)
+4°F (+2.0°C)
+5°F (+2.5°C)
+6°F (+3.0°C)
+7°F (+3.5°C)
+8°F (+4.0°C)
No correction 0.0°F (0.0°C)
00
01
02
03
04
05
06
07
08
09
10
11
12
13
15
14
16
17
30
(For
cooling)
31
(For
heating)
More
Cooling
Less
Heating
Less
Cooling
More
Heating
)
( Factory setting
When Function 95-01(High insulation) is set, the Standard setting "00" will be
the same as No correction "01" [0.0°F(0.0°C)].
Temperature Correction
When changing Function 95, perform this setting before other Room temp.
control settings (Function 30, 31, 92, 93).
If Function 95 is not set fi rst, Room temperature control settings (Function 30, 31, 92, 93)
ill be reset and you must re-do them again.
Heat insulation conditions differ according to the installed environment.
Standard insulation "00" allows system to rapidly respond to the cooling or heating load changes.
High insulation "01" is when the heat insulation structure of the building is
high and does not require
system to rapidly respond to cooling or heating load changes. When High insulation "01" is selected;
Overheating (overcooling) is prevented at the start-up.
All room temp. control settings (Function 30, 31, 92, 93) will reset to No correction [0.0°F (0.0°C)].
)
Setting Description
Function Number
Setting Value
Standard insulation
95
00
01
( Factory setting
High insulation
1-7. Setting the
Heat Insulation condition (building insulation)
03-03
Summary of Contents for R410A
Page 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 23: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Page 63: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Page 76: ...Jan 2016 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...