Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : ASU24RLF
[Condition]
Ambient temperature : Indoor / Outdoor - Same temperature
Refrigerant amount : Standard amount
Piping length : 7.5m (Height difference 1m)
Power voltage : 60Hz - 230V
Operation condition : TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring method : Measure the low pressure with the pressure meter at the service valve.
Caution : Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Cooling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
Measure the outdoor unit overall current with the current clamp meter at Power Cable.
59
(15)
68
(20)
77
(25)
86
(30)
95
(35)
RH70%
RH60%
RH50%
In/Outdoor ambient temperature
7.0
7.5
8.0
8.5
9.0
9.5
10.0
Outdoor total electric current [A]
In/Outdoor ambient temperature
[
°F
]
(
°C)
[
°F
]
(
°C)
59
(15)
68
(20)
77
(25)
86
(30)
95
(35)
RH70%
RH60%
RH50%
(0.7)
(0.8)
(0.9)
(1.0)
(1.1)
(1.2)
Low-pressure of outdoor unit
(1.3)
101.5
116.0
130.5
145.0
159.5
174.1
188.5
(MPa) [psi]
03-09
Summary of Contents for R410A
Page 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 23: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Page 63: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Page 76: ...Jan 2016 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...