1-9 .
Setting the Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor may be required.
Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both "01".
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Setting Description
Function Number
Setting Value
No correction 0.0°F (0.0°C)
-1°F (-0.5°C)
-2°F (-1.0°C)
-4°F (-2.0°C)
-3°F (-1.5°C)
-5°F (-2.5°C)
-6°F (-3.0°C)
-7°F (-3.5°C)
-8°F (-4.0°C)
+1°F (+0.5°C)
+2°F (+1.0°C)
+3°F (+1.5°C)
+4°F (+2.0°C)
+5°F (+2.5°C)
+6°F (+3.0°C)
+7°F (+3.5°C)
+8°F (+4.0°C)
No correction 0.0°F (0.0°C)
00
01
02
03
04
05
06
07
08
09
10
11
12
13
15
14
16
17
92
(For
cooling)
93
(For
heating)
More
Cooling
Less
Heating
Less
Cooling
More
Heating
)
( Factory setting
03-04