8. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the Table 10.
Cooling
Heating
Min
Max
Min
Max
Min
Max
Dry
AOU18RLXFW1
AOU24RLXFW1
12rps
55rps
14rps
67rps
15rps
25rps
16rps
72rps
16rps
90rps
16rps
29rps
( Table 10 : Compressor operation frequency range )
2. OPERATION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in the Fig 9.
( Fig. 9 : Compressor Control at Start-up )
3. LIMITATION OF COMPRESSOR FREQUENCY BY OUTDOOR TEMPERATURE
The minimum compressor frequency is limited by outdoor temperature as shown in the Table 11.
( Table 11 : Limitation of compressor frewuency )
[ Cooling/ Dry ]
AOU18RLXFW1
[ Heating ]
30rps
60sec
47rps
60rps
120sec
180sec
01-08
32°F (0°C)
14°F (-10°C)
100°F (38°C)
50°F (10°C)
Under
40rps
Over
Under
Over
Under
Over
Under
Over
25rps
25rps
12rps
25rps
16rps
32rps
Under
Over
AOU24RLXFW1
32°F (0°C)
14°F (-10°C)
100°F (38°C)
50°F (10°C)
Under
40rps
Over
Under
Over
Under
Over
Under
Over
25rps
32rps
Under
Over
AOU18RLXFW1
44.6°F (7°C)
14°F (-10°C)
Under
40rps
Over
Under
Over
16rps
25rps
Under
Over
AOU24RLXFW1
34°F (1°C)
46.4°F (8°C)
14°F (-10°C)
Under
40rps
Over
Under
Over
25rps
Under
Over
Under
Over
19rps
16rps
Summary of Contents for R410A
Page 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 23: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Page 63: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Page 76: ...Jan 2016 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...