Trouble shooting 6
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
OK
OK
OK
OK
12.6
20.7
26.9
35.2
46.6
62.3
115
Resistance Value (k )
16.1
Temperature
3.45
2.36
1.65
Resistance Value (k )
5.18
7.97
Temperature
Outdoor Temperature Sensor Error
Outdoor Unit Main PCB Circuit
Outdoor Temperature Thermistor
When Outdoor Temperature Thermistor open or short-circuit is
detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
06-10
Outdoor Unit : LED 0.1sec ON/ 0.1sec OFF
Indoor Unit : Operation LED : 3 times, Timer LED : 4 times
ERROR CODE : [E : 0A]
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
BLACK
CN62
CN61
3 2 1
4 3 2 1
BROWN
BLACK
3 2 1
4 3 2 1
23
°F
(-5
°C)
14
°F
(-10
°C)
158
°F
(70
°C)
140
°F
(60
°C)
86
°F
(
30
°C)
68
°F
(20
°C)
59
°F
(15
°C)
50
°F
(10
°C)
41
°F
(5
°C)
32
°F
(0
°C)
122
°F
(
50
°C)
104
°F
(
40
°C)
-4
°F
(-20
°C)
Summary of Contents for Inverter Halcyon AOU12RL
Page 1: ... Manuel d instruction www lutechenergie com ...
Page 5: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 12: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 33: ...6 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Page 74: ...8 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 82: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Mar 2009 Printed in Japan ...