22. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
ASU9 / 12RL
219°F(104°C)
214°F(101°C)
230°F(110°C)
When the discharge temperature becomes higher than Temperature ,the compressor frequency
is decreased 20 Hz, and it continues to decrease the frequency for 20 Hz every 120 seconds until
the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature ,the control of the control of the
compressor frequency is released.
When the discharge temperature becomes higher than Temperature ,the compressor is stopped
and the indoor unit LED starts blinking.
(Table 17 : Discharge Temperature Over Rise Prevension Control / Release Temperature)
Temperature
Temperature
Temperature
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit velue that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
(Table 18 : Current Release Operation Value / Release Value)
05-17
[ Heating ]
OT (Control / Release)
5.5A/ 5.0A
6.0A/ 5.5A
7.0A/ 6.5A
7.0A/ 6.5A
5.5A/ 5.0A
7.0A/ 6.5A
7.5A/ 7.0A
8.5A/ 8.0A
63
°F
(17
°
C)
54
°F
(12
°
C)
OT : Outdoor Temperature
41
°F
(
5
°
C)
ASU9RL
OT (Control / Release)
63
°F
(17
°
C)
54
°F
(
12
°
C)
OT : Outdoor Temperature
41
°F
(5
°
C)
ASU12RL
OT (Control / Release)
3.5A/ 3.0A
4.0A/ 3.5A
5.5A/ 5.0A
4.0A/ 3.5A
5.0A/ 4.5A
6.0A/ 5.5A
115
°F
(46
°
C)
108
°F
(42
°
C)
OT : Outdoor Temperature
ASU9RL
OT (Control / Release)
115
°F
(46
°
C)
108
°F
(42
°
C)
OT : Outdoor Temperature
ASU12RL
[ Cooling ]
Summary of Contents for Inverter Halcyon AOU12RL
Page 1: ... Manuel d instruction www lutechenergie com ...
Page 5: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 12: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 33: ...6 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Page 74: ...8 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 82: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Mar 2009 Printed in Japan ...