2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower by 6
°F(3°C)
than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is higher 5
°F(2.5°C)
than a set temperatire, the compressor will be
stopped.
* When the room temperature is between
+5°F(+2.5°C)
to -6
°F(-3°C)
of the setting temperature,
the compressor frequency is controlled within the range shown in Table2.
However, the maximum frequency is limited in the range shown in Figure 2 based on the
fan speed mode and the outdoor temperature.
( Table 2 : Compressor Frequency Range )
( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )
* The room temperature is controlled 4
°F(2°C)
higher than the setting temperature for 60 minutes
after starting the operation.
After 60 minutes, it is controlled based on the normal setting temperature.
05-02
minimum
frequency
maximum
frequency
ASU9RL
22Hz
99Hz
ASU12RL
18Hz
130Hz
Hi
Me+
Lo
Quiet
AA zone
99Hz
99Hz
79Hz
70Hz
A zone
99Hz
99Hz
79Hz
70Hz
B zone
99Hz
99Hz
79Hz
58Hz
9RL
C zone
AA zone
A zone
B zone
C zone
99Hz
99Hz
79Hz
49Hz
130Hz
130Hz
80Hz
64Hz
130Hz
130Hz
80Hz
64Hz
130Hz
130Hz
80Hz
51Hz
130Hz
130Hz
Me
90Hz
90Hz
90Hz
90Hz
105Hz
105Hz
105Hz
105Hz
80Hz
42Hz
12RL
Outside air Outside air
temperature temperature
66°F
(19°C)
C zone
B zone
A zone
AA zone
63°F
(17°C)
57°F
(14°C)
53°F
(12°C)
45°F
(7°C)
41°F
(5°C)
Summary of Contents for Inverter Halcyon AOU12RL
Page 1: ... Manuel d instruction www lutechenergie com ...
Page 5: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 12: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 33: ...6 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Page 74: ...8 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 82: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Mar 2009 Printed in Japan ...