Trouble shooting 5
OUTDOOR UNIT Error Method:
Indicate or Display:
Outdoor Unit : LED 0.1sec ON/ 0.1sec OFF
Indoor Unit : Operation LED : 3 times, Timer LED : 3 times
ERROR CODE : [E : 06]
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
4.77
5.98
7.56
9.63
12.4
16.1
21.0
27.8
Resistance Value (k )
23
°F
(-5
°C)
14
°F
(-10
°C)
Temperature
OK
OK
OK
OK
DC
3.84
0.446
194
°F
(90
°C)
0.606
176
°F
(80
°C)
0.840
1.19
1.71
2.08
2.53
3.11
Resistance Value (k )
158
°F
(70
°C)
140
°F
(60
°C)
Temperature
0.333
212
°F
(100
°C)
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
BLACK
CN62 CN61
3 2 1
4 3 2 1
BLACK
BLACK
Outdoor Heat Exchanger Temperature
Sensor (Outlet) Error
Outdoor Unit Main PCB Circuit
Heat Exchanger Temperature Thermistor
When Heat Exchanger Temperature Thermistor (Outlet) open or
short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
06-09
3 2 1
4 3 2 1
95
°F
(35
°C)
86
°F
(
30
°C)
77
°F
(
25
°C)
68
°F
(20
°C)
59
°F
(15
°C)
50
°F
(10
°C)
41
°F
(5
°C)
32
°F
(0
°C)
122
°F
(
50
°C)
113
°F
(45
°C)
104
°F
(
40
°C)
Summary of Contents for Inverter Halcyon AOU12RL
Page 1: ... Manuel d instruction www lutechenergie com ...
Page 5: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 12: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 33: ...6 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Page 74: ...8 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 82: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Mar 2009 Printed in Japan ...