background image

En-6

4.4. Installing heat insulation

 

CAUTION

After checking for gas leaks (refer to the Installation Manual of the outdoor unit), 

perform this section.

Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do 

so may cause water leaks.

After checking for gas leaks, insulate by wrapping insulation around the two parts (gas 
and liquid) of the indoor unit coupling, using the Coupler Heat Insulation.
After installing the Coupler Heat Insulation, wrap both ends with vinyl tape so that there is 
no gap.

Coupler heat insulation

No gap

Coupler heat 
insulation

Body

Be sure to overlap the 
insulation

 

CAUTION

Must 

fi

 t tightly against body without any gap.

5.  INSTALLING DRAIN HOSE

Install the drain hose according to the measurements given in the following 

fi

 gure.

(Left side)

(Right side)

Liquid pipe

Drain pipe 

 38 mm (O.D.)

Gas pipe

Drain pipe 

 38 mm (O.D.)

The drain cap is attached 
at the factory setting.

Unit : mm

 

CAUTION

Install the drain hose in accordance with the instructions in this Installation Manual and 
keep the area warm enough to prevent condensation. Problems with the piping may 
lead to water leaks.

NOTE:

Install the drain hose.

Install the drain hose with downward gradient (1/50 to 1/100) and so there are no rises or 

• 

traps in the hose.

Use general hard polyvinyl chloride pipe (VP25) [outside diameter 38 mm] and connect it 

• 

with adhesive (polyvinyl chloride) so that there is no leakage.

When the hose is long, install supporters.

• 

Do not perform air bleeding.

• 

Always heat insulate the indoor side of the drain hose.

• 

Outlet 
air 

fl

 ow

Drain 
hose

Trap

Arrange the drain hose lower 
than this portion.

Rise

Air bleeding

Supporter

GOOD

PROHIBITED

PROHIBITED

PROHIBITED

1.5 to 2 m

When the unit is shipped from the factory, the drain port is on the left side (control box side).

• 

When using the drain port on the right side of the unit, reinstall the drain cap to the left 

• 

side drain port.

Drain port

Drain cap

Cable tie

 

CAUTION

Always check that the drain cap is installed to the unused drain port and is fastened 
with the Cable tie.
If the drain cap is not installed, or is not suf

fi

 ciently fastened by the Cable tie, water 

may drip during the cooling operation.

Cut the drain hose insulation at a position approximately 80 mm from the end with 

• 

cutters, etc.
Stick the large drain hose insulation at the drain hose installation side.

• 

Stick the small drain hose insulation at the drain cap side.

• 

Drain hose 
insulation 
(large)

Drain hose

Drain hose insulation (small)

Drain hose 
insulation 
(small)

Drain hose

Drain hose 
insulation 
(large)

Drain cap

unit

unit

Unit

Unit

Unit : mm

Cut line

Cover the drain cap with the drain hose insulation.

• 

9379127035-02_IM.indb   Sec1:6

9379127035-02_IM.indb   Sec1:6

23/01/2013   16:25:42

23/01/2013   16:25:42

Summary of Contents for INDOOR UNIT (Duct Type) AIR CONDITIONER

Page 1: ... Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir PART NO 9379127035 02 AIR...

Page 2: ... prevent erroneous mixing of other refrigerants the diameter of each port has been changed It is recommended to use a gauge manifold with a high pressure display range 0 1 to 5 3 MPa and a low pressure display range 0 1 to 3 8 MPa Charging hose To increase pressure resistance the hose material and base size were changed Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump...

Page 3: ...portant for the split type air conditioner be cause it is very difficult to move from place to place after the first installation WARNING Select installation locations that can properly support the weight of the indoor Install the units securely so that they do not topple or fall CAUTION Do not install the unit in the following areas Area with high salt content such as at the seaside It will deter...

Page 4: ... units and filter Maintenance hole Intake panel Control box Unit mm 3 3 Installation the unit WARNING Install the air conditioner in a location which can withstand a load do at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries If the job is done with the panel frame o...

Page 5: ... the round flange and square flange when con necting the duct CAUTION Check that duct work does not exceed the range of external static pressure of equipment Make sure to insulate ducts to avoid the dew condensation Make sure to insulate between ducts and walls if metal ducts are used Please explain handling and washing methods of locally purchased materials to the customer To prevent people from ...

Page 6: ...o 42 320 to 420 12 70 1 2 dia 49 to 61 490 to 610 15 88 5 8 dia 63 to 75 630 to 750 19 05 3 4 dia 90 to 110 900 to 1 100 Thicknesses of Annealed Copper Pipes R410A Pipe outside diameter mm in Thickness mm 6 35 1 4 0 80 9 52 3 8 0 80 12 70 1 2 0 80 15 88 5 8 1 00 19 05 3 4 1 20 4 2 Pipe requirement CAUTION Refer to the Installation Manual of the outdoor unit for description of the length of connect...

Page 7: ...nd so there are no rises or traps in the hose Use general hard polyvinyl chloride pipe VP25 outside diameter 38 mm and connect it with adhesive polyvinyl chloride so that there is no leakage When the hose is long install supporters Do not perform air bleeding Always heat insulate the indoor side of the drain hose Outlet air flow Drain hose Trap Arrange the drain hose lower than this portion Rise A...

Page 8: ...a earth leakage breaker In addition install the earth leakage breaker so that the entire AC main power supply is cut off at the same time Otherwise electric shock or fire could result Always connect the earth cable Improper grounding work can cause electric shocks Install the remote controller cables so as not to be direct touched with your hand Perform wiring work in accordance with standards so ...

Page 9: ...t Check local electrical rules and also any specific wiring instructions or limitation 6 2 Connection cable preparation Keep the earth ground wire longer than the other wires Power supply cable or connection cable 20 mm 50mm or more Earth ground wire Use a 4 core wire cable 6 3 Connection of wiring CAUTION Use care not to mistake the power supply cable and connection wires when installing Remove t...

Page 10: ...en installing the front case connect the connector to the front case Screws SET BACK Front case back side Rear case Connector When remote controller cable is concealed 1 Conceal the remote controller cable 2 Pass the remote controller cable through the hole in the rear case and connect the remote controller cable to the remote controller terminal board specified in figure 3 Clamp the remote contro...

Page 11: ... SET button to confirm the setting Press the TIMER SET button for a few seconds until the setting value stops flashing If the setting value display changes or if is displayed when the flashing stops the setting value has not been set correctly An invalid setting value may have been selected for the indoor unit 6 Repeat steps 2 to 5 to perform additional settings Press the SET TEMP buttons and FAN ...

Page 12: ...s remote controllers Factory setting Setting description Function number Setting value A 44 00 B 01 C 02 D 03 8 External input control Operation Stop mode or Forced stop mode can be selected Factory setting Setting description Function number Setting value Operation Stop mode 46 00 Setting forbidden 01 Forced stop mode 02 Setting record Record any changes to the settings in the following table Set...

Page 13: ...main power 8 4 1 Group control system A number of indoor units can be operated at the same time using a single remote controller 1 Wiring method indoor unit to remote controller 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 Indoor unit 1 Bus wire Remote controller cable Remote controller When ground wire is necessary Indoor unit 2 Indoor unit 3 Indoor unit 4 2 DIP switch setting Indoor unit Set the unit number of...

Page 14: ...nnected the outdoor unit using a transmission cable is primary Connect the remote controller wire to the primary unit Twin type Outdoor unit Indoor unit Indoor unit Remote controller primary secondary DIP switch setting Indoor unit 2 Set the unit number of each indoor unit using the DIP switches on the indoor unit circuit board See the following table and figure The DIP switches are normally set t...

Page 15: ...controller while the air conditioner is running Point the transmitter section of the wireless remote controller toward the air conditioner and press the TEST RUN button with the tip of a ball point pen etc Transmitter section TEST RUN button To end test operation press the wireless remote controller START STOP button When the air conditioner is run by pressing the TEST RUN button the OPERATION ind...

Page 16: ...CB model information error 3 5 Manual auto switch error 4 1 Room temp sensor error 4 2 Indoor unit Heat Ex Middle temp sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 15 Indoor unit error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PC...

Reviews: