En-10
.
8. FUNCTION SETTING
CAUTION
Con
fi
rm whether the wiring work for outdoor unit has been
fi
nished.
Con
fi
rm whether the cover for electric control box on the outdoor unit is close.
8.1. Turning on the power
Check the remote controller wiring and DIP switch settings.
(1)
Install the front case.
(2)
When installing the front case, connect the connector to the front case.
Check the indoor and outdoor unit wiring and circuit board
(3)
switch settings, and then turn on the indoor and outdoor units. After “
” has
fl
ashed
on the set temperature display for several seconds, the clock display will appear in the
center of the remote controller display.
The clock display will appear in the center of the remote controller display.
SU MO TU WE TH FR SA
8.2. Function setting
This procedure changes the function settings used to control the indoor unit according to
the installation conditions. Incorrect settings can cause the indoor unit to malfunction. This
procedure should be performed by authorized installation or service personnel only.
Perform the “FUNCTION SETTING” according to the installation conditions using the remote
controller. (Refer to the indoor unit installation manual for details on the function numbers
and setting values.)
(1) Press the SET TEMP. buttons ( ) ( ) and FAN button simultaneously for more than
5 seconds to enter the function setting mode.
SU MO TU WE TH FR SA
(2) Press the SET BACK button to select the indoor unit number.
SU MO TU WE TH FR SA
Unit number of INDOOR UNIT
SET BACK
(3) Press the SET TIME (
) buttons to select the function number.
Function number
SU MO TU WE TH FR SA
(4) Press the SET TEMP. buttons ( ) ( ) to select the setting value.
The display
fl
ashes as shown to the right during setting value selection.
Setting value
SU MO TU WE TH FR SA
(5) Press the TIMER SET button to con
fi
rm the setting.
Press the TIMER SET button for a few seconds until the setting value stops
fl
ashing.
If the setting value display changes or if “- -” is displayed when the
fl
ashing stops, the
setting value has not been set correctly.
(An invalid setting value may have been selected for the indoor unit.)
(6) Repeat steps 2 to 5 to perform additional settings.
Press the SET TEMP. buttons ( ) ( ) and FAN button simultaneously again for
more than 5 seconds to cancel the function setting mode. In addition, the func-
tion setting mode will be automatically canceled after 1 minute if no operation is
performed.
(7) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on
again.
CAUTION
After turning off the power, wait 30 seconds or more before turning on it again. The
FUNCTION SETTING doesn’t become effective if it doesn’t do so.
• Function Details
(1) Filter Sign
The indoor unit has a sign to inform the user that it is time to clean the
fi
lter. Select the
time setting for the
fi
lter sign display interval in the table below according to the amount of
dust or debris in the room. If you do not wish the
fi
lter sign to be displayed, select the set-
ting value for “No indication”.
(
♦
... Factory setting)
Setting description
Function
number
Setting value
Standard (2500 hours)
11
00
Long interval (4400 hours)
01
Short interval (1250 hours)
02
♦
No indication
03
(2) Static pressure
Select appropriate static pressure according to the installation conditions.
(
♦
... Factory setting
)
Setting description
Function
number
Setting value
♦
Normal
21
00
High static pressure 1
01
High static pressure 2
02
High static pressure 3
03
Determine the wind volume in each mode i.e., applicable range of static pressure, refer-
ring to "8.3. Static pressure characteristics." (The unit is factory-set to “00”.)
(3) Cooling room temperature correction
Depending on the installed environment, the room temperature sensor may require a cor-
rection.
The settings may be selected as shown in the table below.
9379127035-02_IM.indb Sec1:10
9379127035-02_IM.indb Sec1:10
23/01/2013 16:25:44
23/01/2013 16:25:44