background image

En-13

Remote 
controller

DIP switch setting 

(Indoor unit)

Standard 

pair

Simultaneous 

twin

Simultaneous 

triple

Remote controller 

setting

Refrigerant circuit 

address setting

Out door 
unit

Out door 
unit

Out door 
unit

Indoor 
unit

Indoor 
unit

Indoor 
unit

Indoor 
unit

Indoor 
unit

Indoor 
unit

Unit number

(Function number 02)

Setting value

Setting value

Primary/Secondary setting

(Function number 51)

Transmission cable, Power supply cable

Remote controller cable

Power supply cable

Bus wire

Make sure that the indoor unit with the unit number 00 is 
connected to the outdoor unit using a transmission cable.

8.4.2. Dual remote controllers 

•  2 separate remote controllers can be used to operate the indoor units.
•  The timer and self-diagnosis functions cannot be used on the secondary units.

(1)  Wiring method (indoor unit to remote controller)

Remote controller cable

Indoor unit

Remote controller

Secondary unit

Primary unit

(2)  Remote controller DIP switch 1 setting
 

Set the remote controller DIP switch 1 No. 2 according to the following table.

 

( Refer to "7.2. Setting the DIP switches.")

Number of remote

controllers

Primary unit

Secondary unit

DIP SW 1 No. 2

DIP SW 1 No. 2

1 (Normal)

OFF

2 (Dual)

OFF

ON

8.4.3. Simultaneous multi-system operation ( 22,24 model )

By combining with an outdoor unit, 2 units for twin indoor units, can be switched ON/OFF 

• 

simultaneously.

Wiring method

(1) 

Refer to 6.ELECTRICAL WIRING for wiring procedure and wiring method.

• 

The indoor unit is connected the outdoor unit using a transmission cable is “primary”.

• 

Connect the remote controller wire to the primary unit.

• 

Twin type

Outdoor 

unit

Indoor 
unit

Indoor 
unit

Remote 
controller

[primary]

[secondary]

DIP switch setting (Indoor unit)

(2) 

Set the unit number of each indoor unit using the DIP switches on the indoor unit 
circuit board. (See the following table and 

fi

 gure.)

The DIP switches are normally set to make the unit number 00.

Indoor unit

Unit number

DIP SWITCH No.

1

2

3

4

1

00

OFF

OFF

OFF

OFF

2

01

ON

OFF

OFF

OFF

3

02

OFF

ON

OFF

OFF

DIP switches

Example : 
Unit number 02

ON

Circuit board in the control box of indoor unit.

NOTE:

Be sure to set the unit numbers sequentially.

Remote controller setting

(3) 

Turn on all of the indoor units.

1. 

Therefore, continue with the setting procedure.

Set the primary and secondary settings.

2. 

Set the indoor unit that is not connected to the outdoor unit using a transmission 
cable as the “01” .
(The setting value is factory-set to “00”.)

Indoor unit

Unit number

Function Number

Setting Value

00

51

00(primary)

01

01(secondary)

 After completing the function settings, turn off all of the indoor units, and then turn 

3. 

them back on.

If error code 21, 22, 24 or 27 is displayed, there may be an incorrect setting. 

Perform the remote controller setting again.

Twin type

Remote 
controller

DIP switch setting 

(Indoor unit)

Remote controller 
setting

Unit number

Unit number

Setting value 
(Primary/secondary)

Out door 

unit

Indoor 

unit 

[primary]

Indoor 

unit 

[secondary]

9. FRESH AIR INTAKE

(Processing before use)

When taking in fresh air, cut a slit shaped cabinet in the left side of the outer case with 

(1) 

nippers.

Cut

Cut

Cabinet (iron plate)

9379127035-02_IM.indb   Sec1:13

9379127035-02_IM.indb   Sec1:13

23/01/2013   16:25:45

23/01/2013   16:25:45

Summary of Contents for INDOOR UNIT (Duct Type) AIR CONDITIONER

Page 1: ... Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir PART NO 9379127035 02 AIR...

Page 2: ... prevent erroneous mixing of other refrigerants the diameter of each port has been changed It is recommended to use a gauge manifold with a high pressure display range 0 1 to 5 3 MPa and a low pressure display range 0 1 to 3 8 MPa Charging hose To increase pressure resistance the hose material and base size were changed Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump...

Page 3: ...portant for the split type air conditioner be cause it is very difficult to move from place to place after the first installation WARNING Select installation locations that can properly support the weight of the indoor Install the units securely so that they do not topple or fall CAUTION Do not install the unit in the following areas Area with high salt content such as at the seaside It will deter...

Page 4: ... units and filter Maintenance hole Intake panel Control box Unit mm 3 3 Installation the unit WARNING Install the air conditioner in a location which can withstand a load do at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries If the job is done with the panel frame o...

Page 5: ... the round flange and square flange when con necting the duct CAUTION Check that duct work does not exceed the range of external static pressure of equipment Make sure to insulate ducts to avoid the dew condensation Make sure to insulate between ducts and walls if metal ducts are used Please explain handling and washing methods of locally purchased materials to the customer To prevent people from ...

Page 6: ...o 42 320 to 420 12 70 1 2 dia 49 to 61 490 to 610 15 88 5 8 dia 63 to 75 630 to 750 19 05 3 4 dia 90 to 110 900 to 1 100 Thicknesses of Annealed Copper Pipes R410A Pipe outside diameter mm in Thickness mm 6 35 1 4 0 80 9 52 3 8 0 80 12 70 1 2 0 80 15 88 5 8 1 00 19 05 3 4 1 20 4 2 Pipe requirement CAUTION Refer to the Installation Manual of the outdoor unit for description of the length of connect...

Page 7: ...nd so there are no rises or traps in the hose Use general hard polyvinyl chloride pipe VP25 outside diameter 38 mm and connect it with adhesive polyvinyl chloride so that there is no leakage When the hose is long install supporters Do not perform air bleeding Always heat insulate the indoor side of the drain hose Outlet air flow Drain hose Trap Arrange the drain hose lower than this portion Rise A...

Page 8: ...a earth leakage breaker In addition install the earth leakage breaker so that the entire AC main power supply is cut off at the same time Otherwise electric shock or fire could result Always connect the earth cable Improper grounding work can cause electric shocks Install the remote controller cables so as not to be direct touched with your hand Perform wiring work in accordance with standards so ...

Page 9: ...t Check local electrical rules and also any specific wiring instructions or limitation 6 2 Connection cable preparation Keep the earth ground wire longer than the other wires Power supply cable or connection cable 20 mm 50mm or more Earth ground wire Use a 4 core wire cable 6 3 Connection of wiring CAUTION Use care not to mistake the power supply cable and connection wires when installing Remove t...

Page 10: ...en installing the front case connect the connector to the front case Screws SET BACK Front case back side Rear case Connector When remote controller cable is concealed 1 Conceal the remote controller cable 2 Pass the remote controller cable through the hole in the rear case and connect the remote controller cable to the remote controller terminal board specified in figure 3 Clamp the remote contro...

Page 11: ... SET button to confirm the setting Press the TIMER SET button for a few seconds until the setting value stops flashing If the setting value display changes or if is displayed when the flashing stops the setting value has not been set correctly An invalid setting value may have been selected for the indoor unit 6 Repeat steps 2 to 5 to perform additional settings Press the SET TEMP buttons and FAN ...

Page 12: ...s remote controllers Factory setting Setting description Function number Setting value A 44 00 B 01 C 02 D 03 8 External input control Operation Stop mode or Forced stop mode can be selected Factory setting Setting description Function number Setting value Operation Stop mode 46 00 Setting forbidden 01 Forced stop mode 02 Setting record Record any changes to the settings in the following table Set...

Page 13: ...main power 8 4 1 Group control system A number of indoor units can be operated at the same time using a single remote controller 1 Wiring method indoor unit to remote controller 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 Indoor unit 1 Bus wire Remote controller cable Remote controller When ground wire is necessary Indoor unit 2 Indoor unit 3 Indoor unit 4 2 DIP switch setting Indoor unit Set the unit number of...

Page 14: ...nnected the outdoor unit using a transmission cable is primary Connect the remote controller wire to the primary unit Twin type Outdoor unit Indoor unit Indoor unit Remote controller primary secondary DIP switch setting Indoor unit 2 Set the unit number of each indoor unit using the DIP switches on the indoor unit circuit board See the following table and figure The DIP switches are normally set t...

Page 15: ...controller while the air conditioner is running Point the transmitter section of the wireless remote controller toward the air conditioner and press the TEST RUN button with the tip of a ball point pen etc Transmitter section TEST RUN button To end test operation press the wireless remote controller START STOP button When the air conditioner is run by pressing the TEST RUN button the OPERATION ind...

Page 16: ...CB model information error 3 5 Manual auto switch error 4 1 Room temp sensor error 4 2 Indoor unit Heat Ex Middle temp sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 15 Indoor unit error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PC...

Reviews: