Self - diagnosis function and Checking points
Error Indication
Operation
(RED)
Timer
(GREEN)
Wired remote
controller
Error
(Protection)
Diagnosis Method
0.5 sec
7 times
The air clean operation signal was detected for 1 minute at the time of air clean mode OFF.
> All stop. Not operate remote controller.
Abnormal current value of IPM is detected.
> Permanent stop.
0.5 sec
4 times
No Display
07
-0
5
CT error
IPM protection
Reverde-VDD permanence
stop protection
(Electric air clean power
supply circuit abnormal)
VDD permanence stop
protection
(Electric air clean)
When the air cleanness monitor trial protection operates 4 times.
> Only clean air permanent stop.
[Diagnosis Point]
The front panel is closed.
The foreign body such as dust doesn't adhere.
[Diagnosis Point]
Electric air clean defective.
Controller PCB defective.
[Diagnosis Point]
Heat radiation is blocked (inlet/outlet).
Check if outdoor fan is defetcive (does not rotate).
Controller PCB defective (Refer to after mentioned "IPM diagnosis").
Refrigeration cycle defective (Refer to after mentioned "refrigeration cycle diagnosis").
The current value during the operation after 1 minute from starting up the compressor is 0A.
> permanent stop.
[Diagnosis Point]
Check if CT wire is open.
Controller PCB defective.
21
17
18
1A
1B
The compressor speed does not synchronze with the control signal. (Including start up failure of the compressor).
> permanent stop.
[Diagnosis Point]
Check if 2-way valve or 3-way valve is left open.
Check the compressor (Winding resistance value, loose lead wire).
Refrigeration cycle defective (Refer to after mentioned "refrigerant cycle diagnosis")
Either the outdoor fan motor abnormal current or location error was detected.
> Permanent stop.
[Diagnosis Point]
Fan motor connector loose/ defective contact.
Fan motor defective.
Controller PCB defective.
Compressor location error
Outdoor fan error
(DC motor)
0.5 sec
8 times
0.5 sec
2 times
0.5 sec
3 times
0.5 sec
5 times
0.5 sec
6 times
0.5 sec
5 times
Summary of Contents for Halcyon AOU12RLQ
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 13: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 16: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 35: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 67: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 68: ...REPLACEMENT PARTS 09 01 Models ASU9RLQ ASU12RLQ ...
Page 69: ...REPLACEMENT PARTS 09 02 Models ASU9RLQ ASU12RLQ ...
Page 70: ...REPLACEMENT PARTS 09 03 Models AOU9RLQ AOU12RLQ ...
Page 71: ...REPLACEMENT PARTS 09 04 Models ASU18CL ASU18RL ...
Page 72: ...REPLACEMENT PARTS 09 05 Models ASU18CL ASU18RL ...
Page 73: ...REPLACEMENT PARTS 09 06 Models ASU18CL ASU18RL ...
Page 78: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 81: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS01012006 JAN 2006 Printed in Japan ...