2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower by 6°F(3°C) than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is higher 5°F(2.5°C) than a set temperatire, the compressor will be
stopped.
minimum
frequency
maximum
frequency
ASU9RLQ
18Hz
130Hz
ASU12RLQ
18Hz
130Hz
ASU18CL
Outside air Outside air
temperature temperature
66°F(19°C)
C zone
63°F(17°C)
57°F(14°C)
B zone
54°F(12°C)
A zone
Hi
Me
Lo
Quiet
A zone
130Hz
96Hz
80Hz
68Hz
B zone
130Hz
96Hz
80Hz
54Hz
9RLQ
C zone
130Hz
96Hz
80Hz
45Hz
A zone
130Hz
96Hz
80Hz
68Hz
B zone
130Hz
96Hz
80Hz
54Hz
12RLQ
C zone
130Hz
96Hz
80Hz
45Hz
A zone
-
-
-
-
B zone
-
-
-
-
18CL
C zone
-
-
-
-
* When the room temperature is b4°F(+2°C) to -6°F(-3°C) of the setting temperature,
the compressor frequency is controlled within the range shown in Table2.
However, the maximum frequency is limited in the range shown in Figure 2 based on the
fan speed mode and the outdoor temperature.
( Table 2 : Compressor Frequency Range )
( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )
* The room temperature is controlled 4°F(2°C) higher than the setting temperature for 60 minutes
after starting the operation.
After 60 minutes, it is controlled based on the normal setting temperature.
05-02
-
-
ASU18RL
18Hz
119Hz
A zone
119Hz
90Hz
70Hz
58Hz
B zone
119Hz
90Hz
70Hz
58Hz
18RL
C zone
119Hz
90Hz
70Hz
58Hz
Summary of Contents for Halcyon AOU12RLQ
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 13: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 16: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 35: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 67: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 68: ...REPLACEMENT PARTS 09 01 Models ASU9RLQ ASU12RLQ ...
Page 69: ...REPLACEMENT PARTS 09 02 Models ASU9RLQ ASU12RLQ ...
Page 70: ...REPLACEMENT PARTS 09 03 Models AOU9RLQ AOU12RLQ ...
Page 71: ...REPLACEMENT PARTS 09 04 Models ASU18CL ASU18RL ...
Page 72: ...REPLACEMENT PARTS 09 05 Models ASU18CL ASU18RL ...
Page 73: ...REPLACEMENT PARTS 09 06 Models ASU18CL ASU18RL ...
Page 78: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 81: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS01012006 JAN 2006 Printed in Japan ...