3. PRECAUTION FOR SERVICING
Feature 1 Refrigerant oil is different from before.
Refrigerant oil for
New Refrigerant
Synthetic oil
Ether
Esther
Different point from
previous one
Previously it was
mineral oil.
Absorbent character
is high.
Contamination occurs
when mixed withe other
kind of oil.
Use the gauge manifold and charge hose
for New Refrigerant(HFC), which shall
be segregated from those of R22.
Attach the stop valve on the vacuum pump
and avoid the oil from reverse frow.
It is necessary to use the vacuum pump
which can obtain the high vacuum condition.
Precaution on Tools
Feature 2 New Refrigerant has Approx 1.6 times higher pressure than previous refrigerant.
R410A
High Pressure
Different point from
previous one
Diameter of Service port
has been changed from
1/4 Flare to 5/16 Flare.
It requires the gauge manifold and charge
hose exclusively for R410A.
It requires the flare tool and torque wrench
that satisfies New JIS standard.
Precaution on Tools
R410A
R22
1.6 times of R22.
JIS standard of flare
process It became lager
To keep thethickness of
copper tube.
(1/4,3/3=more than 0.8mm)
Previous flare tool + flare adapter can be used as well.
06-04
Summary of Contents for Halcyon AOU12RLQ
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 13: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 16: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 35: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 67: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 68: ...REPLACEMENT PARTS 09 01 Models ASU9RLQ ASU12RLQ ...
Page 69: ...REPLACEMENT PARTS 09 02 Models ASU9RLQ ASU12RLQ ...
Page 70: ...REPLACEMENT PARTS 09 03 Models AOU9RLQ AOU12RLQ ...
Page 71: ...REPLACEMENT PARTS 09 04 Models ASU18CL ASU18RL ...
Page 72: ...REPLACEMENT PARTS 09 05 Models ASU18CL ASU18RL ...
Page 73: ...REPLACEMENT PARTS 09 06 Models ASU18CL ASU18RL ...
Page 78: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 81: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS01012006 JAN 2006 Printed in Japan ...