(3). ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger
temperature sensor detects the temperature lower than Temperature .
Then, the anti-freezing control is released when it becomes higher than Temperature .
A-D
E,F
(Table 17 : Anti-freezing Protection Operation / Release Temperature)
Temperature
Temperature
39°F(4°C)
39°F(4°C)
45°F(7°C)
55°F(13°C)
(4). COOLING PRESSURE OVERRISE PROTECTION
(Table 18 : Cooling Pressure Over Rise Protection Function Temperature)
When the outdoor unit heat exchange sensor temperature rises to temperature or greater, the
compressor is stopped and trouble display is performed.
ASU9RLQ
153°F(67°C)
ASU12RLQ
153°F(67°C)
ASU18CL
153°F(67°C)
ASU18RL
153°F(67°C)
Temperature
(5). HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the
detection value of the indoor heat exchanger temperature sensor.
05-18
[ ASU9/12RLQ ]
[ ASU18RL ]
46Hz or greater
45Hz
39Hz or greater
38Hz
39 45Hz
38Hz
26 38Hz 25Hz
19 29Hz 18Hz
18 25Hz OFF
OFF
Indoor heat exchange
temperature
[ Control System ]
Temperature
Temperature
Refer to below
Temperature
Temperature
The compressor frequency is
precisely controlled so that
it does not exceeds Temperature .
It returns to the normal operation
Compressor Operation
18Hz
30
Frequency down every 120 seconds
Frequency down every 120 seconds
ASU9RLQ
131°F(55°C)
ASU12RLQ
131°F(55°C)
ASU18CL
-
ASU18RL
131°F(55°C)
Temp
Temp
Temp
Temp
127°F(53°C)
127°F(53°C)
-
127°F(53°C)
126°F(52°C)
126°F(52°C)
-
126°F(52°C)
122°F(50°C)
122°F(50°C)
-
122°F(50°C)
Summary of Contents for Halcyon AOU12RLQ
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 13: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 16: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 35: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 67: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 68: ...REPLACEMENT PARTS 09 01 Models ASU9RLQ ASU12RLQ ...
Page 69: ...REPLACEMENT PARTS 09 02 Models ASU9RLQ ASU12RLQ ...
Page 70: ...REPLACEMENT PARTS 09 03 Models AOU9RLQ AOU12RLQ ...
Page 71: ...REPLACEMENT PARTS 09 04 Models ASU18CL ASU18RL ...
Page 72: ...REPLACEMENT PARTS 09 05 Models ASU18CL ASU18RL ...
Page 73: ...REPLACEMENT PARTS 09 06 Models ASU18CL ASU18RL ...
Page 78: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 81: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS01012006 JAN 2006 Printed in Japan ...