1-3. Error code table (Indoor unit and wired remote controller)
The operation, timer, and economy indicators operate according to the error contents.
For confirmation of the error contents, refer the flashing pattern as follows.
Error contents
Indoor unit display
Wired
remote
controller
display
Operation [ ]
(Green)
Timer [ ]
(Orange)
Economy [ ]
(Green)
E: 11. Serial communication error (Serial
reverse transfer error) (Outdoor unit)
1 times
1 times
Continuous
11
E: 11. Serial communication error (Serial
forward transfer error) (Indoor unit)
1 times
1 times
Continuous
11
E: 12. Wired remote controller
communication error (Indoor unit)
1 times
2 times
Continuous
12
E: 18. External communication error (Indoor
unit)
1 times
8 times
Continuous
18
E: 22. Indoor unit capacity error (Indoor
unit)
2 times
2 times
Continuous
22
E: 23. Combination error (Outdoor unit)
2 times
3 times
Continuous
23
E: 32. Indoor unit main PCB error (Indoor
unit)
3 times
2 times
Continuous
32
E: 35. MANUAL AUTO button error (Indoor
unit)
3 times
5 times
Continuous
35
E: 41. Room temperature sensor error
(Indoor unit)
4 times
1 times
Continuous
41
E: 42. Indoor unit heat exchanger sensor
error (Indoor unit)
4 times
2 times
Continuous
42
E: 51. Indoor unit fan motor error (Indoor
unit)
5 times
1 times
Continuous
51
5 times
15 times
Continuous
5U
E: 62. Outdoor unit main PCB error
(Outdoor unit)
6 times
2 times
Continuous
62
E: 64. PFC circuit error (Outdoor unit)
6 times
4 times
Continuous
64
E: 65. IPM error (Outdoor unit)
6 times
5 times
Continuous
65
E: 71. Discharge thermistor error (Outdoor
unit)
7 times
1 times
Continuous
71
E: 73. Outdoor unit heat exchanger liquid
outlet thermistor error (Outdoor unit)
7 times
3 times
Continuous
73
E: 74. Outdoor temperature thermistor error
(Outdoor unit)
7 times
4 times
Continuous
74
E: 84. Current sensor error (Outdoor unit)
8 times
4 times
Continuous
84
E: 94. Over current error (Outdoor unit)
9 times
4 times
Continuous
94
E: 95. Compressor motor control error
(Outdoor unit)
9 times
5 times
Continuous
95
E: 97. Outdoor unit fan motor error
(Outdoor unit)
9 times
7 times
Continuous
97
E: 99. 4-way valve error (Outdoor unit)
9 times
9 times
Continuous
99
E: A1. Discharge temperature error
(Outdoor unit)
10 times
1 times
Continuous
A1
1-3. Error code table (Indoor unit and wired remote controller)
- (03-2) -
1. Error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for General AOHG07KMCC
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 02 03 SR_CH01_AS061EG_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 02 03 SR_CH02_AS061EG_01 ...
Page 41: ...3 TROUBLESHOOTING 2022 02 03 SR_CH03_AS061EG_01 ...
Page 44: ......
Page 97: ...4 CONTROL AND FUNCTIONS 2022 02 03 SR_CH04_AS061EG_01 ...
Page 133: ...5 FILED WORKING 2022 02 03 SR_CH05_AS061EG_01 ...