7-6. POWERFUL operation
The POWERFUL operation starts by pressing POWERFUL button on the remote controller.
The indoor unit and outdoor unit operate at maximum power as shown in the table below.
Compressor frequency
Maximum
Fan mode
POWERFUL
Vertical airflow direction
louver setting
Cooling
3
Dry
Heating
6
Release condition:
• Cooling/Dry
Room temperature ≤ Setting temperature -0.5°C or Operation time has passed 20 minutes.
• Heating
Room temperature ≥ Setting tempe0.5°C or Operation time has passed 20 minutes.
7-7. Fresh air control
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation as below.
Operation
Stop
Operation
Stop
Fan motor
(Indoor unit)
Fan motor
(for Fresh Air)
7-8. Compressor preheating
By preheating the compressor, warm airflow is quickly discharged when the operation is started.
•
Triggering condition
– 30 minutes after compressor stopped.
– Outdoor unit heat exchanger temperature (Tn)
-4°C
Off
On
Tn
Tn
-2°C
When the jumper wire (JM2) is disconnected:
5°C
Off
On
Tn
Tn
7°C
7-6. POWERFUL operation
- (04-28) -
7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for General AOHG07KMCC
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 02 03 SR_CH01_AS061EG_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 02 03 SR_CH02_AS061EG_01 ...
Page 41: ...3 TROUBLESHOOTING 2022 02 03 SR_CH03_AS061EG_01 ...
Page 44: ......
Page 97: ...4 CONTROL AND FUNCTIONS 2022 02 03 SR_CH04_AS061EG_01 ...
Page 133: ...5 FILED WORKING 2022 02 03 SR_CH05_AS061EG_01 ...