8. Various protections
8-1. Discharge gas temperature over-rise prevention control
The discharge gas temperature sensor (discharge thermistor: outdoor unit side) detects the dis-
charge gas temperature.
• When the discharge temperature becomes higher than the trigger condition, the rotation number of
compressor is decreased as the table below, and it continues to decrease until the discharge tem-
perature becomes lower than the trigger condition.
• When the discharge temperature becomes lower than the release condition, control of compressor
rotation number is released.
• When the discharge temperature becomes higher than the compressor protection temperature,
the compressor is stopped and the indoor unit LED starts blinking.
Trigger condition
104°C
Rotation number of compressor
-20 rps/120 seconds
Release condition
101°C
Compressor protection temperature
110°C
8-2. Anti-freezing control (cooling and dry mode)
The rotation number of compressor is decrease in cooling and dry mode when the indoor unit heat
exchanger temperature sensor detects the temperature lower than the trigger condition.
When the indoor unit heat exchanger temperature reaches release condition, the anti-freezing con-
trol is stopped.
Trigger condition
4°C
Release condition
Outdoor temp. ≥ 10°C*
1
Outdoor temp. ≥ 12°C*
2
7°C
Outdoor temp. < 10°C*
1
Outdoor temp. < 12°C*
2
13°C
*1: During the outdoor temperature dropping
*2: During the outdoor temperature rising
8-1. Discharge gas temperature over-rise prevention control
- (04-31) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for General AOHG07KMCC
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 02 03 SR_CH01_AS061EG_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 02 03 SR_CH02_AS061EG_01 ...
Page 41: ...3 TROUBLESHOOTING 2022 02 03 SR_CH03_AS061EG_01 ...
Page 44: ......
Page 97: ...4 CONTROL AND FUNCTIONS 2022 02 03 SR_CH04_AS061EG_01 ...
Page 133: ...5 FILED WORKING 2022 02 03 SR_CH05_AS061EG_01 ...