1-5. Limitation of compressor rotation number by outdoor
temperature
The minimum rotation number of compressor is limited by outdoor temperature as below.
•
Cooling/Dry mode
F zone
38°C
E zone
19°C
D zone
10°C
C zone
B zone
A zone
0°C
-10°C
Model name
Outdoor temperature zone
Limitation of compressor
rotation number
AOHG07KMCC
AOHG09KMCC
AOHG12KMCC
A zone
42 rps
B zone
42 rps
C zone
33 rps
D zone
28 rps
E zone
16 rps
F zone
21 rps
AOHG14KMCC
A zone
36 rps
B zone
36 rps
C zone
28 rps
D zone
26 rps
E zone
1 rps
F zone
36 rps
1-5. Limitation of compressor rotation number by outdoor temperature
- (04-6) -
1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS