2-9. E: 41. Room temperature sensor error (Indoor unit)
Indicator
Indoor unit
Operation indicator
4 time flash
Timer indicator
1 time flash
Economy indicator
Continuous flash
Error code
E: 41
Detective actuator
Indoor unit main PCB
Room temperature thermistor is open or short is
detected always.
Room temperature thermistor
Forecast of cause
Connector failure
Thermistor failure
Main PCB failure
Check point 1. Check connection of connector
•
Check if connector is loose or removed.
•
Check erroneous connection.
•
Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Remove connector and check thermistor resistance value
•
For the room thermistor resistance value, refer to
"Thermistor resistance values"
•
If thermistor is either open or shorted, replace it and reset the power.
↓
Check point 3. Check voltage of main PCB
Make sure circuit diagram of each indoor unit and check terminal voltage at thermis-
tor (DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-20.
(07-14 models: CN1)
If the voltage does not appear, replace main PCB.
↓
End
2-9. E: 41. Room temperature sensor error (Indoor unit)
- (03-13) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for General AOHG07KMCC
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 02 03 SR_CH01_AS061EG_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 02 03 SR_CH02_AS061EG_01 ...
Page 41: ...3 TROUBLESHOOTING 2022 02 03 SR_CH03_AS061EG_01 ...
Page 44: ......
Page 97: ...4 CONTROL AND FUNCTIONS 2022 02 03 SR_CH04_AS061EG_01 ...
Page 133: ...5 FILED WORKING 2022 02 03 SR_CH05_AS061EG_01 ...