Chapter 3 Rack Installation
3.1 Installing Power Distribution Unit (For Regions other than EMEA&I)
FUJITSU Storage ETERNUS DX60 S2 Disk storage system User’s Guide -Installation-
48
Copyright 2014 FUJITSU LIMITED
P3AM-5502-05ENZ0
4
Attach the blank panel to the front side of the rack.
The blank panel should be attached at the same height as the power distribution unit.
End of procedure
3.1.2
Installing Power Distribution Unit (2U)
This section describes how to install the Power distribution unit for ETERNUS DX Disk storage
system (2U, Max 8 enclosures execution) in a rack.
Procedure
1
Attach the M5 cage nuts to the rear rack pillar.
•
Attachment positions
On either side, insert eight M5 cage nuts in the 1st, 3rd, 4th, and 6th holes above the
power distribution unit base line.
(Rear rack pillars)
(Front rack pillars)
Blank panel
Power distribution unit
This section explains the connection procedure for power distribution units
(2U, Max 6 enclosures connection). This procedure can also be applied for
Power distribution unit (2U, Max 8 enclosures connection).
1U
1U
2U
Power distribution unit
Power distribution unit
(Rear rack pillars)
Base line of
power distribution unit
M5 cage nut
M5 cage nut
1st position
3rd position
4th position
6th position
[Left]
[Right]
1st position
3rd position
4th position
6th position