BroadOne GX4000 Manual (R3.0) issue 1.03
1-31
Immunity to narrow band Specification
Emission of narrowband noise Specification
AC 240 V Power Feed
Table 1.6-2 shows the power supply interface requirement in accordance
with ETSI ETS 132-1 (September 1996) below;
Table 1.6-2 Power Supply Requirement at Interface
“A”
Item
Specification
(1) Nominal voltage
230 Vac at interface
“A”.
(2) Normal service
voltage range
207 to 253 Vac
(3) Abnormal service
voltage range
(a) Abnormal service voltage under steady-state condition
GX4000 will not suffer any damage when subjected to the following
voltage ranges; 0.0 to 207 Vac and frequency tolerance: 45 to 55 Hz
(b) Recovery from steady state abnormal voltage
Following the restoration to the normal voltage range, GX4000 will
automatically restore service and resume operation according to its
specification. And the abnormal voltage shall not lead to the
disconnection of the power supply by causing circuit breakers & so on.