En-7

10~15

Hanging bolt (locally purchased)

Nut A (locally purchased)

Washer (Accessories)

After installing the body, 
tighten the nuts. 

Unit: mm

Washer (Accessories)

Nut B (Double Nut)
(locally purchased)

3.3.3. Leveling

Using a level, or vinyl hose 

fi

 lled with water, 

fi

 ne adjust so that the body is level.

Inclined installation so as the drain pipe side is higher may cause a malfunction of the 

fl

 oat 

switch, and may cause water leakage.

Vinyl hoses

Drain pipe

3. 4. Drain installation

 WARNING

•  Do not insert the drain piping into the sewer where sulfurous gas occurs. (Heat 

exchange erosion may occur.)

•  Insulate the parts properly so that water will not drip from the connection parts.
•  Check for proper drainage after the construction by using the visible portion of 

transparent drain port and the drain piping 

fi

 nal outlet on the body.

 CAUTION

Do not apply adhesive agent on the drain port of the body. (Use the attached drain 
hose and connect the drain piping.)

3.4.1. Installing the drain pipe:

• Install the drain pipe with downward gradient (1/50 to 1/100) and so there are no rises or 

traps in the pipe.

• Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32 mm] and connect it 

with adhesive (polyvinyl chloride) so that there is no leakage.

• When the pipe is long, install supporters.
• Do not perform air bleeding.
• Always heat insulate the indoor side of the drain pipe.
• If it is impossible to have suf

fi

 cient gradient of pipe, perform drain lift-up.

Pipe size

Drain pipe

VP25 (O.D. 32 mm)

Hanging 

fi

 ttings

1.5 to 2 m

VP25 (O.D. 32 mm)
Downward gradient 1/100 to 1/50

Rise

PROHIBITED:

Trap

Air bleeding

 

When lifting up drain:

•  Height of inclined pipe should be less than 850 mm from the ceiling. A rise dimension over 

this range will cause leakage.

•  Lift up the pipe vertically at the position of 300 mm or less from the unit.

300 mm or less

VP25 (O.D. 32 mm) 

local arrangement

850 mm or less

Horizontal or 
upward gradient

Downward gradient 
1/100 to 1/50

VP30 (O.D. 38 mm) or more Downward 
gradient 1/100 to 1/50

850 mm or less

3.4.2. Installation procedure

(1) Install the attached drain hose to the drain port of the body. Attach hose band on top of 

the drain hose.

(2) Use vinyl adhesive agent to glue the drain piping (PVC pipe VP25) which is prepared 

on site or elbow socket. (Apply color adhesive agent evenly until the gauge line and 
seal.)

(3) Check the drainage.
(4) Install the heat insulation.
(5) Use the attached heat insulation to insulate the drain port and band parts of the body.

Install the knob faces 
upward

Attached drain hose 
heat insulation 

Attached heat insulation

Attached 
hose band

Locally arranged 
vinyl pipe 

Attached drain hose

(a) Top view

(c) Top view

(b) Side view

VP25

Applying area of 
adhesive 

35

4 or less 

Gauge line

Hose band

5-10

20

Make sure there 

are no gaps 

Wind the attached heat insulation 

around the hose band 

(d) Hose opening view

Make sure the alignment is 

on top 

Unit: mm

381798070_IM.indb   7

381798070_IM.indb   7

12/5/2018   9:39:32 AM

12/5/2018   9:39:32 AM

Summary of Contents for AUXG-KRLB Series

Page 1: ... and use the power cable combined with an Earth Leakage Circuit Breaker ELCB This product is not explosion proof and therefore should not be installed in an explo sive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical component...

Page 2: ... which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion All possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which flammable refrigerant can possibly be...

Page 3: ...g the system it shall be pressure tested with OFN The system shall be leak tested on completion of charging but prior to commission ing A follow up leak test shall be carried out prior to leaving the site CAUTION 10 Decommissioning Before carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its details It is recommended good practice tha...

Page 4: ... the manufacturer or other prescribed parts The use of non prescribed parts can cause serious accidents such as the unit falling water leakage electric shock or fire Do not turn on the power until all work has been completed CAUTION This manual describes how to install the indoor unit only To install the outdoor unit or branch box if any refer to the installation manual included in each product 2 ...

Page 5: ...door unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fall or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fall or the unit to leak water Area that generates substances that adversely...

Page 6: ...g and durable ceiling 3 or more Floor Obstruction Unit m 1 5 or more 1 8 or more 1 or more This product can be installed at a height of up to 4 2 m However if the heights of the ceiling is higher than 3 2 m or lower than 2 7 m it is necessary to set the position from remote controller Refer to 7 FUNCTION SETTING Discharge direction setting Unit mm The discharge direction can be selected as shown b...

Page 7: ...ble to have sufficient gradient of pipe perform drain lift up Pipe size Drain pipe VP25 O D 32 mm Hanging fittings 1 5 to 2 m VP25 O D 32 mm Downward gradient 1 100 to 1 50 Rise PROHIBITED Trap Air bleeding When lifting up drain Height of inclined pipe should be less than 850 mm from the ceiling A rise dimension over this range will cause leakage Lift up the pipe vertically at the position of 300 ...

Page 8: ... 0 When using conventional flare tools to flare R32 pipes the dimension A should be approxi mately 0 5 mm more than indicated in the table for flaring with R32 flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A Width across flats Pipe outside diameter mm in Width across flats of Flare nut mm 6 35 1 4 17 9 52 3 8 22 12 70 1 2 26 15 88 5 8 29 19 05 3 4 36 N...

Page 9: ...the air conditioner may be damaged or cause malfunction Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shock Do not connect power supply cables to the transmission or remote controller termi nals as this will damage the product Never bundle the power supply cable and trans...

Page 10: ... as shown in terminal label Be sure to refer to the connection diagram for the correct field wiring Wrong wiring causes malfunction of the unit 3 6 5 Connection wiring CAUTION Be careful not to mistake the power supply cable and connection wires when install ing Install so that the wires for the remote controller will not come in contact with other connection wires 1 Remove the control box cover a...

Page 11: ...Stop mode or Forced stop mode can be selected with function setting of indoor unit A twisted pair cable 22 AWG should be used Maximum length of cable is 150 m 492 ft Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Connected device Terminal Dry contact termin...

Page 12: ...manual or the operating manual supplied with the air conditioner Setting the switches other than specified will cause an accident or trouble Do not touch the circuit board and circuit board parts directly with your hands Oth erwise injury or electric shock could result Use an insulated screwdriver to set the dip switches 6 1 Group control CAUTION Group control is only possible between units with r...

Page 13: ...h 2 Wired Type A I U A B I U Master Master Slave A B Remote controller cable Refer to 2 4 Electrical requirement A 500 m A B 500 m 7 FUNCTION SETTING Refer to the installation manual of remote controller for setting method 7 1 Function Details Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room ...

Page 14: ... number Setting value Setting description 42 00 Indoor unit 01 Both 00 Sensor on the indoor unit is active 01 Sensors on both indoor unit and wired remote controller are active Remote controller sensor must be turned on by using the remote controller Remote controller custom code Only for wireless remote controller The indoor unit custom code can be changed Select the appropriate custom code Facto...

Page 15: ...he operating manual of the wired remote controller The Operation indicator lamp and Timer indicator lamp will simultaneously flash during the test run mode Heating test run will begin in a few minutes when HEAT is selected by the remote controller reverse cycle model only 10 FINISHING CAUTION After checking for gas leaks refer to the Installation Manual of the outdoor unit perform this section Ins...

Page 16: ... Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error Error display Wired remote controller Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 8 2 Sub cool Heat Ex gas inlet temp senso...

Reviews: