Screw for Mounting Plate
( 4 . 1 x 3 2 )
THE CHOICE OF MOUNTING SITE
(Please note the following matters and obtain permission from customer before installation).
WARNING
●
The unit should be mounted at stable, non-vibratory location
which can provide full support to the unit.
WARNING
●
The outdoor unit must be mounted at a location which can support
heavy weight. Otherwise, noise and vibration will increase.
CAUTION
●
No nearby heat source and no obstruction near the air outlet is
allowed.
●
The clearance distances from top, right and left are speci
fi
ed in
fi
gure below.
●
The location must be convenient for water drainage and pipe
connection with the Outdoor unit.
●
To avoid interference from noise please place the unit and its
remote controller at least 1m from the radio, television and inverter
type
fl
uorescent lamp.
●
To avoid any error in signal transmission from the remote controller,
please put the controller far away from high-frequency machines
and high-power wireless systems.
●
The installation height of indoor unit must be 2.3m or more.
INDOOR UNIT
Names of Indoor Components
Direction of Piping
Figure showing the Installation
of Indoor and Outdoor Unit.
●
The difference in height
between the indoor and
outdoor unit should be kept
below 20m.
●
The connecting pipe, no
matter big or small, should
all be insulated with insulation
pipe and then wrapped with
vinyl tape. (The insulator will
deteriorate if it is not wrapped
with tape).
The connection of insulated
drain hose.
Please use insulated drain
hose for the indoor piping
(commercial product).
OUTDOOR UNIT
Be sure to
completely
seal any
gap with
putty.
T h e r e a r e 6 d i r e c t i o n s
allowed, namely, horizontally
perpendicular to the unit,
vertically down from right,
horizontally out from right and
horizontally out to left.
<
IA820: A
>
Screw for holder of
Remote Controller
( 3 . 1 x 1 6 )
AAA Size Battery
Holder for Remote
Controller
Mounting Plate
Qty
No.
Component’s Name
1
6
1
2
2
Remote Controller
Purifying Filter
!
!
!
1
2
3
4
5
6
7
1
2
3
Bush
Names of Outdoor Components
Qty
No.
Item
Drain Pipe
1
9
10
Bush
1
In case the pipe length is more than 20m, add refrigerant R410A
at 10 gram per every meter exceeds. However, pipe length shall
not exceed 30m.
!
CAUTION
Dimension of Mounting Stand
of the Outdoor unit
(unit : mm)
8
●
Read the safety precautions carefully before operating the unit.
●
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ........ Incorrect methods of installation may cause death or serious injury.
CAUTION ......... Improper installation may result in serious consequence.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of
operating the unit as described in the user’s guide.
HITACHI SPLIT-UNIT AIR CONDITIONER
INSTALLATION MANUAL
Indoor Unit
Outdoor Unit
RAS-60YHA3 RAC-60YHA3
SAFETY PRECAUTION
!
!
FOR SERVICE PERSONNEL ONLY
WARNING
!
●
Please request your sales agent or quali
fi
ed technician to install your unit. Water leakage, short circuit or
fi
re may occur if
you do the installation work yourself.
●
Please observe the instructions stated in the installation manual during the process of installation. Improper installation may
cause water leakage, electric shock and
fi
re.
●
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not,
the units may collapse and impose danger.
●
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when
dealing with the electrical work. Use power cables approved by the authorities of your country.
●
Be sure to use the speci
fi
ed wire for connecting the indoor and outdoor units. Please ensure that the connections are tight
after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating
and
fi
re.
●
Please use the speci
fi
ed components for installation work. Otherwise, the units may collapse or water leakage, electric shock
and
fi
re may occur.
●
Be sure to use the speci
fi
ed piping set for R410A. Otherwise, this may result in broken copper pipes or faults.
●
When installing or removing an air conditioner, only speci
fi
ed refrigerant (R410A) shall be allowed, do not allow air or moisture
to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a
rupture may be caused.
●
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with
fi
re, a poisonous
gas may occur.
●
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas
leaks into the room, coming into contact with
fi
re in the fan-driven heater, space heater, etc., a poisonous gas may occur.
●
Unauthorized modi
fi
cations to the air conditioner may be dangerous. If a breakdown occurs please call a quali
fi
ed air
conditioner technician or electrician. Improper repairs may result in water leakage, electric shock and
fi
re, etc.
●
+ –
Screwdriver
●
Measuring Tape
●
Knife
●
Saw
●
Pipe Cutter
●
Hexagonal Wrench Key (
4mm)
●
Power Drill (ø 65mm ~ ø 80mm)
●
Vacuum Pump
●
Pliers or Wrench
●
Torque Wrench
●
Vacuum
Pump Adaptor
●
Flare Tool
●
Gas Leakage Detector
●
Manifold Valve
●
Charge Hose
●
Reammer
●
File
●
Carefully read through the procedures of proper
installation before starting installation work.
●
The sales agent should inform customers regarding
the correct operation of installation.
Tools Needed For Installation Work
!
●
A circuit breaker or fuse (20A time delay) must be installed. Without a circuit breaker or fuse the danger of electric
shock
exists.
The external switch shall be incorporated to completely disconnect from power supply. It should disconnect all poles, and a
contact separation of at least 3mm must be present.
●
Do not install the unit near a location where there is
fl
ammable gas. The outdoor unit may catch
fi
re if
fl
ammable gas leaks around it.
●
Do not install the indoor unit in a machine shop or kitchen where vapor from oil or its mist
fl
ows to the indoor unit. The oil
will deposit on the heat exchanger, thereby reducing the indoor unit performance and may deform and in the worst case,
break the plastic parts of the indoor unit.
●
Please ensure smooth
fl
ow of water when installing the drain hose.
●
Piping shall be suitable supported with a maximum spacing of 1m between the supports.
CAUTION
CAUTION
●
Do not expose the unit under direct sunshine or rain. Besides,
ventilation must be good and clear of obstruction.
●
The air blown out of the unit should not point directly to animals
or plants.
●
The clearances of the unit from top, left, right, front and back
are speci
fi
ed in
fi
gure below. At least 3 of the above sides must
be open air.
●
Be sure that the hot air blown out of the unit and noise do not
disturb the neighbourhood.
●
Do not install at a location where there is
fl
ammable gas, steam,
oil and smoke.
●
The location must be convenient for water drainage.
●
Place the Outdoor unit and its connecting cord at least 1m away
from the antenna or signal line of television, radio or telephone.
This is to avoid noise interference.
●
Do not install outdoor unit facing strong wind direction. It may
damage the fan motor.
●
Do not install the outdoor unit in a place where small animals
may build their nests. If small animal goes inside the unit and
touches the electrical parts, failure of the unit, smoke or
fi
re may
be caused. Request your customer to keep the surrounding of
the unit clean.
Refrigerant pipe size (outer diameter): Narrow pipe, Liquid (ø6.35mm) ; Wide pipe, Gas (ø12.70mm)
!
Installation of Mounting Plate, Wall Penetration and Installation of Protection Pipe
1
CAUTION
!
●
The draining of the water container inside the indoor unit can be done from the left.
Therefore the mounting plate must be
fi
xed horizontally or slightly tilted towards the
side of drain hose. Otherwise, condensed water may over
fl
ow the water container.
Direct Mounting On The Wall
●
Please use hidden beams in the wall to hold the mounting plate.
Wall Penetration and Installation of Protection Pipe
●
Drill a ø 65mm hole on
wall which is slightly tilted
towards the outdoor side.
Drill the wall at a small
angle.
●
Cut the protection pipe
according to the wall
thickness.
●
Empty gap in the sleeve
of protection pipe should
be completely sealed with
putty to avoid dripping of
rain water into the room.
Installation of the Indoor Unit
2
DIRECTLY BACKWARD PIPING
Preparation
●
Connect connecting cord.
●
Pull out the pipe, connecting cord and drain hose.
●
Arrange a drain hose in lowest part of a wall hole.
Installation
●
The upper part of the Indoor unit is hanged on the mounting plate.
●
The projection at the lower part of the Indoor unit is hooked onto the mounting plate.
Please pull the lower part of
the Indoor unit outwards to
check if the unit is hooked
onto the mounting plate.
Improper installation may
cause vibration and noise.
!
CAUTION
HORIZONTAL PIPING
Preparation
Change of Drain Hose and Installation Procedures.
●
Exchange the location of drain hose and drain cap during horizontal piping as shown in
fi
gure below. Be sure to plug in the drain hose until the insulating material folds upon itself.
●
Please use pliers to pull out the drain cap.
(This is an easier way to remove the drain cap).
INSTALLATION OF REFRIGERATING PIPES AFTER CONNECTION
●
The refrigerating pipes should be adjusted to
fi
t
into the hole on the wall and then ready for further
connection.
●
The terminals of 2 connected pipes must be covered
with insulator used for terminal connection. Then the
pipes are wrapped with insulation pipe.
●
Connect the connecting cord after removing electrical
cover. (Refer to “CONNECTION OF POWER CORD”)
●
After adjustment,
fi
t the connecting cord and pipes
into the space available under the indoor unit. Use
holder to hold them tight.
!
CAUTION
●
The rubber strap used for
fi
xing the insulator should
not be tied with great force.
Otherwise, this will damage
heat insulation and causes
water condensation.
●
Holder can be attached at the either of 2 places.
Please select the easier position.
THE CONNECTION OF REFRIGERATING PIPE DURING THE
INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
!
CAUTION
●
Please
fi
x in the plastic core
after
fl
aring to avoid plastic
chips entering the pipes.
CAUTION
!
You are free to choose the side (left or right) for the installation of drain
hose. Please ensure the smooth
fl
ow of condensed water of the Indoor
unit during installation. (Carelessness may result in water leakage.)
!
CAUTION
Be sure that the
drain hose is not
loosely connected
or bend.
Be sure that the wire is not
in contact with any metal
in the wall. Please use
the protection pipe as wire
passing through the hollow
part of the wall so as to
prevent the possibility of
damaged by mouse.
Unless it seals completely,
any air with high humidity
flows from outdoor and
any dew may drop.
!
WARNING
●
The refrigerating pipes and connecting cord
transform and are attached.
●
The end of the refrigerating pipes are at locations
marked with “
” symbol.
Installation of Drain Hose
3
Installation
Hang the Indoor unit onto the mounting plate. Use the temporary
stand at the back of the Indoor unit to push its lower part 15cm
forwards.
●
Place the drain hose through the hole on the wall.
●
Wrap the refrigerating pipes with insulation pipe after connecting
refrigerating pipe.
●
Connect the connecting cord after removing electrical cover.
(Refer to “Connection of Power Cord”)
●
After adjustment, the connecting cord and refrigerating pipes
are placed into the space available under the Indoor unit.
●
The projection of Indoor unit must hook to the mounting plate.
INDOOR UNIT
HOW TO REMOVE INDOOR UNIT FROM MOUNTING PLATE
●
Pull down PULL section on the bottom of indoor
unit and pull it towards you, then claws are
released from mounting plate. (Indicated by 2
arrows in the drawing on the right.)
●
When bottom face of indoor unit cannot be
pulled due to obstacles, etc. Remove front cover,
insert screw driver into circle hole, pull claws
down and pull indoor unit towards you.
●
Please check how to remove and attach front
cover in this instruction manual.
!
CAUTION
Condensed water may leak out if not inserted properly.
HORIZONTAL & DOWNWARD PIPING – MAKING OPENINGS
●
During horizontal or downward piping, use a knife to cut
openings as shown in
fi
gure. Then smoothen the edges of
openings with a
fi
le.
●
Turn the piping while holding down the
lower portion of pipe-support by hand.
Heat insulation pipe
Connecting
cord
Refrigerating pipe
Pull this to the front
during the connection
of refrigerating pipes
to ease task.
Procedures of Installation and Precautions
●
Procedures to
fi
x the mounting plate.
1. Drill holes on wall.
2. Push plug into the holes. 3. Fix the mounting plate on
(As shown below)
(As shown below)
wall with 4.1 x 32 screw
(As shown in
fi
gure below)
●
Procedures to
fi
x the holder of remote control.
1. Drill holes on wall.
2. Push plug into the holes.
(As shown below)
(As shown below)