En-14

 

Room temperature control for indoor unit sensor

Depending on the installed environment, correction of the room temperature sensor may 
be required.
Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting “00” 
(manufacturer’s recommended value).

(

...  Factory setting)

Function number

Setting 

value

Setting description

30

(For cooling)

31

(For heating)

00

Standard setting

01

No correction 0.0 °C (0 °F)

02

-0.5 °C (-1 °F)

More 

Cooling 

Less 

Heating

03

-1.0 °C (-2 °F)

04

-1.5 °C (-3 °F)

05

-2.0 °C (-4 °F)

06

-2.5 °C (-5 °F)

07

-3.0 °C (-6 °F)

08

-3.5 °C (-7 °F)

09

-4.0 °C (-8 °F)

10

+0.5 °C (+1 °F)

Less 

Cooling 

More 

Heating

11

+1.0 °C (+2 °F)

12

+1.5 °C (+3 °F)

13

+2.0 °C (+4 °F)

14

+2.5 °C (+5 °F)

15

+3.0 °C (+6 °F)

16

+3.5 °C (+7 °F)

17

+4.0 °C (+8 °F)

 

Room temperature control for wired remote controller sensor

Depending on the installed environment, correction of the wire remote temperature sensor 
may be required.
Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”.
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.

(

...  Factory setting)

Function number

Setting 

value

Setting description

35

(For cooling)

36

(For heating)

00

No correction

01

No correction 0.0 °C (0 °F)

02

-0.5 °C (-1 °F)

More 

Cooling 

Less 

Heating

03

-1.0 °C (-2 °F)

04

-1.5 °C (-3 °F)

05

-2.0 °C (-4 °F)

06

-2.5 °C (-5 °F)

07

-3.0 °C (-6 °F)

08

-3.5 °C (-7 °F)

09

-4.0 °C (-8 °F)

10

+0.5 °C (+1 °F)

Less 

Cooling 

More 

Heating

11

+1.0 °C (+2 °F)

12

+1.5 °C (+3 °F)

13

+2.0 °C (+4 °F)

14

+2.5 °C (+5 °F)

15

+3.0 °C (+6 °F)

16

+3.5 °C (+7 °F)

17

+4.0 °C (+8 °F)

 

Auto restart

Enable or disable automatic restart after a power interruption.

(

...  Factory setting)

Function 

number

Setting 

value

Setting description

40

00

Enable

01

Disable

* Auto restart is an emergency function such as for power outage etc. Do not attempt to 

use this function in normal operation. Be sure to operate the unit by remote controller or 
external device.

 

Room temperature sensor switching

(Only for wireless remote controller)
When using the Wired remote controller temperature sensor, change the setting to "Both" 
(01).

(

...  Factory setting)

Function 

number

Setting 

value

Setting description

42

00

Indoor unit

01

Both

00:  Sensor on the indoor unit is active.
01:  Sensors on both indoor unit and wired remote controller are active.
* Remote controller sensor must be turned on by using the remote controller

 

Remote controller custom code

(Only for wireless remote controller)
The indoor unit custom code can be changed.
Select the appropriate custom code.

(

...  Factory setting)

Function 

number

Setting 

value

Setting description

44

00

A

01

B

02

C

03

D

 

External input control

"Operation/Stop" mode or "Forced stop" mode can be selected.

(

...  Factory setting)

Function 

number

Setting 

value

Setting description

46

00

Operation/Stop mode 1

01

(Setting prohibited)

02

Forced stop mode

03

Operation/Stop mode 2

 

Room temperature sensor switching (Aux.)

To use the temperature sensor on the wired remote controller only, change the setting to 
"Wired remote controller" (01). This function will only work if the function setting 42 is set 
at "Both" (01)

(

...  Factory setting)

Function 

number

Setting 

value

Setting description

48

00

Both

01

Wired remote controller

 

Indoor unit fan control for energy saving for cooling

Enables or disables the power-saving function by controlling the indoor unit fan rotation 
when the outdoor unit is stopped during cooling operation.

(

...  Factory setting)

Function 

number

Setting 

value

Setting description 

49

00

Disable

01

Enable

02

Remote controller

00: When the outdoor unit is stopped, the indoor unit fan operates continuously following 

the setting on the remote controller.

01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very 

low speed.

02: Enable or disable this function by remote controller setting.

Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for 
energy saving function or connecting a network converter.

To con

fi

 rm if the remote controller has this setting, refer to the operating manual of each 

remote controller.

 

Switching functions for external output terminal

Functions of the external output terminal can be switched.

(

...  Factory setting)

Function 

number

Setting 

value

Setting description 

60

00

Operation status

09

Error status

10

Indoor unit fan operation status

11

External heater

381798070_IM.indb   14

381798070_IM.indb   14

12/5/2018   9:39:33 AM

12/5/2018   9:39:33 AM

Summary of Contents for AUXG-KRLB Series

Page 1: ... and use the power cable combined with an Earth Leakage Circuit Breaker ELCB This product is not explosion proof and therefore should not be installed in an explo sive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical component...

Page 2: ... which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion All possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which flammable refrigerant can possibly be...

Page 3: ...g the system it shall be pressure tested with OFN The system shall be leak tested on completion of charging but prior to commission ing A follow up leak test shall be carried out prior to leaving the site CAUTION 10 Decommissioning Before carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its details It is recommended good practice tha...

Page 4: ... the manufacturer or other prescribed parts The use of non prescribed parts can cause serious accidents such as the unit falling water leakage electric shock or fire Do not turn on the power until all work has been completed CAUTION This manual describes how to install the indoor unit only To install the outdoor unit or branch box if any refer to the installation manual included in each product 2 ...

Page 5: ...door unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fall or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fall or the unit to leak water Area that generates substances that adversely...

Page 6: ...g and durable ceiling 3 or more Floor Obstruction Unit m 1 5 or more 1 8 or more 1 or more This product can be installed at a height of up to 4 2 m However if the heights of the ceiling is higher than 3 2 m or lower than 2 7 m it is necessary to set the position from remote controller Refer to 7 FUNCTION SETTING Discharge direction setting Unit mm The discharge direction can be selected as shown b...

Page 7: ...ble to have sufficient gradient of pipe perform drain lift up Pipe size Drain pipe VP25 O D 32 mm Hanging fittings 1 5 to 2 m VP25 O D 32 mm Downward gradient 1 100 to 1 50 Rise PROHIBITED Trap Air bleeding When lifting up drain Height of inclined pipe should be less than 850 mm from the ceiling A rise dimension over this range will cause leakage Lift up the pipe vertically at the position of 300 ...

Page 8: ... 0 When using conventional flare tools to flare R32 pipes the dimension A should be approxi mately 0 5 mm more than indicated in the table for flaring with R32 flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A Width across flats Pipe outside diameter mm in Width across flats of Flare nut mm 6 35 1 4 17 9 52 3 8 22 12 70 1 2 26 15 88 5 8 29 19 05 3 4 36 N...

Page 9: ...the air conditioner may be damaged or cause malfunction Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shock Do not connect power supply cables to the transmission or remote controller termi nals as this will damage the product Never bundle the power supply cable and trans...

Page 10: ... as shown in terminal label Be sure to refer to the connection diagram for the correct field wiring Wrong wiring causes malfunction of the unit 3 6 5 Connection wiring CAUTION Be careful not to mistake the power supply cable and connection wires when install ing Install so that the wires for the remote controller will not come in contact with other connection wires 1 Remove the control box cover a...

Page 11: ...Stop mode or Forced stop mode can be selected with function setting of indoor unit A twisted pair cable 22 AWG should be used Maximum length of cable is 150 m 492 ft Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Connected device Terminal Dry contact termin...

Page 12: ...manual or the operating manual supplied with the air conditioner Setting the switches other than specified will cause an accident or trouble Do not touch the circuit board and circuit board parts directly with your hands Oth erwise injury or electric shock could result Use an insulated screwdriver to set the dip switches 6 1 Group control CAUTION Group control is only possible between units with r...

Page 13: ...h 2 Wired Type A I U A B I U Master Master Slave A B Remote controller cable Refer to 2 4 Electrical requirement A 500 m A B 500 m 7 FUNCTION SETTING Refer to the installation manual of remote controller for setting method 7 1 Function Details Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room ...

Page 14: ... number Setting value Setting description 42 00 Indoor unit 01 Both 00 Sensor on the indoor unit is active 01 Sensors on both indoor unit and wired remote controller are active Remote controller sensor must be turned on by using the remote controller Remote controller custom code Only for wireless remote controller The indoor unit custom code can be changed Select the appropriate custom code Facto...

Page 15: ...he operating manual of the wired remote controller The Operation indicator lamp and Timer indicator lamp will simultaneously flash during the test run mode Heating test run will begin in a few minutes when HEAT is selected by the remote controller reverse cycle model only 10 FINISHING CAUTION After checking for gas leaks refer to the Installation Manual of the outdoor unit perform this section Ins...

Page 16: ... Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error Error display Wired remote controller Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 8 2 Sub cool Heat Ex gas inlet temp senso...

Reviews: