Fujitsu AUXG-KRLB Series Installation Manual Download Page 4

En-4

Explanation of symbols displayed on the indoor unit or outdoor unit.

WARNING

This symbol shows that this appliance uses a 

fl

 ammable 

refrigerant. 
If the refrigerant is leaked and exposed to an external igni-
tion source, there is a risk of 

fi

 re.

CAUTION

This symbol shows that the operation manual should be 
read carefully.

CAUTION

This symbol shows that a service personnel should be 
handling this equipment with reference to the installation 
manual.

CAUTION

This symbol shows that information is available such as 
the operating manual or installation manual.

2. PRODUCT SPECIFICATION

2. 1.  Installation tools

Tool name

Change from R22 to R32 (R410A)

Gauge manifold

Pressure is high and cannot be measured with a R22 
gauge. To prevent erroneous mixing of other refrigerants, 
the diameter of each port has been changed.
It is recommended to use gauge with seals -0.1 to 5.3 MPa 
(-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.

Charge hose

To increase pressure resistance, the hose material and base 
size were changed. (R32/R410A)

Vacuum pump

A conventional vacuum pump can be used by installing a 
vacuum pump adapter.
(Use of a vacuum pump with a series motor is prohibited.)

Gas leakage detector

Special gas leakage detector for HFC refrigerant R410A or 
R32.

Copper pipes

It is necessary to use seamless copper pipes and it is desirable that the amount of residual 
oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or 
discolored portion (especially on the interior surface). Otherwise, the expansion value or 
capillary tube may become blocked with contaminants.
As an air conditioner using R32 (R410A) incurs pressure higher than when using R22, it is 
necessary to choose adequate materials. 

 WARNING

•  Do not use the existing (for R22) piping and 

fl

 are nuts.

If the existing materials are used, the pressure inside the refrigerant cycle will rise and 
cause failure, injury, etc. (Use the special R32/R410A materials.)

•  Use (re

fi

 ll or replace with) speci

fi

 ed refrigerant (R32) only.  Use of unspeci

fi

 ed refriger-

ant can cause product malfunction, burst, or injury.

•  Do not mix any gas or impurities except speci

fi

 ed refrigerant (R32).  In

fl

 ow of air or ap-

plication of unspeci

fi

 ed material makes the internal pressure of the refrigerant cycle too 

high, and may cause product malfunction, burst of piping, or injury.

•  For installation purposes, be sure to use the parts supplied by the manufacturer or 

other prescribed parts. The use of non-prescribed parts can cause serious accidents 
such as the unit falling, water leakage, electric shock, or 

fi

 re.

•  Do not turn on the power until all work has been completed.

 CAUTION

This manual describes how to install the indoor unit only. To install the outdoor unit or 
branch box, (if any), refer to the installation manual included in each product.

2. 2.  Accessories

 WARNING

•  For installation purposes, be sure to use the parts supplied by the manufacturer or 

other prescribed parts. 

•  The use of non-prescribed parts can cause serious accidents such as the unit falling, 

water leakage, electric shock, or 

fi

 re.

• The following installation parts are furnished. Use them as required.
• Keep the installation manual in a safe place and do not discard any other accessories 

until the installation work has been completed.

Name and Shape

Q’ty

Description

Installation manual

1

(This book)

Operating manual

1

CD-ROM

1

Template

(Carton top)

1

For installing indoor unit

Washer

8

For installing indoor unit

Coupler heat insulation (Large)

1

For indoor side pipe joint (Gas pipe)

Coupler heat insulation (Small)

1

For indoor side pipe joint 
(Liquid pipe)

Insulation

1

For installing drain pipe

Drain hose

1

For installing drain pipe
VP25 (O.D.32, I.D.25)

Hose Band

1

For installing drain hose

Drain hose heat insulation

1

For installing drain pipe

Cable tie (Large)

4

For connection pipe 

fi

 xing.

Cable tie (Small)

2

Only one is used for this model.

2. 3. Pipe requirement

 CAUTION

Refer to the installation manual of the outdoor unit for description of the length of con-
necting pipe or for difference of its elevation.

Model

Diameter [mm (in)]

Gas pipe

Liquid pipe

18/22/24

12.70 (1/2)

6.35 (1/4)

30/36/45/54

15.88 (5/8)

9.52 (3/8)

•  Use pipe with water-resistant heat insulation.

 CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may cause 
water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is 
expected to exceed 70 %, install heat insulation around the refrigerant piping.
If the expected humidity level is 70-80 %, use heat insulation that is 15 mm or thicker 
and if the expected humidity exceeds 80 %, use heat insulation that is 20 mm or thicker. 
If heat insulation is used that is not as thick as speci

fi

 ed, condensation may form on the 

surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 20 °C).

381798070_IM.indb   4

381798070_IM.indb   4

12/5/2018   9:39:31 AM

12/5/2018   9:39:31 AM

Summary of Contents for AUXG-KRLB Series

Page 1: ... and use the power cable combined with an Earth Leakage Circuit Breaker ELCB This product is not explosion proof and therefore should not be installed in an explo sive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical component...

Page 2: ... which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion All possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which flammable refrigerant can possibly be...

Page 3: ...g the system it shall be pressure tested with OFN The system shall be leak tested on completion of charging but prior to commission ing A follow up leak test shall be carried out prior to leaving the site CAUTION 10 Decommissioning Before carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its details It is recommended good practice tha...

Page 4: ... the manufacturer or other prescribed parts The use of non prescribed parts can cause serious accidents such as the unit falling water leakage electric shock or fire Do not turn on the power until all work has been completed CAUTION This manual describes how to install the indoor unit only To install the outdoor unit or branch box if any refer to the installation manual included in each product 2 ...

Page 5: ...door unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fall or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fall or the unit to leak water Area that generates substances that adversely...

Page 6: ...g and durable ceiling 3 or more Floor Obstruction Unit m 1 5 or more 1 8 or more 1 or more This product can be installed at a height of up to 4 2 m However if the heights of the ceiling is higher than 3 2 m or lower than 2 7 m it is necessary to set the position from remote controller Refer to 7 FUNCTION SETTING Discharge direction setting Unit mm The discharge direction can be selected as shown b...

Page 7: ...ble to have sufficient gradient of pipe perform drain lift up Pipe size Drain pipe VP25 O D 32 mm Hanging fittings 1 5 to 2 m VP25 O D 32 mm Downward gradient 1 100 to 1 50 Rise PROHIBITED Trap Air bleeding When lifting up drain Height of inclined pipe should be less than 850 mm from the ceiling A rise dimension over this range will cause leakage Lift up the pipe vertically at the position of 300 ...

Page 8: ... 0 When using conventional flare tools to flare R32 pipes the dimension A should be approxi mately 0 5 mm more than indicated in the table for flaring with R32 flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A Width across flats Pipe outside diameter mm in Width across flats of Flare nut mm 6 35 1 4 17 9 52 3 8 22 12 70 1 2 26 15 88 5 8 29 19 05 3 4 36 N...

Page 9: ...the air conditioner may be damaged or cause malfunction Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shock Do not connect power supply cables to the transmission or remote controller termi nals as this will damage the product Never bundle the power supply cable and trans...

Page 10: ... as shown in terminal label Be sure to refer to the connection diagram for the correct field wiring Wrong wiring causes malfunction of the unit 3 6 5 Connection wiring CAUTION Be careful not to mistake the power supply cable and connection wires when install ing Install so that the wires for the remote controller will not come in contact with other connection wires 1 Remove the control box cover a...

Page 11: ...Stop mode or Forced stop mode can be selected with function setting of indoor unit A twisted pair cable 22 AWG should be used Maximum length of cable is 150 m 492 ft Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Connected device Terminal Dry contact termin...

Page 12: ...manual or the operating manual supplied with the air conditioner Setting the switches other than specified will cause an accident or trouble Do not touch the circuit board and circuit board parts directly with your hands Oth erwise injury or electric shock could result Use an insulated screwdriver to set the dip switches 6 1 Group control CAUTION Group control is only possible between units with r...

Page 13: ...h 2 Wired Type A I U A B I U Master Master Slave A B Remote controller cable Refer to 2 4 Electrical requirement A 500 m A B 500 m 7 FUNCTION SETTING Refer to the installation manual of remote controller for setting method 7 1 Function Details Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room ...

Page 14: ... number Setting value Setting description 42 00 Indoor unit 01 Both 00 Sensor on the indoor unit is active 01 Sensors on both indoor unit and wired remote controller are active Remote controller sensor must be turned on by using the remote controller Remote controller custom code Only for wireless remote controller The indoor unit custom code can be changed Select the appropriate custom code Facto...

Page 15: ...he operating manual of the wired remote controller The Operation indicator lamp and Timer indicator lamp will simultaneously flash during the test run mode Heating test run will begin in a few minutes when HEAT is selected by the remote controller reverse cycle model only 10 FINISHING CAUTION After checking for gas leaks refer to the Installation Manual of the outdoor unit perform this section Ins...

Page 16: ... Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error Error display Wired remote controller Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 8 2 Sub cool Heat Ex gas inlet temp senso...

Reviews: