background image

En-2

Precautions for using R32 refrigerant

The basic installation work procedures are the same as conventional refrigerant (R410A, 
R22) models.
However, pay careful attention to the following points:

Since the working pressure is 1.6 times higher than that of refrigerant R22 models, 
some of the piping and installation and service tools are special. (Refer to “2. 1. Instal-
lation tools”.)
Especially, when replacing a refrigerant R22 model with a new refrigerant R32 model, 
always replace the conventional piping and flare nuts with the R32 and R410A piping and 

fl

 are nuts on the outdoor unit side. 

For R32 and R410A, the same 

fl

 are nut on the outdoor unit side and pipe can be used.

Models that use refrigerant R32 and R410A have a different charging port thread diam-
eter to prevent erroneous charging with refrigerant R22 and for safety. Therefore, check 
beforehand. [The charging port thread diameter for R32 and R410A is 1/2-20 UNF.]
Be more careful than R22 so that foreign matter (oil, water, etc.) does not enter the 
piping. Also, when storing the piping, securely seal the opening by pinching, taping, etc. 
(Handling of R32 is similar to R410A.)

 CAUTION

1-Installation (Space)

•  That the installation of pipe-work shall be kept to a minimum.
•  That pipe-work shall be protected from physical damage.
•  The appliance shall not be installed in an unventilated space, if that space is smaller 

than X m².

Amount of refrigerant charge

M (kg)

Minimum room area

X (m

2

)

 1.22 

-

1.22 < M 

 1.23 

1.45

1.23 < M 

 1.50 

2.15

1.50 < M 

 1.75 

2.92

1.75 < M 

 2.0 

3.82

2.0 < M 

 2.5 

5.96

2.5 < M 

 3.0 

8.59

3.0 < M 

 3.5 

11.68

3.5 < M 

 4.0 

15.26

(IEC 60335-2-40)

•  That compliance with national gas regulations shall be observed.
•  That mechanical connections shall be accessible for maintenance purposes.
•  In cases that require mechanical ventilation, ventilation openings shall be kept clear 

of obstruction.

•  When disposing of the product is used, be based on national regulations, properly 

processed.

2-Servicing
2-1 Service personnel

•  Any person who is involved with working on or breaking into a refrigerant circuit 

should hold a current valid certi

fi

 cate from an industry-accredited assessment 

authority, which authorises their competence to handle refrigerants safely in accor-
dance with an industry recognised assessment speci

fi

 cation.

•  Servicing shall only be performed as recommended by the equipment manufacturer. 

Maintenance and repair requiring  the assistance of other skilled personnel shall be 
carried out under the supervision of the person competent in the use of 

fl

 ammable 

refrigerants.

•  Servicing shall be performed only as recommended by the manufacturer.

2-2 Work

•  Prior to beginning work on systems containing 

fl

 ammable refrigerants, safety checks 

are necessary to ensure that the risk of ignition is minimized. For repair to the refrig-
erating system, the precautions in 2-2 to 2-8 shall be complied with prior to conduct-
ing work on the system.

•  Work shall be undertaken under a controlled procedure so as to minimize the risk of 

fl

 ammable gas or vapour being present while the work is being performed.

•  All maintenance staff and others working in the local area shall be instructed on the 

nature of work being carried out.

•  Work in con

fi

 ned spaces shall be avoided.

•  The area around the workspace shall be sectioned off.
•  Ensure that the conditions within the area have been made safe by control of 

fl

 am-

mable material.

2-3 Checking for presence of refrigerant

•  The area shall be checked with an appropriate refrigerant detector prior to and during 

work, to ensure the technician is aware of potentially 

fl

 ammable atmospheres.

•  Ensure that the leak detection equipment being used is suitable for use with 

fl

 am-

mable refrigerants, i.e. nonsparking, adequately sealed or intrinsically safe.

 CAUTION

2-4 Presence of 

fi

 re extinguisher

•  If any hot work is to be conducted on the refrigeration equipment or any associated 

parts, appropriate 

fi

 re extinguishing equipment shall be available at hand. 

•  Have a dry powder or CO

2

 

fi

 re extinguisher adjacent to the charging area.

2-5 No ignition sources

•  No person carrying out work in relation to a refrigeration system which involves 

exposing any pipe work that contains or has contained 

fl

 ammable refrigerant shall 

use any sources of ignition in such a manner that it may lead to the risk of 

fi

 re or 

explosion.

•  All possible ignition sources, including cigarette smoking, should be kept suf

fi

 ciently 

far away from the site of installation, repairing, removing and disposal, during which 

fl

 ammable refrigerant can possibly be released to the surrounding space.

•  Prior to work taking place, the area around the equipment is to be surveyed to make 

sure that there are no 

fl

 ammable hazards or ignition risks. “No Smoking” signs shall 

be displayed.

2-6 Ventilated area

•  Ensure that the area is in the open or that it is adequately ventilated before breaking 

into the system or conducting any hot work.

•  A degree of ventilation shall continue during the period that the work is carried out.
•  The ventilation should safely disperse any released refrigerant and preferably expel 

it externally into the atmosphere.

2-7 Checks to the refrigeration equipment

•  Where electrical components are being changed, they shall be 

fi

 t for the purpose 

and to the correct speci

fi

 cation.

•  At all times the manufacturer’s maintenance and service guidelines shall be followed.
•  If in doubt consult the manufacturer’s technical department for assistance.
•  The following checks shall be applied to installations using 

fl

 ammable refrigerants.

-  The charge size is in accordance with the room size within which the refrigerant 

containing parts are installed.

-  The ventilation machinery and outlets are operating adequately and are not 

obstructed.

-  If an indirect refrigerating circuit is being used, the secondary circuit shall be 

checked for the presence of refrigerant. 

-  Marking to the equipment continues to be visible and legible. Markings and signs 

that are illegible shall be corrected.

-  Refrigeration pipe or components are installed in a position where they are unlikely 

to be exposed to any substance which may corrode refrigerant containing compo-
nents, unless the components are constructed of materials which are inherently 
resistant to being corroded or are suitably protected against being so corroded.

2-8 Checks to electrical devices

•  Repair and maintenance to electrical components shall include initial safety checks 

and component inspection procedures.

•  If a fault exists that could compromise safety, then no electrical supply shall be con-

nected to the circuit until it is satisfactorily dealt with.

•  If the fault cannot be corrected immediately but it is necessary to continue operation, 

an adequate temporary solution shall be used.

•  This shall be reported to the owner of the equipment so all parties are advised.
•  Initial safety checks shall include.

-  That capacitors are discharged: this shall be done in a safe manner to avoid pos-

sibility of sparking.

-  That there no live electrical components and wiring are exposed while charging, 

recovering or purging the system.

-  That there is continuity of earth bonding.

3-Repairs to sealed components

•  During repairs to sealed components, all electrical supplies shall be disconnected 

from the equipment being worked upon prior to any removal of sealed covers, etc.

•  If it is absolutely necessary to have an electrical supply to equipment during servic-

ing, then a permanently operating form of leak detection shall be located at the most 
critical point to warn of a potentially hazardous situation.

•  Particular attention shall be paid to the following to ensure that by working on electri-

cal components, the casing is not altered in such a way that the level of protection is 
affected.

•  This shall include damage to cables, excessive number of connections, terminals not 

made to original speci

fi

 cation, damage to seals, incorrect 

fi

 tting of glands, etc.

•  Ensure that apparatus is mounted securely.
•  Ensure that seals or sealing materials have not degraded such that they no longer 

serve the purpose of preventing the ingress of 

fl

 ammable atmospheres.

•  Replacement parts shall be in accordance with the manufacturer’s speci

fi

 cations.

NOTES:   The use of silicon sealant may inhibit the effectiveness of some types of leak 

detection equipment.
Intrinsically safe components do not have to be isolated prior to working on 
them.

381798070_IM.indb   2

381798070_IM.indb   2

12/5/2018   9:39:31 AM

12/5/2018   9:39:31 AM

Summary of Contents for AUXG-KRLB Series

Page 1: ... and use the power cable combined with an Earth Leakage Circuit Breaker ELCB This product is not explosion proof and therefore should not be installed in an explo sive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical component...

Page 2: ... which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion All possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which flammable refrigerant can possibly be...

Page 3: ...g the system it shall be pressure tested with OFN The system shall be leak tested on completion of charging but prior to commission ing A follow up leak test shall be carried out prior to leaving the site CAUTION 10 Decommissioning Before carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its details It is recommended good practice tha...

Page 4: ... the manufacturer or other prescribed parts The use of non prescribed parts can cause serious accidents such as the unit falling water leakage electric shock or fire Do not turn on the power until all work has been completed CAUTION This manual describes how to install the indoor unit only To install the outdoor unit or branch box if any refer to the installation manual included in each product 2 ...

Page 5: ...door unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fall or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fall or the unit to leak water Area that generates substances that adversely...

Page 6: ...g and durable ceiling 3 or more Floor Obstruction Unit m 1 5 or more 1 8 or more 1 or more This product can be installed at a height of up to 4 2 m However if the heights of the ceiling is higher than 3 2 m or lower than 2 7 m it is necessary to set the position from remote controller Refer to 7 FUNCTION SETTING Discharge direction setting Unit mm The discharge direction can be selected as shown b...

Page 7: ...ble to have sufficient gradient of pipe perform drain lift up Pipe size Drain pipe VP25 O D 32 mm Hanging fittings 1 5 to 2 m VP25 O D 32 mm Downward gradient 1 100 to 1 50 Rise PROHIBITED Trap Air bleeding When lifting up drain Height of inclined pipe should be less than 850 mm from the ceiling A rise dimension over this range will cause leakage Lift up the pipe vertically at the position of 300 ...

Page 8: ... 0 When using conventional flare tools to flare R32 pipes the dimension A should be approxi mately 0 5 mm more than indicated in the table for flaring with R32 flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A Width across flats Pipe outside diameter mm in Width across flats of Flare nut mm 6 35 1 4 17 9 52 3 8 22 12 70 1 2 26 15 88 5 8 29 19 05 3 4 36 N...

Page 9: ...the air conditioner may be damaged or cause malfunction Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shock Do not connect power supply cables to the transmission or remote controller termi nals as this will damage the product Never bundle the power supply cable and trans...

Page 10: ... as shown in terminal label Be sure to refer to the connection diagram for the correct field wiring Wrong wiring causes malfunction of the unit 3 6 5 Connection wiring CAUTION Be careful not to mistake the power supply cable and connection wires when install ing Install so that the wires for the remote controller will not come in contact with other connection wires 1 Remove the control box cover a...

Page 11: ...Stop mode or Forced stop mode can be selected with function setting of indoor unit A twisted pair cable 22 AWG should be used Maximum length of cable is 150 m 492 ft Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Connected device Terminal Dry contact termin...

Page 12: ...manual or the operating manual supplied with the air conditioner Setting the switches other than specified will cause an accident or trouble Do not touch the circuit board and circuit board parts directly with your hands Oth erwise injury or electric shock could result Use an insulated screwdriver to set the dip switches 6 1 Group control CAUTION Group control is only possible between units with r...

Page 13: ...h 2 Wired Type A I U A B I U Master Master Slave A B Remote controller cable Refer to 2 4 Electrical requirement A 500 m A B 500 m 7 FUNCTION SETTING Refer to the installation manual of remote controller for setting method 7 1 Function Details Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room ...

Page 14: ... number Setting value Setting description 42 00 Indoor unit 01 Both 00 Sensor on the indoor unit is active 01 Sensors on both indoor unit and wired remote controller are active Remote controller sensor must be turned on by using the remote controller Remote controller custom code Only for wireless remote controller The indoor unit custom code can be changed Select the appropriate custom code Facto...

Page 15: ...he operating manual of the wired remote controller The Operation indicator lamp and Timer indicator lamp will simultaneously flash during the test run mode Heating test run will begin in a few minutes when HEAT is selected by the remote controller reverse cycle model only 10 FINISHING CAUTION After checking for gas leaks refer to the Installation Manual of the outdoor unit perform this section Ins...

Page 16: ... Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error Error display Wired remote controller Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 8 2 Sub cool Heat Ex gas inlet temp senso...

Reviews: