1.  SAFETY PRECAUTIONS

•  Be sure to read this manual thoroughly before installation.

•  The warnings and precautions indicated in this manual contain important information 

pertaining to your safety. Be sure to observe them.

•  Hand this manual, together with the operating manual, to the customer. Request the 

customer to keep them on hand for future use, such as for relocating or repairing the 

unit. 

 WARNING

Indicates a potentially or imminently hazardous situation 
which, if not avoided, could result in death or serious injury. 

 CAUTION

Indicates a potentially hazardous situation that may result in 
minor or moderate injury or damage to property.

 WARNING

•  Installation of this product must be done by experienced service technicians or profes

-

sional installers only in accordance with this manual. Installation by non-professional 

or improper installation of the product might cause serious accidents such as injury, 

water leakage, electric shock, or fire. If the product is installed in disregard of the 

instructions in this manual, it will void the manufacturer’s warranty.

•  Do not turn on the power until all work has been completed. Turning on the power be

-

fore the work is completed can cause serious accidents such as electric shock or fire.

•  If refrigerant leaks when you are working, ventilate the area. If the leaking refrigerant 

is exposed to a direct flame, it may produce a toxic gas.

•  Installation must be performed in accordance with regulations, codes, or  standards for 

electrical wiring and equipment in each country, region, or the installation place.

•  Do not use means to accelerate the defrosting process or to clean, other than those 

recommended by the manufacturer.

•  This appliance is not intended for use by persons (including children) with reduced 

physical, sensory or mental capabilities, or lack of experience and knowledge, unless 

they have been given supervision or instruction concerning use of the appliance by a 

person responsible for their safety. Children should be supervised to ensure that they 

do not play with the appliance.

 CAUTION

•  Read carefully all safety information written in this manual before you install or use the 

air conditioner.

•  Install the product by following local codes and regulations in force at the place of 

installation, and the instructions provided by the manufacturer.

•  This product is part of a set constituting an air conditioner. The product must not be 

installed alone or be installed with non-authorized device by the manufacturer.

•  Always use a separate power supply line protected by a circuit breaker operating on all 

wires with a distance between contact of 3 mm for this product.

•  To protect the persons, earth (ground) the product correctly, and use the power cable 

combined with an Earth Leakage Circuit Breaker (ELCB).

 CAUTION

•  This product is not explosion proof, and therefore should not be installed in explosive 

atmosphere.

•  To avoid getting an electric shock, never touch the electrical components soon after 

the power supply has been turned off. After turning off the power, always wait 5 min

-

utes or more before you touch the electrical components.

•  This product contains no user-serviceable parts. Always consult experienced service 

technicians for reparing.

•  When moving or relocating the air conditioner, consult experienced service technicians 

for disconnection and reinstallation of the product.

•  Do not place any other electrical products or household belongings under the product. 

Condensation dripping from the product might get them wet, and may cause damage 

or malfunction to the property.

•  Be careful not to scratch the air conditioner when handling it.

•  After installation, explain correct operation to the customer, using the operating manual.

2.  ABOUT THIS PRODUCT

2.1. Precautions for using R410A refrigerant

The basic installation work procedures are the same as conventional refrigerant (R22) 
models.  
However, pay careful attention to the following points:

Since the working pressure is 1.6 times higher than that of conventional refrigerant (R22) 

models, some of the piping and installation and service tools are special. (See the table 

below.)
Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant 

R410A model, always replace the conventional piping and flare nuts with the R410A 

piping and flare nuts.
Models that use refrigerant R410A have a different charging port thread diameter 

to prevent erroneous charging with conventional refrigerant (R22) and for safety. 

Therefore, check beforehand. [The charging port thread diameter for R410A is  

1/2-20 UNF]
Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with 

refrigerant (R22) models. Also, when storing the piping ,securely seal the opening by 

pinching, taping, etc.
When charging the refrigerant, take into account the slight change in the composition of 

the gas and liquid phases. And always charge from the liquid phase where refrigerant 

composition is stable.

AIR CONDITIONER
Wall Mounted Type

INSTALLATION MANUAL

Contents

1.  SAFETY PRECAUTIONS .................................................................. 1
2.  ABOUT THIS PRODUCT................................................................... 1
3.  GENERAL SPECIFICATION ............................................................. 2
4.  ELECTRICAL REQUIREMENT ......................................................... 2
5.  SELECTING THE MOUNTING POSITION ....................................... 3
6.  INSTALLATION WORK ..................................................................... 3
7.  ELECTRICAL WIRING  ..................................................................... 5
8.  FINISHING ........................................................................................ 6
9.  FRONT PANEL REMOVAL AND INSTALLATION .............................

7

10.  TEST RUN .........................................................................................

7

11.   REMOTE CONTROLLER INSTALLATION ........................................

7

12.  OPTIONAL KIT INSTALLATION  .......................................................

7

13.  SELECTING THE REMOTE CONTROLLER CUSTOM CODE ........

8

14.  FUNCTION SETTING........................................................................

8

15.  CUSTOMER GUIDANCE ................................................................ 10
16.  ERROR CODES .............................................................................. 10

PART No. 9387082050

For authorized service personnel only.

[Original instructions]

English

Deutsch

Français

Español

Italiano

EλληvIkά

Português

Ру

сский

Türkçe

9387082050_IM.indb   1

12/10/2015   13:33:19

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for ASYG36LMTA

Page 1: ... Leakage Circuit Breaker ELCB CAUTION This product is not explosion proof and therefore should not be installed in explosive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical components This product contains no user serviceable...

Page 2: ...r 1 Saddle 1 set Wall pipe 1 Drain hose 1 Decorative tape 1 Tapping screws 1 set Vinyl tape 1 Sealant 1 2 4 Optional parts Refer to each installation manual for the method of installing optional parts Parts name Model name Application Wired Remote Controller UTY RVN M For air conditioner operation Wired Remote Controller UTY RNR Z1 For air conditioner operation Wired Remote Controller UTY RLR For ...

Page 3: ...The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Install the indoor unit on the wall where the height from the floor is more than 1 8 m 6 INSTALLATION WORK...

Page 4: ...xagonal wrench 4 mm at opposite side to insert the drain cap till the drain cap contacts the tip of the drain cock No gap Hexagonal wrench Drain cock Drain cap CAUTION Insert the drain hose and drain cap into the drain port making sure that it comes in contact with the back of the drain port and then mount it If the drain hose is not connected properly leaking will occur For left piping and left r...

Page 5: ... using the specified tightening method Otherwise the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water from leaking into the control box make sure that the piping is well...

Page 6: ...tallation may cause a fire When fixing the connection cable with the cable clamp always fasten the cable at the plastic jacket portion but not at the insulator portion If the insulator is chafed electric leakage may occur Always connect the earth ground wire Improper earthing grounding work can cause electric shocks Do not use the earth ground screw for the indoor unit to the outdoor unit unless i...

Page 7: ...der to a wall pillar etc with the tapping screw Remote controller holder fixing Remote controller mounting Remote controller holder Tapping screw small 1 Set Remote controller 2 Down 12 OPTIONAL KIT INSTALLATION This air conditioner can be connected with the following optional kits Wired remote controller Simple remote controller External connect kit External input and output PCB 9 FRONT PANEL REM...

Page 8: ...umber selection 3 Press the TEMP buttons to select the set ting value Press the 10 C HEAT button to switch between the left and right digits 4 Press the MODE button once to send the function set ting information Please confirm the beeping sound 5 Next please press Start Stop button once to fix the function setting Please confirm the beeping sound 6 Press the RESET button to cancel the function set...

Page 9: ...n be selected Factory setting Setting Description Function Number Setting Value Operation Stop mode1 46 00 Setting forbidden 01 Forced stop mode 02 Operation Stop mode 2 03 Room temperature sensor switching Aux To use the temperature sensor on the wired remote controller only change the setting to Wired remote controller 01 This function will only work if the function setting 42 is set at Both 01 ...

Page 10: ...uto switch error 4 1 Room temp sensor error 4 2 Indoor unit Heat Ex Middle temp sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 8 Intake grille error 5 15 Indoor unit error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PCB microcomputer...

Reviews: