En-9

Room temperature control for indoor unit sensor

 Depending on the installed environment, correction of the room temperature sensor may 
be required. Select the appropriate control setting according to the installed environment.
The  temperature  correction  values  show  the  difference  from  the  Standard  setting  “00” 
(manufacturer’s recommended value).

(♦...  Factory setting)

Setting Description 

Function  

Number

Setting Value

Standard setting

30

(For cooling)

31

(For heating)

00

No correction 0.0 °C

01

-0.5 °C

More cooling

Less heating

02

-1.0 °C

03

-1.5 °C

04

-2.0 °C

05

-2.5 °C

06

-3.0 °C

07

-3.5 °C

08

-4.0 °C

09

+0.5 °C

Less cooling

More heating

10

+1.0 °C

11

+1.5 °C

12

+2.0 °C

13

+2.5 °C

14

+3.0 °C

15

+3.5 °C

16

+4.0 °C

17

Room temperature control for wired remote controller sensor

 Depending on the installed environment, correction of the wire remote temperature sensor 
may be required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”.
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.

(♦...  Factory setting)

Setting Description 

Function  

Number

Setting Value

No correction

35

(For cooling)

36

(For heating)

00

No correction 0.0 °C

01

-0.5 °C

More cooling

Less heating

02

-1.0 °C

03

-1.5 °C

04

-2.0 °C

05

-2.5 °C

06

-3.0 °C

07

-3.5 °C

08

-4.0 °C

09

+0.5 °C

Less cooling

More heating

10

+1.0 °C

11

+1.5 °C

12

+2.0 °C

13

+2.5 °C

14

+3.0 °C

15

+3.5 °C

16

+4.0 °C

17

Auto restart

Enable or disable automatic restart after a power interruption.

(♦...  Factory setting)

Setting Description

Function  

Number

Setting Value

   Enable

40

00

Disable

01

*  Auto restart is an emergency function such as for power outage etc. Do not attempt to 

use this function in normal operation. Be sure to operate the unit by remote controller or 
external device.

Room temperature sensor switching

(Only for wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to “Both” (01).

(♦...  Factory setting)

Setting Description

Function  

Number

Setting Value

   Indoor unit

42

00

Both

01

00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
*  Remote controller sensor must be turned on by using the remote controller.

Remote controller custom code

(Only for wireless remote controller)

The indoor unit custom code can be changed. Select the appropriate custom code.

(♦...  Factory setting)

Setting Description 

Function  

Number

Setting Value

   A

44

00

B

01

C

02

D

03

External input control

 “Operation/Stop” mode or “Forced stop” mode can be selected.

(♦...  Factory setting)

Setting Description 

Function  

Number

Setting Value

Operation/Stop mode1

46

00

(Setting forbidden)

01

Forced stop mode

02

Operation/Stop mode 2

03

Room temperature sensor switching (Aux.)

 To use the temperature sensor on the wired remote controller only, change the setting to 

“Wired remote controller” (01).

This function will only work if the function setting 42 is set at “Both” (01).

(♦...  Factory setting)

Setting Description 

Function  

Number

Setting Value

Both

48

00

Wired remote controller

01

Indoor unit fan control for energy saving for cooling

 Enables or disables the power-saving function by controlling the indoor unit fan rotation when 

the outdoor unit is stopped during cooling operation.

(♦...  Factory setting)

Setting Description 

Function  

Number

Setting Value

Disable

49

00

Enable

01

Remote controller

02

00:  When the outdoor unit is stopped, the indoor unit fan operates continuously following 

the setting on the remote controller.

01:  When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very 

low speed.

02:  Enable or disable this function by remote controller setting.

*  As the factory setting, this setting is initially activated.

*  When connecting VRF system using network converter, this setting must be set to “00” or “01”.

Switching functions for external output terminal

 Functions of the external output terminal can be switched. For details, refer to “External 

input and output”.

(♦...  Factory setting)

Setting Description 

Function  

Number

Setting Value

Operation status

60

00

Error status

09

Indoor unit fan operation status

10

Set point attainment status

12

Server room control switching

Switches between normal control and server room control.

To use this function, address setting of the primary unit and secondary unit needs to be done.

(♦...  Factory setting)

Setting Description 

Function  

Number

Setting Value

Normal control

96

00

Server room control (Primary unit)

01

Server room control (Secondary unit)

02

Setting record

Record any changes to the settings in the following table.

Setting Description

Setting Value

Remote controller address setting
Filter sign
Room temperature control for indoor 

unit sensor

Cooling
Heating

Room temperature control for wired 

remote controller sensor

Cooling
Heating

Auto restart
Room temperature sensor switching 
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
Indoor unit fan control for energy saving for cooling
Switching functions for external output terminal
Server room control switching

After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.

9387082050_IM.indb   9

12/10/2015   13:33:28

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for ASYG36LMTA

Page 1: ... Leakage Circuit Breaker ELCB CAUTION This product is not explosion proof and therefore should not be installed in explosive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical components This product contains no user serviceable...

Page 2: ...r 1 Saddle 1 set Wall pipe 1 Drain hose 1 Decorative tape 1 Tapping screws 1 set Vinyl tape 1 Sealant 1 2 4 Optional parts Refer to each installation manual for the method of installing optional parts Parts name Model name Application Wired Remote Controller UTY RVN M For air conditioner operation Wired Remote Controller UTY RNR Z1 For air conditioner operation Wired Remote Controller UTY RLR For ...

Page 3: ...The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Install the indoor unit on the wall where the height from the floor is more than 1 8 m 6 INSTALLATION WORK...

Page 4: ...xagonal wrench 4 mm at opposite side to insert the drain cap till the drain cap contacts the tip of the drain cock No gap Hexagonal wrench Drain cock Drain cap CAUTION Insert the drain hose and drain cap into the drain port making sure that it comes in contact with the back of the drain port and then mount it If the drain hose is not connected properly leaking will occur For left piping and left r...

Page 5: ... using the specified tightening method Otherwise the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water from leaking into the control box make sure that the piping is well...

Page 6: ...tallation may cause a fire When fixing the connection cable with the cable clamp always fasten the cable at the plastic jacket portion but not at the insulator portion If the insulator is chafed electric leakage may occur Always connect the earth ground wire Improper earthing grounding work can cause electric shocks Do not use the earth ground screw for the indoor unit to the outdoor unit unless i...

Page 7: ...der to a wall pillar etc with the tapping screw Remote controller holder fixing Remote controller mounting Remote controller holder Tapping screw small 1 Set Remote controller 2 Down 12 OPTIONAL KIT INSTALLATION This air conditioner can be connected with the following optional kits Wired remote controller Simple remote controller External connect kit External input and output PCB 9 FRONT PANEL REM...

Page 8: ...umber selection 3 Press the TEMP buttons to select the set ting value Press the 10 C HEAT button to switch between the left and right digits 4 Press the MODE button once to send the function set ting information Please confirm the beeping sound 5 Next please press Start Stop button once to fix the function setting Please confirm the beeping sound 6 Press the RESET button to cancel the function set...

Page 9: ...n be selected Factory setting Setting Description Function Number Setting Value Operation Stop mode1 46 00 Setting forbidden 01 Forced stop mode 02 Operation Stop mode 2 03 Room temperature sensor switching Aux To use the temperature sensor on the wired remote controller only change the setting to Wired remote controller 01 This function will only work if the function setting 42 is set at Both 01 ...

Page 10: ...uto switch error 4 1 Room temp sensor error 4 2 Indoor unit Heat Ex Middle temp sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 8 Intake grille error 5 15 Indoor unit error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PCB microcomputer...