En-9
Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may
be required. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting “00”
(manufacturer’s recommended value).
(♦... Factory setting)
Setting Description
Function
Number
Setting Value
♦
Standard setting
30
(For cooling)
31
(For heating)
00
No correction 0.0 °C
01
-0.5 °C
More cooling
Less heating
02
-1.0 °C
03
-1.5 °C
04
-2.0 °C
05
-2.5 °C
06
-3.0 °C
07
-3.5 °C
08
-4.0 °C
09
+0.5 °C
Less cooling
More heating
10
+1.0 °C
11
+1.5 °C
12
+2.0 °C
13
+2.5 °C
14
+3.0 °C
15
+3.5 °C
16
+4.0 °C
17
Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor
may be required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”.
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
(♦... Factory setting)
Setting Description
Function
Number
Setting Value
♦
No correction
35
(For cooling)
36
(For heating)
00
No correction 0.0 °C
01
-0.5 °C
More cooling
Less heating
02
-1.0 °C
03
-1.5 °C
04
-2.0 °C
05
-2.5 °C
06
-3.0 °C
07
-3.5 °C
08
-4.0 °C
09
+0.5 °C
Less cooling
More heating
10
+1.0 °C
11
+1.5 °C
12
+2.0 °C
13
+2.5 °C
14
+3.0 °C
15
+3.5 °C
16
+4.0 °C
17
Auto restart
Enable or disable automatic restart after a power interruption.
(♦... Factory setting)
Setting Description
Function
Number
Setting Value
♦
Enable
40
00
Disable
01
* Auto restart is an emergency function such as for power outage etc. Do not attempt to
use this function in normal operation. Be sure to operate the unit by remote controller or
external device.
Room temperature sensor switching
(Only for wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to “Both” (01).
(♦... Factory setting)
Setting Description
Function
Number
Setting Value
♦
Indoor unit
42
00
Both
01
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
* Remote controller sensor must be turned on by using the remote controller.
Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
(♦... Factory setting)
Setting Description
Function
Number
Setting Value
♦
A
44
00
B
01
C
02
D
03
External input control
“Operation/Stop” mode or “Forced stop” mode can be selected.
(♦... Factory setting)
Setting Description
Function
Number
Setting Value
♦
Operation/Stop mode1
46
00
(Setting forbidden)
01
Forced stop mode
02
Operation/Stop mode 2
03
Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to
“Wired remote controller” (01).
This function will only work if the function setting 42 is set at “Both” (01).
(♦... Factory setting)
Setting Description
Function
Number
Setting Value
♦
Both
48
00
Wired remote controller
01
Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when
the outdoor unit is stopped during cooling operation.
(♦... Factory setting)
Setting Description
Function
Number
Setting Value
Disable
49
00
Enable
01
♦
Remote controller
02
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
02: Enable or disable this function by remote controller setting.
* As the factory setting, this setting is initially activated.
* When connecting VRF system using network converter, this setting must be set to “00” or “01”.
Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External
input and output”.
(♦... Factory setting)
Setting Description
Function
Number
Setting Value
♦
Operation status
60
00
Error status
09
Indoor unit fan operation status
10
Set point attainment status
12
Server room control switching
Switches between normal control and server room control.
To use this function, address setting of the primary unit and secondary unit needs to be done.
(♦... Factory setting)
Setting Description
Function
Number
Setting Value
♦
Normal control
96
00
Server room control (Primary unit)
01
Server room control (Secondary unit)
02
Setting record
Record any changes to the settings in the following table.
Setting Description
Setting Value
Remote controller address setting
Filter sign
Room temperature control for indoor
unit sensor
Cooling
Heating
Room temperature control for wired
remote controller sensor
Cooling
Heating
Auto restart
Room temperature sensor switching
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
Indoor unit fan control for energy saving for cooling
Switching functions for external output terminal
Server room control switching
After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.