background image

En-10

15. CUSTOMER  GUIDANCE

Explain the following to the customer in accordance with the operating manual:

(1)  Starting and stopping method, operation switching, temperature adjustment, timer, air 

flow switching, and other remote control unit operations.

(2)  Air filter removal and cleaning, and how to use the air louvers.

(3) Give the operating manual to the customer.

16. ERROR  CODES

If you use a wireless remote controller, the lamp on the photo detector unit will output error 

codes by way of blinking patterns. If you use a wired remote controller, error codes will ap

-

pear on the remote control display. See the lamp blinking patterns and error codes in the 

table. An error display is displayed only during operation.

Error display

Wired 

remote 

controller

Error code

Description

OPERATION 

lamp

(green)

TIMER 

lamp

(orange)

ECONOMY 

lamp

(green)

(1)

(1)

Serial communication error

(1)

(2)

• Wired remote controller  

communication error

• Server room control  

communication error

(1)

(5)

Check run unfinished

(1)

(6)

Peripheral unit transmission PCB 
connection error

(2)

(1)

Unit number or Refrigerant circuit 
address setting error 
[Simultaneous Multi]

(2)

(2)

Indoor unit capacity error

(2)

(3)

Combination error

(2)

(4)

•  Connection unit number error 

(indoor slave unit) 
[Simultaneous Multi]

•  Connection unit number error 

(indoor unit or branch unit) 
[Flexible Multi]

(2)

(6)

Address setting error in wired 
remote controller system

(2)

(7)

Master unit, slave unit set-up error 
[Simultaneous Multi]

(3)

(2)

Indoor unit PCB model  
information error

(3)

(5)

Manual auto switch error

(4)

(1)

Room temp. sensor error 

(4)

(2)

Indoor unit Heat Ex. Middle temp. 
sensor error

(5)

(1)

Indoor unit fan motor error

(5)

(3)

Drain pump error

(5)

(7)

Damper error 

(5)

(8)

Intake grille error

(5)

(15)

Indoor unit error

(6)

(2)

Outdoor unit main PCB model 
information error or  
communication error

(6)

(3)

Inverter  error 

(6)

(4)

Active filter error, PFC circuit error 

(6)

(5)

Trip terminal L error

(6)

(10)

Display PCB microcomputers 
communication error  

(7)

(1)

Discharge temp. sensor error

(7)

(2)

Compressor temp. sensor error

(7)

(3)

Outdoor unit Heat Ex. liquid temp. 
sensor error

(7)

(4)

Outdoor temp. sensor error

(7)

(5)

Suction Gas temp. sensor error

(7)

(6)

• 2-way valve temp. sensor error
• 3-way valve temp. sensor error

(7)

(7)

Heat sink temp. sensor error

(8)

(2)

• Sub-cool Heat Ex. gas inlet 

temp. sensor error

• Sub-cool Heat Ex. gas outlet 

temp. sensor error

(8)

(3)

Liquid pipe temp. sensor error

(8)

(4)

Current sensor error

(8)

(6)

• Discharge pressure sensor error
• Suction pressure sensor error
• High pressure switch error

(9)

(4)

Trip detection

(9)

(5)

Compressor rotor position  
detection error 

(9)

(7)

Outdoor unit fan motor error

(9)

(9)

4-way valve error

(10)

(1)

Discharge temp. error

(10)

(3)

Compressor temp. error

(10)

(4)

High pressure error

(10)

(5)

Low pressure error

(13)

(2)

Branch boxes error 
[Flexible Multi]

Display mode 

 : 0.5s ON / 0.5s OFF

 : 0.1s ON / 0.1s OFF

( ) : Number of flashing

[Troubleshooting with the indoor unit display]

OPERATION indicator (green)

TIMER indicator (orange)

ECONOMY indicator (green)

[Troubleshooting with the Wired Remote Controller Display (Option)]

If an error occurs, the following display will be shown. (“Er” will appear in the set room 

temperature display.)

Error code

9387082050_IM.indb   10

12/10/2015   13:33:34

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for ASYG36LMTA

Page 1: ... Leakage Circuit Breaker ELCB CAUTION This product is not explosion proof and therefore should not be installed in explosive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical components This product contains no user serviceable...

Page 2: ...r 1 Saddle 1 set Wall pipe 1 Drain hose 1 Decorative tape 1 Tapping screws 1 set Vinyl tape 1 Sealant 1 2 4 Optional parts Refer to each installation manual for the method of installing optional parts Parts name Model name Application Wired Remote Controller UTY RVN M For air conditioner operation Wired Remote Controller UTY RNR Z1 For air conditioner operation Wired Remote Controller UTY RLR For ...

Page 3: ...The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Install the indoor unit on the wall where the height from the floor is more than 1 8 m 6 INSTALLATION WORK...

Page 4: ...xagonal wrench 4 mm at opposite side to insert the drain cap till the drain cap contacts the tip of the drain cock No gap Hexagonal wrench Drain cock Drain cap CAUTION Insert the drain hose and drain cap into the drain port making sure that it comes in contact with the back of the drain port and then mount it If the drain hose is not connected properly leaking will occur For left piping and left r...

Page 5: ... using the specified tightening method Otherwise the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water from leaking into the control box make sure that the piping is well...

Page 6: ...tallation may cause a fire When fixing the connection cable with the cable clamp always fasten the cable at the plastic jacket portion but not at the insulator portion If the insulator is chafed electric leakage may occur Always connect the earth ground wire Improper earthing grounding work can cause electric shocks Do not use the earth ground screw for the indoor unit to the outdoor unit unless i...

Page 7: ...der to a wall pillar etc with the tapping screw Remote controller holder fixing Remote controller mounting Remote controller holder Tapping screw small 1 Set Remote controller 2 Down 12 OPTIONAL KIT INSTALLATION This air conditioner can be connected with the following optional kits Wired remote controller Simple remote controller External connect kit External input and output PCB 9 FRONT PANEL REM...

Page 8: ...umber selection 3 Press the TEMP buttons to select the set ting value Press the 10 C HEAT button to switch between the left and right digits 4 Press the MODE button once to send the function set ting information Please confirm the beeping sound 5 Next please press Start Stop button once to fix the function setting Please confirm the beeping sound 6 Press the RESET button to cancel the function set...

Page 9: ...n be selected Factory setting Setting Description Function Number Setting Value Operation Stop mode1 46 00 Setting forbidden 01 Forced stop mode 02 Operation Stop mode 2 03 Room temperature sensor switching Aux To use the temperature sensor on the wired remote controller only change the setting to Wired remote controller 01 This function will only work if the function setting 42 is set at Both 01 ...

Page 10: ...uto switch error 4 1 Room temp sensor error 4 2 Indoor unit Heat Ex Middle temp sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 8 Intake grille error 5 15 Indoor unit error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PCB microcomputer...

Reviews: