background image

En-3

 CAUTION

Install the outdoor unit in a location that is away from exhaust or the vent ports that 
discharge vapor, soot, dust, or debris.

Install the indoor unit, outdoor unit, power supply cable, transmission cable, and remote 
control cable at least 1 m away from a television or radio receivers. The purpose of this 
is to prevent TV reception interference or radio noise. (Even if they are installed more 
than 1 m apart, you could still receive noise under some signal conditions.)

Branch switch and 
circuit breaker

1 m or more

1 m or more

Branch switch and 
circuit breaker

If children under 10 years old may approach the unit, take preventive measures so that 
they cannot reach the unit.

Keep the length of the piping of the indoor and outdoor units within the allowable range.

For maintenance purposes, do not bury the piping.

3.2. Drain installation

 

CAUTION

Perform drain work in accordance with this Manual, and ensure that the drain water is 
properly drained. If the drain work is not carried out correctly, water may drip down from 
the unit, wetting the furniture.

When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe 
and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may 
freeze in extremely cold weather. (Reverse cycle model only)

As the drain water 

fl

 ows out of the outdoor unit during heating operation, install the 

• 

drain pipe and connect it to a commercial 16 mm hose. (Reverse cycle model only)
When installing the drain pipe, plug all the holes other than the drain pipe mounting 

• 

hole in the bottom of the outdoor unit with putty so there is no water leakage. (Reverse 
cycle model only)

 

(Unit : mm)

Drain cap mounting hole

AIR

Drain pipe mounting hole

302

265

188

51

439

623

Base

Drain pipe

Drain pipe mounting hole

а

3.3. Installation dimensions

 CAUTION

The installation space shown in the following examples is based on an ambient 
temperature under cooling operation of 35 °C (DB) at the air intake of the outdoor unit. 
Provide more space around the air intake than shown in the examples if the ambient 
temperature exceeds 35 °C (DB) or if the thermal load of all of the outdoor units exceeds 
the capacity.

Consider the transportation route, installation space, maintenance space, and access, 
and install the unit in a location with suf

fi

 cient space for the refrigerant piping.

 CAUTION

Observe the installation space speci

fi

 cations that are shown in the 

fi

 gures.

Keep the same space at rear air intake.
Provide the same space for the air intake at the rear of the outdoor unit.
If the installation is not performed according to the speci

fi

 cations, it could cause a short 

circuit and result in a lack of operating performance. As a result, the outdoor unit might 
easily be stopped by high-pressure protection. 

Air intake

Rear view

Installation methods not shown in the following examples are not recommended. 
Performance may drop signi

fi

 cantly.

3.3.1. Single outdoor unit installation

When the upward area is open 

(Unit : mm)

(1) Obstacles at rear only

150

(2) Obstacles at rear and sides only

200

300

200

(3) Obstacles at front only

1000 or more

(4) Obstacles at front and rear only

1000 or more

150

When an obstruction is present also in the upward area 

(Unit : mm)

(1) Obstacles at rear and above only

300

Max. 500

1000

(2)  Obstacles at rear, sides, and above only

1500

250

250

500

Max. 500

3.3.2. Multiple outdoor unit installation

Provide at least 15 mm of space between the outdoor units if multiple units are 

• 

installed.
When routing the piping from the side of an outdoor unit, provide space for the piping.

• 

No more than 3 units must be installed side by side. When 3 units or more are 

• 

arranged in a line, provide the space as shown in the following example when an 
obstruction is present also in the upward area.

When the upward area is open 

(Unit : mm)

(1) Obstacles at rear only

300

(2) Obstacles at front only

1500 or more

9379069403_IM.indb   3

9379069403_IM.indb   3

1/29/2013   4:44:18 PM

1/29/2013   4:44:18 PM

Summary of Contents for AOYG60LATT

Page 1: ...vicio autorizado MANUALE DI INSTALLAZIONE UNITÀ ESTERNA A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΞΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE EXTERIOR Apenas para pessoal de assistência autorizado РУКОВОДСТВО ПО УСТАНОВКЕ ВНЕШНИЙ МОДУЛЬ Только для авторизованного обслуживающего персонала MONTAJ KILAVUZU DIŞ ÜNİTE Yalnızca...

Page 2: ...ncluding children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance Do not touch the aluminum fins of heat exchanger built in the indoor or outdoor unit...

Page 3: ...nce other than the prescribed refrigerant into the refrigeration cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leak make sure that it does not exceed the concentration limit If a refrigerant leak exceeds the concentration limit it can lead to accidents such as oxygen starvati...

Page 4: ...tion space shown in the following examples is based on an ambient temperature under cooling operation of 35 C DB at the air intake of the outdoor unit Provide more space around the air intake than shown in the examples if the ambient temperature exceeds 35 C DB or if the thermal load of all of the outdoor units exceeds the capacity Consider the transportation route installation space maintenance s...

Page 5: ...n which may cause noise and vibration Therefore attach damping materials such as damping pads to the outdoor unit during installation Install the foundation making sure that there is enough space for installing the connection pipes Secure the unit to a solid block using foundation bolts Use 4 sets of commercially available M10 bolts nuts and washers The bolts should protrude 20 mm Refer to the fig...

Page 6: ...ont lateral side rear side and bottom Fig A When connecting at the bottom remove the service panel and piping cover on the front of the outdoor unit and open the knock out hole provided at the bottom corner of the piping outlet It can be installed as shown on Fig B cutting out the 2 slits as indicated on Fig C When cutting slits use a steel saw Fig A Service panel Front connection Bottom connectio...

Page 7: ...tighten the flare nut correctly Outer panel may be distorted if fastened only with a wrench Be sure to fix the elementary part with a spanner and fasten with a wrench refer to below diagram Do not apply force to the blank cap of the valve or hang a wrench etc on the cap It may cause leakage of refrigerant Blank cap Flare nut Torque wrench Holding wrench Torque wrench 90 Flare nut mm in Tightening ...

Page 8: ...harge from the liquid phase side whose composition is stable Adding refrigerant through the gas pipe will cause a malfunction Check if the steel cylinder has a siphon installed or not before filling There is an indication with siphon for filling liquid on the steel cylinder Filling method for cylinder with siphon R410A Gas Liquid Set the cylinder vertical and fill with the liquid Liquid can be fil...

Page 9: ...mission cable come in contact with valves Gas Never install a power factor improvement condenser Instead of improving the power factor the condenser may overheat Be sure to perform the earthing grounding work Do not connect earthing grounding wires to a gas pipe water pipe lightning rod or earthing grounding wire for a telephone Connection to a gas pipe may cause a fire or explosion if gas leaks C...

Page 10: ... the insulation sheet after the wiring is complete s d 7 PIPE INSTALLATION 2 WARNING Install the insulated pipes so that they do not touch the compressor 7 1 Installing insulation Use an insulation on the refrigerant pipes to prevent condensation and dripping Fig A Determine the thickness of the insulation material by referring to Table A Table A Selection of insulation for using an insulation mat...

Page 11: ...ting is activated Lighting pattern of L5 L6 and L7 indicates peak cut level B Refer to 9 LOCAL SETTING Switch Function or operation method SW1 DIP switch For selecting cooling or heating during test operation Positions 2 to 4 of DIP switch are not used SW2 Push switch To switch between Local setting and Error code display SW3 Push switch To switch between the individual Local settings and the Erro...

Page 12: ... LOW NOISE Blink PEAK CUT MODE 4 Press ENTER switch SW4 TEST RUN L1 L2 L3 L4 PUMP DOWN LOW NOISE PEAK CUT MODE Sign Lights on 5 Press SELECT switch SW3 and adjust LED display as shown in below figure PEAK CUT L5 L6 L7 Blink Blink Blink Blink Blink 0 of rated input ratio 50 of rated input ratio 75 of rated input ratio 100 of rated input ratio 9 1 1 Setting for low noise SW2 SW3 SW4 SW5 LED display ...

Page 13: ...ay Normal operation by pressing EXIT switch SW5 When pressed number is lost during operation restart from the beginning of operation procedure after returning to Operation status display normal operation by pressing the EXIT switch once s d 10 TEST RUN CAUTION Always turn on the power 6 hours prior to the start of the operation in order to protect the compressor 10 1 Check items before performing ...

Page 14: ...sed refrigerant may flow into the piping after the compressor stops Step 5 Closing direction Step 4 Hexagon wrench Liquid pipe Gas pipe Closing direction 6 LED display changes after 1 minute as shown in the figure below ERROR TEST RUN PUMP DOWN LOW NOISE PEAK CUT POWER MODE L1 L2 L3 L4 L5 L6 L7 Fans and compressor stop automatically If the pump down is successfully completed the above LED display ...

Page 15: ... 2 Compressor temp sensor error 2 7 3 Heat Ex middle temp sensor error 2 7 3 Outdoor unit Heat Ex liquid temp sensor error 2 7 4 Outdoor temp sensor error 2 7 7 Heat sink temp sensor error 2 7 7 PFC heat sink temp sensor error 2 8 4 Current sensor 1 error stoppage permanently 2 8 6 High pressure switch 1 error 2 8 6 Pressure sensor error 2 9 4 Trip detection stoppage permanently 2 9 5 Compressor m...

Reviews: