En-6

 CAUTION

The static electricity that is charged to the human body can damage the control PC 

Board when handling the control PC Board for address setting, etc. 

Please keep caution to the following points. 

Provide the grounding of Indoor unit, Outdoor unit and Option equipment. 

Cut off the power supply (breaker).

 

Touch the metal section (such as the unpainted control box section) of the indoor or 

outdoor unit for more than 10 seconds. Discharge the static electricity in your body. 

Never touch the component terminal or pattern on the PC Board.

Electrical requirement

31 21 

 CAUTION

Be sure to install a breaker of the specified capacity.

Regulation of cables and breaker differs from each locality, refer in accordance with 

local rules.

Voltage rating

1Φ 230V (50Hz)

Operating range

198-264V

Cable

Cable size (mm

2

*1

Type

Remarks 

Power supply cable

4.0

Type 60245 

IEC 66

2 cable + Earth (Ground), 

 

1 Ø 230V

Connection cable

1.5

Type 60245 

IEC 57

3 cable + Earth (Ground), 

 

1 Ø 230V

*1

   Selected sample: Select the correct cable type and size according to the country or 

region’s regulations. 

Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the 

wire diameter when the wire length is long. 

Breaker

Specification

*2

Circuit breaker (over current)

Current : 25 (A)

Earth leakage breaker

Leakage current : 30mA 0.1sec or less

*

3

*2

   Select the appropriate breaker of the described specification according to the national 

or regional standards.

*3

   Select the breaker that enough load current can pass through it.

Before starting work check that power is not being supplied to all poles of the indoor unit 

 

and outdoor unit.

Install all electrical works in accordance to standard.

 

Install the disconnect device with a contact gap of at least 3mm in all poles nearby the 

 

units. (Both indoor unit and outdoor unit)

Wiring size must comply with the applicable local and national code. 

 

Unit wiring

31 21 

When stripping off the coating of a lead wire, always use a special tool such as a wire 

 

stripper. If there is no special tool available, carefully strip the coating with a knife etc.

Earth (Ground) wire

30 mm

100 mm or more

Power supply cable

Earth (Ground) wire

15 mm

60 mm or more

Connection cable

How to connect wiring to the terminal

Caution when wiring cable 

Use crimp-type terminals with insulating sleeves as shown in the figure to 

(

1

)

 

connect to the terminal block.

Securely clamp the crimp-type terminals to the wires using an appropriate tool 

(

2

)

 

so that the wires do not come loose1

Use the specified wires, connect them securely, and fasten them so that there is 

(

3

)

 

no stress placed on the terminals1

Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

(

4

)

 

screwdriver that is too small, otherwise, the screw heads may be damaged and 

prevent the screws from being properly tightened.

Do not tighten the terminal screws too much, otherwise, the screws may break.

(

5

)

 

See the table below for the terminal screw tightening torques1

(

6

)

 

Strip : 10mm

Wire

Terminal blocks

Crimp-type 

terminal

Sleeve

Wire

Crimp-type 

terminal

Screw with 

special washer

Screw with special washer

Crimp-type terminal

Tightening torque [N·m (kgf·cm)]

M4 screw

1.2 to 1.8 (12 to 18)

 Connection diagrams

31 41 

1

2

3

1

2

3

1

2

3

1

2

3

1

2

3

1

2

3

1

2

3

1

2

3

OUTDOOR UNIT

Power cable

EARTH 

(GROUND)

D

D

C

C

B

B

A

L

N

A

POWER

230V

50 Hz · 1ø

INDOOR UNIT

Connection cable

Connection cable

Connection cable

Connection cable

Outdoor unit

31 31 

Service panel removal

(

1

)

 

Remove the two mounting 

 

screws.

Remove the service panel 

 

by pushing downwards.

Hook

(3 places)

Service 

panel

Direction of the 

service panel 

removal

Connect the power supply 

(

2

)

 

cable and the connection 

cable to terminal.

Power cable

UNIT D 

connection 

cable

UNIT C 

connection 

cable

UNIT B 

connection 

cable

UNIT A 

connection 

cable

Fasten the power supply 

(

3

)

 

cable and connection 

cable with cable clamp.

UNIT A 

UNIT B 

UNIT C 

UNIT D 

9374872121-03_IM.indb   6

2/10/2555   10:07:56

Summary of Contents for aoyg30lat4

Page 1: ...AZIONE ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ MANUAL DE INSTALAÇÃO РУКОВОДСТВО ПО УСТАНОВКЕ MONTAJ KILAVUZU For authorized personnel only PART NO 9374872121 03 Nur für autorisiertes Personal Pour le personnel agréé uniquement Solo para personal autorizado Ad uso esclusivo del personale autorizzato Για εξουσιοδοτημένο προσωπικό σέρβις Apenas para técnicos autorizados Для уполномоченного персонала Yetkili servis p...

Page 2: ... all security information before use or install the air conditioner Do not attempt to install the air conditioner or a part of the air conditioner by yourself This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids Refer to regulation and laws in use on installation place The installation must be carried out in compliance with regulations in f...

Page 3: ...ce 230 V 50 Hz Power cable Connection cable Refrigerant pipe d c H1 H1 H2 b a CONNECTABLE INDOOR UNIT CAPACITY TYPE 222222222 CAUTION The total capacity of the indoor units connected must be between 27 000 and 49 000BTU Be sure to check the connecting pattern in technical manual when installed since connection pattern is specified in it Operation cannot be guaranteed if connected by a method not s...

Page 4: ... accumulation snow fall or freezing take appropriate measures to protect it from those elements To ensure a stable operation install inlet and outlet ducts Install the outdoor unit in a location that is away from exhaust or the vent ports that discharge vapor soot dust or debris Install the indoor unit outdoor unit power supply cable connection cable and remote controller cable at least 1 m away f...

Page 5: ...h as concrete blocks The foundation shall support the legs of the unit and have a width of 50mm or more Depending on the installation conditions the outdoor unit may spread its vibration during operation which may cause noise and vibration Therefore attach damping materials such as damping pads to the outdoor unit during installation Install the foundation making sure that there is enough space fo...

Page 6: ...63 to 75 630 to 750 19 05 3 4 dia 90 to 110 900 to 1100 HOW TO USE ADAPTER Connection ports of outdoor unit 444444444 When using the ADAPTER be careful not to overtighten the nut or the smaller pipe may be damaged Apply a coat of refrigeration oil to the threaded connection port of the outdoor unit where the flare nut comes in Use appropriate wrenches to avoid damaging the connection thread by ove...

Page 7: ...t comply with the applicable local and national code Unit wiring 555555 When stripping off the coating of a lead wire always use a special tool such as a wire stripper If there is no special tool available carefully strip the coating with a knife etc Earth Ground wire 30 mm 100 mm or more Power supply cable Earth Ground wire 15 mm 60 mm or more Connection cable How to connect wiring to the termina...

Page 8: ... it is satisfactory If a pressure decrease is confirmed there is a leak so it is necessary to specify the leak location and make minor adjustments Discharge the nitrogen gas and starting removing the gas with a vacuum pump Open the valve of the gauge manifold fully Operate the vacuum pump and start pump down Check that the compound pressure gauge reads 0 1 MPa 76 cmHg operate the vacuum pump for 3...

Page 9: ...sor error for Indoor unit D 5 times 3 way valve temp sensor error for Indoor unit A 6 times 3 way valve temp sensor error for Indoor unit B 6 times 3 way valve temp sensor error for Indoor unit C 6 times 3 way valve temp sensor error for Indoor unit D 6 times Compressor temp sensor error 7 times Heat sink temp sensor error 8 times High pressure switch 1 error 9 times High pressure switch 2 error 1...

Reviews: