En-4

Single outdoor unit installation 

21 21 11 
When the upward area is open

When there are 

 

obstacles at the 

back side.

100 mm

 

or more

AIR

When there are 

 

obstacles at the 

back and front 

sides.

100 mm

 

or more

600 mm

 

or more

AIR

When an obstruction is present also in the upward area

 

When there are 

 

obstacles at the 

back, side(s), and 

top

100-300 mm* 

 

250 mm or more 

(Service space)

300 mm 

 

or more

60

0-1

000

 mm*

AIR

If the space is larger than that is stated, the condition will be the same as that there are no 

obstacles.

Multiple outdoor unit installation

21 21 21 

Provide at least 250 mm of space between the outdoor units if multiple units are installed.

 

When routing the piping from the side of an outdoor unit, provide space for the piping.

 

No more than 3 units must be installed side by side. 

 

When 3 units or more are arranged in a line, provide the space as shown in the following 

example when an obstruction is present also in the upward area. 

When there are obstacles at the back side with the installation of more than one unit.

 

250 mm 

 

or more

250 mm 

 

or more

300

 mm 

 

or more

AIR

Transportation of the unit

21 41 

 WARNING

Do not touch the fins. Otherwise, personal injury could result.

 CAUTION

When carrying the unit, hold the handles on the right and left sides and be careful. 

If the outdoor unit is carried from the bottom, hands or fingers may be pinched.

Be sure to hold the handles on the sides of the unit. Otherwise, holding the suction grille 

 

on the sides of the unit may cause deformation.

Handle

Installation of the unit

21 31 

Install 4 anchor bolts at the locations indicated with arrows in the figure.

 

To reduce vibration, do not install the unit directly on the ground. Install it on a secure 

 

base (such as concrete blocks).

The foundation shall support the legs of the unit and have a width of 50mm or more.

 

Depending on the installation conditions, the outdoor unit may spread its vibration during 

 

operation, which may cause noise and vibration. Therefore, attach damping materials 

(such as damping pads) to the outdoor unit during installation.

Install the foundation, making sure that there is enough space for installing the connection 

 

pipes.

Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially 

 

available M10 bolts, nuts, and washers.)

The bolts should protrude 20mm. (Refer to the figure.)

 

If overturning prevention is required, purchase the necessary commercially available 

 

items.

650mm

Bottom side

4-ø12 hole

370mm

AIR

Fix securely with bolts on a solid block. (Use 4 sets of commercially available M10 bolt, 

nut and washer.)

Bolt

Nut 

Block

PIPE INSTALLATION I

41 

Flare connection (pipe connection)

41 11 

 CAUTION

Do not use mineral oil on a flared part. Prevent mineral oil from getting into the system 

as this would reduce the lifetime of the units.

While welding the pipes, be sure to blow dry nitrogen gas through them.

The maximum lengths of this product are shown in the table. If the units are further 

apart than this, correct operation cannot be guaranteed.

Flaring

Use special pipe cutter and flare tool exclusive for R410A.

 

Cut the connection pipe to the necessary length with a pipe cutter.

(

1

)

 

Hold the pipe downward so that the cuttings will not enter the pipe and remove any 

(

2

)

 

burrs.

Insert the flare nut (always use the flare nut attached to the indoor and outdoor units 

(

3

)

 

respectively) onto the pipe and perform the flare processing with a flare tool. Leakage 

of refrigerant may result if other flare nuts are used.

Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

(

4

)

 

entering the pipes.

L

Check if [L] is flared uniformly

and is not cracked or scratched.

Pipe

A

B

Die

9374872121-03_IM.indb   4

2/10/2555   10:07:54

Summary of Contents for aoyg30lat4

Page 1: ...AZIONE ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ MANUAL DE INSTALAÇÃO РУКОВОДСТВО ПО УСТАНОВКЕ MONTAJ KILAVUZU For authorized personnel only PART NO 9374872121 03 Nur für autorisiertes Personal Pour le personnel agréé uniquement Solo para personal autorizado Ad uso esclusivo del personale autorizzato Για εξουσιοδοτημένο προσωπικό σέρβις Apenas para técnicos autorizados Для уполномоченного персонала Yetkili servis p...

Page 2: ... all security information before use or install the air conditioner Do not attempt to install the air conditioner or a part of the air conditioner by yourself This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids Refer to regulation and laws in use on installation place The installation must be carried out in compliance with regulations in f...

Page 3: ...ce 230 V 50 Hz Power cable Connection cable Refrigerant pipe d c H1 H1 H2 b a CONNECTABLE INDOOR UNIT CAPACITY TYPE 222222222 CAUTION The total capacity of the indoor units connected must be between 27 000 and 49 000BTU Be sure to check the connecting pattern in technical manual when installed since connection pattern is specified in it Operation cannot be guaranteed if connected by a method not s...

Page 4: ... accumulation snow fall or freezing take appropriate measures to protect it from those elements To ensure a stable operation install inlet and outlet ducts Install the outdoor unit in a location that is away from exhaust or the vent ports that discharge vapor soot dust or debris Install the indoor unit outdoor unit power supply cable connection cable and remote controller cable at least 1 m away f...

Page 5: ...h as concrete blocks The foundation shall support the legs of the unit and have a width of 50mm or more Depending on the installation conditions the outdoor unit may spread its vibration during operation which may cause noise and vibration Therefore attach damping materials such as damping pads to the outdoor unit during installation Install the foundation making sure that there is enough space fo...

Page 6: ...63 to 75 630 to 750 19 05 3 4 dia 90 to 110 900 to 1100 HOW TO USE ADAPTER Connection ports of outdoor unit 444444444 When using the ADAPTER be careful not to overtighten the nut or the smaller pipe may be damaged Apply a coat of refrigeration oil to the threaded connection port of the outdoor unit where the flare nut comes in Use appropriate wrenches to avoid damaging the connection thread by ove...

Page 7: ...t comply with the applicable local and national code Unit wiring 555555 When stripping off the coating of a lead wire always use a special tool such as a wire stripper If there is no special tool available carefully strip the coating with a knife etc Earth Ground wire 30 mm 100 mm or more Power supply cable Earth Ground wire 15 mm 60 mm or more Connection cable How to connect wiring to the termina...

Page 8: ... it is satisfactory If a pressure decrease is confirmed there is a leak so it is necessary to specify the leak location and make minor adjustments Discharge the nitrogen gas and starting removing the gas with a vacuum pump Open the valve of the gauge manifold fully Operate the vacuum pump and start pump down Check that the compound pressure gauge reads 0 1 MPa 76 cmHg operate the vacuum pump for 3...

Page 9: ...sor error for Indoor unit D 5 times 3 way valve temp sensor error for Indoor unit A 6 times 3 way valve temp sensor error for Indoor unit B 6 times 3 way valve temp sensor error for Indoor unit C 6 times 3 way valve temp sensor error for Indoor unit D 6 times Compressor temp sensor error 7 times Heat sink temp sensor error 8 times High pressure switch 1 error 9 times High pressure switch 2 error 1...

Reviews: