AIR CONDITIONER  

OUTDOOR UNIT

INSTALLATION MANUAL

INSTALLATIONSANLEITUNG

MANUEL D'INSTALLATION

MANUAL DE INSTALACIÓN

MANUALE D'INSTALLAZIONE

ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ

MANUAL DE INSTALAÇÃO

РУКОВОДСТВО ПО УСТАНОВКЕ

MONTAJ KILAVUZU

For authorized personnel only.

PART NO. 9374872121-03

Nur für autorisiertes Personal.

Pour le personnel agréé uniquement.

Solo para personal autorizado.

Ad uso esclusivo del personale autorizzato.

Για εξουσιοδοτημένο προσωπικό σέρβις.

Apenas para técnicos autorizados.

Для уполномоченного персонала.

Yetkili servis personeli içindir.

9374872121-03_IM.indb   1

2/10/2555   10:07:45

Summary of Contents for aoyg30lat4

Page 1: ...AZIONE ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ MANUAL DE INSTALAÇÃO РУКОВОДСТВО ПО УСТАНОВКЕ MONTAJ KILAVUZU For authorized personnel only PART NO 9374872121 03 Nur für autorisiertes Personal Pour le personnel agréé uniquement Solo para personal autorizado Ad uso esclusivo del personale autorizzato Για εξουσιοδοτημένο προσωπικό σέρβις Apenas para técnicos autorizados Для уполномоченного персонала Yetkili servis p...

Page 2: ... all security information before use or install the air conditioner Do not attempt to install the air conditioner or a part of the air conditioner by yourself This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids Refer to regulation and laws in use on installation place The installation must be carried out in compliance with regulations in f...

Page 3: ...ce 230 V 50 Hz Power cable Connection cable Refrigerant pipe d c H1 H1 H2 b a CONNECTABLE INDOOR UNIT CAPACITY TYPE 222222222 CAUTION The total capacity of the indoor units connected must be between 27 000 and 49 000BTU Be sure to check the connecting pattern in technical manual when installed since connection pattern is specified in it Operation cannot be guaranteed if connected by a method not s...

Page 4: ... accumulation snow fall or freezing take appropriate measures to protect it from those elements To ensure a stable operation install inlet and outlet ducts Install the outdoor unit in a location that is away from exhaust or the vent ports that discharge vapor soot dust or debris Install the indoor unit outdoor unit power supply cable connection cable and remote controller cable at least 1 m away f...

Page 5: ...h as concrete blocks The foundation shall support the legs of the unit and have a width of 50mm or more Depending on the installation conditions the outdoor unit may spread its vibration during operation which may cause noise and vibration Therefore attach damping materials such as damping pads to the outdoor unit during installation Install the foundation making sure that there is enough space fo...

Page 6: ...63 to 75 630 to 750 19 05 3 4 dia 90 to 110 900 to 1100 HOW TO USE ADAPTER Connection ports of outdoor unit 444444444 When using the ADAPTER be careful not to overtighten the nut or the smaller pipe may be damaged Apply a coat of refrigeration oil to the threaded connection port of the outdoor unit where the flare nut comes in Use appropriate wrenches to avoid damaging the connection thread by ove...

Page 7: ...t comply with the applicable local and national code Unit wiring 555555 When stripping off the coating of a lead wire always use a special tool such as a wire stripper If there is no special tool available carefully strip the coating with a knife etc Earth Ground wire 30 mm 100 mm or more Power supply cable Earth Ground wire 15 mm 60 mm or more Connection cable How to connect wiring to the termina...

Page 8: ... it is satisfactory If a pressure decrease is confirmed there is a leak so it is necessary to specify the leak location and make minor adjustments Discharge the nitrogen gas and starting removing the gas with a vacuum pump Open the valve of the gauge manifold fully Operate the vacuum pump and start pump down Check that the compound pressure gauge reads 0 1 MPa 76 cmHg operate the vacuum pump for 3...

Page 9: ...sor error for Indoor unit D 5 times 3 way valve temp sensor error for Indoor unit A 6 times 3 way valve temp sensor error for Indoor unit B 6 times 3 way valve temp sensor error for Indoor unit C 6 times 3 way valve temp sensor error for Indoor unit D 6 times Compressor temp sensor error 7 times Heat sink temp sensor error 8 times High pressure switch 1 error 9 times High pressure switch 2 error 1...