En-11

 CUSTOMER GUIDANCE

15. 

Explain the following to the customer in accordance with the operating manual:
(1)  Starting and stopping method, operation switching, temperature adjustment, timer, air 

ß

 ow switching, and other remote control unit operations.

(2)  Air 

Þ

 lter removal and cleaning, and how to use the air louvers.

(3) Give the operating manual to the customer.

 ERROR CODES

16. 

If you use a wireless remote controller, the lamp on the photo detector unit will output er-
ror codes by way of blinking patterns. If you use a wired remote controller, error codes will 
appear on the remote controller display. See the lamp blinking patterns and error codes in 
the table. An error display is displayed only during operation.

Error display

Wired 

remote 

controller 

Error code

Description

OPERATION 

lamp

(green)

TIMER 

lamp

(orange)

ECONOMY 

lamp

(green)

(

(1)

(

(1)

)

Serial communication error

(

(1)

(

(2)

)

Wired remote controller 
communication  error

(

(1)

(

(5)

)

Check run unfinished

(

(2)

(

(1)

)

Unit number or Refrigerant circuit 
address setting error [Simultane-
ous Multi]

(

(2)

(

(2)

)

Indoor unit capacity error

(

(2)

(

(3)

)

Combination error

(

(2)

(

(4)

)

•  Connection unit number error 

(indoor slave unit) [Simultane-
ous Multi]

•  Connection unit number error 

(indoor unit or branch unit) 
[Flexible Multi]

(

(2)

(

(7)

)

Master unit, slave unit set-up 
error [Simultaneous Multi]

(

(3)

(

(2)

)

Indoor unit PCB model 
information error

(

(3)

(

(5)

)

Manual auto switch error

(

(4)

(

(1)

)

Room temp. sensor error 

(

(4)

(

(2)

)

Indoor unit Heat Ex. Middle temp. 
sensor error

(

(5)

(

(1)

)

Indoor unit fan motor error

(

(5)

(

(3)

)

Drain pump error

(

(5)

(

(7)

)

Damper error

(

(5)

(

(8)

)

Intake grille error

(

(5)

(

(15)

)

Indoor unit error

(

(6)

(

(2)

)

Outdoor unit main PCB model 
information error or 
communication error

(

(6)

(

(3)

)

Inverter  error 

(

(6)

(

(4)

)

Active filter error, PFC circuit er-
ror 

(

(6)

(

(5)

)

Trip terminal L error

(

(6)

(

(10)

)

Display PCB microcomputers 
communication error  

(

(7)

(

(1)

)

Discharge temp. sensor error

(

(7)

(

(2)

)

Compressor temp. sensor error

(

(7)

(

(3)

)

Outdoor unit Heat Ex. liquid 
temp. sensor error

(

(7)

(

(4)

)

Outdoor temp. sensor error

(

(7)

(

(5)

)

Suction Gas temp. sensor error

(

(7)

(

(6)

)

2-way valve temp. sensor error

• 

3-way valve temp. sensor error

• 

Heating Room Temperature Correction

 Depending on the installed environment, the room temperature sensor may require a cor-
rection. 
  The settings may be changed as shown in the table below.

(

'

...  Factory setting)

Setting Description 

Function 

Number

Setting Value

'

Standard

31

00

Lower control

01

Slightly warmer control

02

Warmer control

03

Auto Restart

 Enable or disable automatic system restart after a power outage. 

(

'

...  Factory setting)

Setting Description

Function 

Number

Setting Value

'

   Yes

40

00

No

01

*  Auto restart is an emergency function such as for power failure etc. Do not start and stop 

the indoor unit by this function in normal operation. Be sure to operate by the control unit, 
or external input device.

Indoor room temperature sensor switching function

(Only for wired remote controller)
The  following  settings  are  needed  when  using  the  wired  remote  controller  temperature 
sensor.

(

'

...  Factory setting)

Setting Description

Function 

Number

Setting Value

'

   No

42

00

Yes

01

* If setting value is “00” : 

 Room temperature is controlled by the indoor unit temperature sensor.

* If setting value is “01” : 

 Room temperature is controlled by either indoor unit temperature sensor or remote con-
troller unit sensor.

Remote controller signal code

 Change the indoor unit Signal Code, depending on the remote controllers.

(

'

...  Factory setting)

Setting Description 

Function 

Number

Setting Value

'

   A

44

00

B

01

C

02

D

03

External input control

 “Operation/Stop” mode or “Forced stop” mode can be elected.

(

'

...  Factory setting)

Setting Description 

Function 

Number

Setting Value

'

Operation/Stop mode

46

00

(Setting forbidden)

01

Forced stop mode

02

Setting record

Record any changes to the settings in the following table.

Setting Description

Setting Value

Filter sign

Cooler room temperature correction

Heater room temperature correction

Auto restart

Indoor room temperature sensor switching function 

Remote controller signal code

External input control

After  completing  the  FUNCTION  SETTING,  be  sure  to  turn  off  the  power  and  turn  it  on 
again.

Summary of Contents for AOYG14LTCN

Page 1: ... Swedish Polish AIR CONDITIONER ASENNUSOHJE SISÄYKSIKKÖ seinälle asennettava malli Vain valtuutetuille huoltohenkilöille INSTALLASJONSVEILEDNING INNENDØRSENHET veggmontert modell Kun for autorisert servicepersonell INSTALLATIONSHANDBOK INOMHUSENHET väggmonterad Endast för auktoriserad servicepersonal INSTRUKCJA MONTA U URZ DZENIE WEWN TRZNE do monta u ciennego Do u ytku wy cznie przez autoryzowany...

Page 2: ...use damage or malfunction of your property ABOUT THE UNIT 2 Precautions for using R410A refrigerant 2 1 The basic installation work procedures are the same as conventional refrigerant R22 models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 models some of the piping and installation and service tools a...

Page 3: ...s to secure refrigerant piping ELECTRICAL REQUIREMENT 4 The indoor unit is powered from the outdoor unit or branch box Do not power indoor unit from separate power source WARNING Refer to local codes for acceptable cable type Cable Cable size Remarks Connection cable Type 60245 IEC 57 3 cable Ground 1 Ø 230 V Max Cable Length Limit voltage drop to less than 2 Increase cable gauge if voltage drop i...

Page 4: ...g When the piping is connected in direction 2 3 4 or 5 use a cutting tool to cut along the groove for the piping that will coming out of the under cover For 5 Left outlet For 4 Left bottom outlet For 3 Right bottom outlet For 2 Right outlet Cutting the hole in the wall for the connecting piping 6 6 1 Cut a 65 mm diameter hole in the wall at the position shown in the following 2 Cut the hole so tha...

Page 5: ... and left rear piping align the marks on the wall hook bracket and shape the connection pipe Bend the connection piping at a bend radius of 70 mm or more and install no more than 35 mm from the wall After passing the indoor piping and drain hose through the wall hole hang the indoor unit on the hooks at the top and bottom of the wall hook bracket No gap Hexagonal wrench Drain cock Drain cap Instal...

Page 6: ... line Type 245 IEC57 Inter unit OUTDOOR UNIT or BRANCH BOX Please connect it to the speciÞed terminal INDOOR UNIT TERMINAL Power line Control line Indoor unit wiring 7 2 1 Remove the wire cover Remove the 1 screw 2 Remove the cable clamp Remove the 1 screw 3 Bend the end of the connection cable as shown in the Þgure 4 Connect the end of the connection cable fully inserting into the terminal block ...

Page 7: ...e Connection cable Pipe Drain hose Check the following GOOD Drain hose Saddle Lifted up Wave End in water Drain hose Connection pipe Wall pipe Connection cable Left piping For connection from the left rear NO GOOD NO GOOD NO GOOD Pipe Connection pipe heat insulation Bind the pipes together so that there is no gap Indoor unit pipe heat insulation FRONT PANEL REMOVAL AND INSTALLATION 9 Intake grille...

Page 8: ...R UNIT PCB TERMINAL Front panel installation 9 4 1 First Þt the lower part of the front panel and insert top and bottom hooks 2 top sides 7 bottom sides 2 center Indoor unit Bottom holes 3 position Bottom hooks 3 position Bottom holes 4 position Center holes 2 position Center hooks 2 position Top hooks 2 position Top holes 2 position Indoor unit Front panel Bottom hooks 2 position Bottom hooks 2 p...

Page 9: ...CN8 Relay wire Notice 2 Clasp Connector CND01 Relay control board Clasps 2 Notice the installing direction of the relay control board The elevation of the control box is fit for the recess of the relay control board 1 Insert the relay control board toward 2 clasps 2 Then set the board with the clasp 3 Connect the relay wire terminal to the connector CND01 on the relay control board 4 Connect the r...

Page 10: ...ding on the installed environment the room temperature sensor may require a cor rection The settings may be selected as shown in the table below Factory setting Setting Description Function Number Setting Value Standard 30 00 Slightly lower control 01 Lower control 02 Warmer control 03 Function number Setting value Installing the external connect kit terminal sold separately Connect the wire of ex...

Page 11: ...nsor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error Heating Room Temperature Correction Depending on the installed environment the room temperature sensor may require a cor rection The settings may be changed as shown in the table below Factory setting Setting Description Function Number Setting Value Standard 31 00 Lower control 01 Slightly...

Page 12: ...unit fan motor error 9 9 4 way valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Troubleshooting with the indoor unit display OPERATION indicator lamp green TIMER indicator lamp orange ECONOMY indicator lamp green Troubleshooting w...

Reviews: