Fujitsu AOYG14LTCN Installation Manual Download Page 6

En-6

6.9.2. Bending pipes

•   If pipes are shaped by hand, be careful not to collapse them.
•   Do not bend the pipes in an angle more than 90°.
•   When pipes are repeatedly bend or stretched, the material will harden, making it dif

Þ

 cult 

to bend or stretch them any more.

•   Do not bend or stretch the pipes more than 3 times.

 CAUTION

 To prevent breaking of the pipe, avoid sharp bends. 

 If the pipe is bent repeatedly at the same place, it will break.

6.9.3. Pipe connection

 CAUTION

  Be sure to Install the pipe against the port on the indoor unit correctly. If the center-

ing is improper, the 

ß

 are nut cannot tighten smoothly. If the 

ß

 are nut is forced to turn, 

the threads will be damaged.

  Do not remove the 

ß

 are nut from the indoor unit pipe until immediately before con-

necting the connection pipe.

  Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order 

to tighten the 

ß

 are nut correctly. 

  Tighten  the 

ß

 are  nuts  with  a  torque  wrench  using  the  speci

Þ

 ed  tightening  method. 

Otherwise, the 

ß

 are nuts could break after a prolonged period, causing refrigerant to 

leak and generate hazardous gas if the refrigerant comes into contact with a 

ß

 ame.

  Connect the piping so that the control box cover can easily be removed for servicing 

when necessary.

  In order to prevent water from leaking into the control box, make sure that the piping 

is well insulated.

When the flare nut is tightened properly by your hand, hold the body side coupling with a 
wrench, then tighten with a torque wrench. (See the table below for the flare nut tightening 
torques.)

 

Tighten with 2 wrenches.

Holding wrench

Flare nut

Connection pipe

Torque wrench

Indoor  unit  pipe 
(Body side)

Flare nut [mm (in.)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

ELECTRICAL WIRING

7. 

Wiring system diagram

7. 1. 

 WARNING

Before connecting the wires, make sure the power supply is OFF.

Every wire must be connected 

Þ

 rmly.

 No wire should be allowed to touch refrigerant tubing, the compressor or any moving 
part.
 Loose wiring may cause the terminal to overheat or result in unit malfunction. A 

Þ

 re 

hazard may also exist. Therefore, be sure all wiring is tightly connected.
Connect wires to the matching numbers of terminals.

Grounding line

Type 245 IEC57
(Inter-unit)

OUTDOOR UNIT 
or BRANCH BOX

Please connect it to  
the speci

Þ

 ed terminal.

INDOOR UNIT

TERMINAL

Power line

Control line

 Indoor unit wiring

7. 2. 

(1) Remove the wire cover. (Remove the 1 screw.)
(2) Remove the cable clamp. (Remove the 1 screw.)
(3) Bend the end of the connection cable as shown in the 

Þ

 gure.

(4) Connect the end of the connection cable fully inserting into the terminal block.
(5) Fasten the connection cable with a cable clamp. (Attach the 1 screw.)

Insert the wire cover tab into the square hole 
of the indoor unit and fasten with a screw.

End of connection cable

30 mm

Cable clamp

Connection 
cable

Screw

Screw

Wire cover

Connection cable

Terminal block

Cable clamp

Connection 
cable

Screw

Screw

Wire cover

50 mm

How to connect wiring to the terminals

7. 3. 

Caution when wiring cable

When stripping off the insulation of a lead wire, always use a special tool such as a wire 
stripper. If there is no special tool available, carefully strip the insulation with a knife etc.
(1)  Use crimp-type terminals with insulating sleeves as shown in the 

Þ

 gure below to con-

nect to the terminal block.

(2)  Securely clamp the crimp-type terminals to the wires using an appropriate tool so that 

the wires do not come loose.

Strip : 10 mm 

Crimp-type 
terminal

Sleeve

(3)  Use the speci

Þ

 ed wires, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-

driver that is too small, otherwise, the screw heads may be damaged and prevent the 
screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.

Screw with special washer

Wire

Crimp-type terminal

Terminal blocks

Wire

Screw with special washer

Crimp-type 

terminal

(6)  See the table below for the terminal screw tightening torques.

Tightening torque [N·m (kgf·cm)]

M4 screw

1.2 to 1.8 (12 to 18)

 CAUTION

  Match the terminal block numbers and connection cable colors with those of the 

outdoor unit or branch box.

  Erroneous wiring may cause burning of the electric parts.

  Connect the connection cables 

Þ

 rmly to the terminal block. Imperfect installation may 

cause a 

Þ

 re.

  Always fasten the outside covering of the connection cable with the cable clamp. (If 

the insulator is chafed, electric discharge may occur.)

Always connect the ground wire.

Do not use the earth screw of the indoor unit for the connection other than a speci

Þ

 ed 

outdoor unit or branch box.

Summary of Contents for AOYG14LTCN

Page 1: ... Swedish Polish AIR CONDITIONER ASENNUSOHJE SISÄYKSIKKÖ seinälle asennettava malli Vain valtuutetuille huoltohenkilöille INSTALLASJONSVEILEDNING INNENDØRSENHET veggmontert modell Kun for autorisert servicepersonell INSTALLATIONSHANDBOK INOMHUSENHET väggmonterad Endast för auktoriserad servicepersonal INSTRUKCJA MONTA U URZ DZENIE WEWN TRZNE do monta u ciennego Do u ytku wy cznie przez autoryzowany...

Page 2: ...use damage or malfunction of your property ABOUT THE UNIT 2 Precautions for using R410A refrigerant 2 1 The basic installation work procedures are the same as conventional refrigerant R22 models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 models some of the piping and installation and service tools a...

Page 3: ...s to secure refrigerant piping ELECTRICAL REQUIREMENT 4 The indoor unit is powered from the outdoor unit or branch box Do not power indoor unit from separate power source WARNING Refer to local codes for acceptable cable type Cable Cable size Remarks Connection cable Type 60245 IEC 57 3 cable Ground 1 Ø 230 V Max Cable Length Limit voltage drop to less than 2 Increase cable gauge if voltage drop i...

Page 4: ...g When the piping is connected in direction 2 3 4 or 5 use a cutting tool to cut along the groove for the piping that will coming out of the under cover For 5 Left outlet For 4 Left bottom outlet For 3 Right bottom outlet For 2 Right outlet Cutting the hole in the wall for the connecting piping 6 6 1 Cut a 65 mm diameter hole in the wall at the position shown in the following 2 Cut the hole so tha...

Page 5: ... and left rear piping align the marks on the wall hook bracket and shape the connection pipe Bend the connection piping at a bend radius of 70 mm or more and install no more than 35 mm from the wall After passing the indoor piping and drain hose through the wall hole hang the indoor unit on the hooks at the top and bottom of the wall hook bracket No gap Hexagonal wrench Drain cock Drain cap Instal...

Page 6: ... line Type 245 IEC57 Inter unit OUTDOOR UNIT or BRANCH BOX Please connect it to the speciÞed terminal INDOOR UNIT TERMINAL Power line Control line Indoor unit wiring 7 2 1 Remove the wire cover Remove the 1 screw 2 Remove the cable clamp Remove the 1 screw 3 Bend the end of the connection cable as shown in the Þgure 4 Connect the end of the connection cable fully inserting into the terminal block ...

Page 7: ...e Connection cable Pipe Drain hose Check the following GOOD Drain hose Saddle Lifted up Wave End in water Drain hose Connection pipe Wall pipe Connection cable Left piping For connection from the left rear NO GOOD NO GOOD NO GOOD Pipe Connection pipe heat insulation Bind the pipes together so that there is no gap Indoor unit pipe heat insulation FRONT PANEL REMOVAL AND INSTALLATION 9 Intake grille...

Page 8: ...R UNIT PCB TERMINAL Front panel installation 9 4 1 First Þt the lower part of the front panel and insert top and bottom hooks 2 top sides 7 bottom sides 2 center Indoor unit Bottom holes 3 position Bottom hooks 3 position Bottom holes 4 position Center holes 2 position Center hooks 2 position Top hooks 2 position Top holes 2 position Indoor unit Front panel Bottom hooks 2 position Bottom hooks 2 p...

Page 9: ...CN8 Relay wire Notice 2 Clasp Connector CND01 Relay control board Clasps 2 Notice the installing direction of the relay control board The elevation of the control box is fit for the recess of the relay control board 1 Insert the relay control board toward 2 clasps 2 Then set the board with the clasp 3 Connect the relay wire terminal to the connector CND01 on the relay control board 4 Connect the r...

Page 10: ...ding on the installed environment the room temperature sensor may require a cor rection The settings may be selected as shown in the table below Factory setting Setting Description Function Number Setting Value Standard 30 00 Slightly lower control 01 Lower control 02 Warmer control 03 Function number Setting value Installing the external connect kit terminal sold separately Connect the wire of ex...

Page 11: ...nsor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error Heating Room Temperature Correction Depending on the installed environment the room temperature sensor may require a cor rection The settings may be changed as shown in the table below Factory setting Setting Description Function Number Setting Value Standard 31 00 Lower control 01 Slightly...

Page 12: ...unit fan motor error 9 9 4 way valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Troubleshooting with the indoor unit display OPERATION indicator lamp green TIMER indicator lamp orange ECONOMY indicator lamp green Troubleshooting w...

Reviews: