Fujitsu AOYG14LTCN Installation Manual Download Page 5

En-5

Forming the drain hose and pipe

6. 8. 

[Rear piping, Right piping, Bottom piping]

• Install the indoor unit piping in the direction of the wall hole and bind the drain hose 

and pipe together with vinyl tape.

• Install the piping so that the drain hose is at the bottom.
• Wrap the pipes of the indoor unit that are visible from the outside with decorative tape.

[For Left rear piping, Left piping]

Interchange the drain cap and the drain hose.

 CAUTION

Insert  drain  hose  and  drain  cap  securely.  Drain  should  slope  down  to  avoid  water 
leakage.

When  inserting,  be  sure  not  to  attach  any  material  besides  water.  If  any  other 
material is attached, it will cause deterioration and water leakage.

After removing drain hose, be sure not to forget mounting drain cap.

Be sure to 

Þ

 x the drain hose with tape to the bottom of piping.

Prevent drain water freezing under low temperature environment.
When  installing  indoor  unit’s  drain  hose  outdoors,  necessary  measure  for  frost 
protection should be taken to prevent drain water freezing.
Under  low  temperature  environment  (when  outdoor  temperature  under  0  °C),  after 
cooling  operation  is  executed,  water  in  the  drain  hose  could  be  frozen.  Once  drain 
water is frozen, the drain hose will be blocked and water leakage may result at the 
indoor unit.

Installation method of Drain cap 

Use a hexagonal wrench 4 mm at opposite side to insert 
the drain cap, till the drain cap contacts the tip of drain 
cock.

Right piping

Bottom piping

Bind with vinyl tape

Refrigerant pipes (top)

Rear piping

Indoor unit drain hose (bottom)

For left outlet piping, 

cut off the piping 

outlet cutting groove 

with a hacksaw. 

Indoor unit 

drain hose

Drain cap

Remove the drain cap by pulling 

at the projection at the end of the 

cap with pliers, etc.

Removal method of drain hose

Remove  the  screw  at  the  left  of  drain 
hose and pull out drain hose.

Installation method of drain hose

Vertically  insert  the  drain  hose  toward  the 
inside, so that the drain 

Þ

 xture (white) can ac-

curately  align  with  the  screw  hole  around  the 
drain cock.
After  inserting  and  before  replacing,  please 
reinstall and 

Þ

 x the removed screws.

• 

Please hold around the joint of the drain hose during working.

• 

As the screw is inside, be sure to use screwdriver treated with magnet.

Screw

Drain fixture

Drain hose

Screw hole

Drain cock

Drain hose

Screw

Drain fixture

• For left piping and left rear piping, align the marks on the wall hook bracket and shape the 

connection pipe.

• Bend the connection piping at a bend radius of 70 mm or more and install no more than 

35 mm from the wall.

• After passing the indoor piping and drain hose through the wall hole, hang the indoor unit on 

the hooks at the top and bottom of the wall hook bracket.

No gap

Hexagonal 
wrench

Drain 

cock

Drain cap

[Installing the indoor unit]

•   Hang the indoor unit from the hooks at the top of the wall hook bracket.
•   Insert the spacer, etc. between the indoor unit and the wall hook bracket and separate 

the bottom of the indoor unit from the wall.

Indoor unit

Wall hook bracket

(Spacer)

Connection pipe (6.35 mm dia.)

Align the marks

Indoor unit

Connection pipe (9.52 or 12.7 mm dia.)

Top hooks

Bottom hooks

Wall hook bracket

Bend R70 mm with 
a pipe bender

After hooking the indoor unit to the top hook, hook the 

Þ

 ttings of the indoor unit to the 2 

bottom hooks while lowering the unit and pushing it against the wall.

Flare connection (Pipe connection)

6. 9. 

 CAUTION

 Tighten the 

ß

 are nuts with a torque wrench using the speci

Þ

 ed tightening method. Oth-

erwise, the 

ß

 are nuts could break after a prolonged period, causing refrigerant to leak 

and generate hazardous gas if the refrigerant comes into contact with a 

ß

 ame.

6.9.1. Flaring

Use special pipe cutter and 

ß

 are tool exclusive for R410A.

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3)  Insert the 

ß

 are nut (always use the 

ß

 are nut attached to the indoor unit(s) and outdoor unit 

or  branch  box  respectively)  onto  the  pipe  and  perform  the 

ß

 are  processing  with  a 

ß

 are 

tool. Use the special R410A 

ß

 are tool, or the conventional 

ß

 are tool. Leakage of refriger-

ant may result if other 

ß

 are nuts are used.

(4)  Protect  the  pipes  by  pinching  them  or  with  tape  to  prevent  dust,  dirt,  or  water  from 

entering the pipes.

Die

A

Pipe

B

L

Check  if  [L]  is  flared  uniformly 
and is not cracked or scratched.

Pipe outside diameter 

[mm (in.)]

Dimension A [mm]

Dimension B [mm]

Flare tool for R410A, 

clutch type

6.35 (1/4)

0 to 0.5

9.1

9.52 (3/8)

13.2

12.70 (1/2)

16.6

When using conventional 

ß

 are tools to 

ß

 are R410A pipes, the dimension A should be ap-

proximately 0.5 mm more than indicated in the table (for 

ß

 aring with R410A 

ß

 are tools) to 

achieve the speci

Þ

 ed 

ß

 aring. Use a thickness gauge to measure the dimension A. 

Width across 

flats

Pipe outside diameter [mm (in.)]

Width across flats 

of Flare nut [mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

Summary of Contents for AOYG14LTCN

Page 1: ... Swedish Polish AIR CONDITIONER ASENNUSOHJE SISÄYKSIKKÖ seinälle asennettava malli Vain valtuutetuille huoltohenkilöille INSTALLASJONSVEILEDNING INNENDØRSENHET veggmontert modell Kun for autorisert servicepersonell INSTALLATIONSHANDBOK INOMHUSENHET väggmonterad Endast för auktoriserad servicepersonal INSTRUKCJA MONTA U URZ DZENIE WEWN TRZNE do monta u ciennego Do u ytku wy cznie przez autoryzowany...

Page 2: ...use damage or malfunction of your property ABOUT THE UNIT 2 Precautions for using R410A refrigerant 2 1 The basic installation work procedures are the same as conventional refrigerant R22 models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 models some of the piping and installation and service tools a...

Page 3: ...s to secure refrigerant piping ELECTRICAL REQUIREMENT 4 The indoor unit is powered from the outdoor unit or branch box Do not power indoor unit from separate power source WARNING Refer to local codes for acceptable cable type Cable Cable size Remarks Connection cable Type 60245 IEC 57 3 cable Ground 1 Ø 230 V Max Cable Length Limit voltage drop to less than 2 Increase cable gauge if voltage drop i...

Page 4: ...g When the piping is connected in direction 2 3 4 or 5 use a cutting tool to cut along the groove for the piping that will coming out of the under cover For 5 Left outlet For 4 Left bottom outlet For 3 Right bottom outlet For 2 Right outlet Cutting the hole in the wall for the connecting piping 6 6 1 Cut a 65 mm diameter hole in the wall at the position shown in the following 2 Cut the hole so tha...

Page 5: ... and left rear piping align the marks on the wall hook bracket and shape the connection pipe Bend the connection piping at a bend radius of 70 mm or more and install no more than 35 mm from the wall After passing the indoor piping and drain hose through the wall hole hang the indoor unit on the hooks at the top and bottom of the wall hook bracket No gap Hexagonal wrench Drain cock Drain cap Instal...

Page 6: ... line Type 245 IEC57 Inter unit OUTDOOR UNIT or BRANCH BOX Please connect it to the speciÞed terminal INDOOR UNIT TERMINAL Power line Control line Indoor unit wiring 7 2 1 Remove the wire cover Remove the 1 screw 2 Remove the cable clamp Remove the 1 screw 3 Bend the end of the connection cable as shown in the Þgure 4 Connect the end of the connection cable fully inserting into the terminal block ...

Page 7: ...e Connection cable Pipe Drain hose Check the following GOOD Drain hose Saddle Lifted up Wave End in water Drain hose Connection pipe Wall pipe Connection cable Left piping For connection from the left rear NO GOOD NO GOOD NO GOOD Pipe Connection pipe heat insulation Bind the pipes together so that there is no gap Indoor unit pipe heat insulation FRONT PANEL REMOVAL AND INSTALLATION 9 Intake grille...

Page 8: ...R UNIT PCB TERMINAL Front panel installation 9 4 1 First Þt the lower part of the front panel and insert top and bottom hooks 2 top sides 7 bottom sides 2 center Indoor unit Bottom holes 3 position Bottom hooks 3 position Bottom holes 4 position Center holes 2 position Center hooks 2 position Top hooks 2 position Top holes 2 position Indoor unit Front panel Bottom hooks 2 position Bottom hooks 2 p...

Page 9: ...CN8 Relay wire Notice 2 Clasp Connector CND01 Relay control board Clasps 2 Notice the installing direction of the relay control board The elevation of the control box is fit for the recess of the relay control board 1 Insert the relay control board toward 2 clasps 2 Then set the board with the clasp 3 Connect the relay wire terminal to the connector CND01 on the relay control board 4 Connect the r...

Page 10: ...ding on the installed environment the room temperature sensor may require a cor rection The settings may be selected as shown in the table below Factory setting Setting Description Function Number Setting Value Standard 30 00 Slightly lower control 01 Lower control 02 Warmer control 03 Function number Setting value Installing the external connect kit terminal sold separately Connect the wire of ex...

Page 11: ...nsor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error Heating Room Temperature Correction Depending on the installed environment the room temperature sensor may require a cor rection The settings may be changed as shown in the table below Factory setting Setting Description Function Number Setting Value Standard 31 00 Lower control 01 Slightly...

Page 12: ...unit fan motor error 9 9 4 way valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Troubleshooting with the indoor unit display OPERATION indicator lamp green TIMER indicator lamp orange ECONOMY indicator lamp green Troubleshooting w...

Reviews: