P
External heater output
Specifications of the signal output performance are as shown as follows:
Example:
When set temperature (Ts) is set at 22 °C;
• And room temperature (Tr) increase above 12 °C, signal output is on.
• And Tr increase above 21 °C, signal output is off.
• And Tr decrease below 19 °C, signal output is on.
• And Tr decrease below 10 °C, signal output is off.
The output also turns off in defrost operation.
Function
setting /
Rotary SW of External
input and output PCB
External output
Output
signal
Command
60-11 / D
Output of indoor unit
CN47
Low
→
High
Heater on
High
→
Low
Heater off
60-00 / 2
External input and output
PCB
Output 3
Off
→
On
Heater on
60-09 / B
60-10 / C
On
→
Off
Heater off
Output signal
Condition
Low
→
High
Heater turns on as shown in diagram of heating temperature
Off
→
On
High
→
Low
Heater turns off as shown in diagram of heating temperature
• Other than Heating mode
On
→
Off
• Error occurred
• Forced thermo off
• Fan stop protection
Off
Off
On
Tr-Ts
Tr-Ts=-1 °C
Tr-Ts=-10 °C
Tr-Ts=-3 °C
Tr-Ts=-12 °C
Summary of Contents for AOYG12LBLA
Page 27: ... 21 DUCT TYPE ARYG12 54LHTBP 5 2 Models ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP and ARYG54LHTBP ...
Page 110: ... 104 OUTDOOR UNIT AOYG12 54LB 5 Wiring diagrams 5 1 Models AOYG12LBLA and AOYG14LBLA ...
Page 111: ... 105 OUTDOOR UNIT AOYG12 54LB 5 2 Models AOYG18LBCA and AOYG24LBCA 5 3 Model AOYG30LBTA ...
Page 112: ... 106 OUTDOOR UNIT AOYG12 54LB 5 4 Model AOYG36LBTA ...
Page 113: ... 107 OUTDOOR UNIT AOYG12 54LB 5 5 Models AOYG45LBTA and AOYG54LBTA ...