- 72 -
DUC
T TYPE
ARYG12-5
4LHT
B
P
2) Static pressure
Select the appropriate static pressure according to the installation conditions.
NOTE:
Range of static pressure is different by model.
If the static pressure is set above maximum range, the setting will be the same as the maximum.
Example:
For 45, 54 type models, setting "170 Pa" (17) to "200 Pa" (20) will be the same as "160 Pa" (16).
For details, refer to Chapter 7.
Function number
Setting value
Setting description
Factory setting
26
03
30 Pa
04
40 Pa
05
50 Pa
06
60 Pa
07
70 Pa
08
80 Pa
09
90 Pa
10
100 Pa
11
110 Pa
12
120 Pa
13
130 Pa
14
140 Pa
15
150 Pa
16
160 Pa
17
170 Pa
18
180 Pa
19
190 Pa
20
200 Pa
31
Standard (35 Pa: 12, 14, 18, 24 type)
Standard (47 Pa: 30, 36 type)
Standard (60 Pa: 45, 54 type)
♦
32
Automatic airflow adjustment
Type name
Setting of static pressure range
12, 14, 18, 24, 30 type, and 36 type
30 to 200 Pa
45 and 54 type
30 to 160 Pa