- 13 -
DUC
T TYPE
ARYG12-5
4LHT
B
P
Remote controller type
Wired
NOTES:
Specifications are based on the following conditions:
–Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
–Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
–Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.), Standard static pressure; 18 type and 24 type: 35Pa, 30 type: 47Pa
Protective function might work when using it outside the operation range.
*1: Maximum current:
–The maximum value when operated within the operation range.
–The total current of indoor unit and outdoor unit.
*2: Sound pressure level:
–Measured values in manufacturer’s anechoic chamber.
–Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Model name
ARYG18LHTBP
ARYG24LHTBP
ARYG30LHTBP
Energy efficiency class
Cooling
A
++
A
++
A
+
Heating (Average)
A
+
A
+
A
Pdesign
Cooling
kW
5.2 (35°C)
6.8 (35°C)
8.5 (35°C)
Heating (Average)
4.3 (-10°C)
6.0 (-10°C)
8.0 (-10°C)
SEER
Cooling
kWh/
kWh
7.15
6.50
5.95
SCOP
Heating (Average)
4.11
4.01
3.95
Annual energy consumption
QCE
kWh/a
255
366
500
QHE (Average)
1,462
2,092
2,833
Sound power level
Cooling
HIGH
dB (A)
54
57
63
Heating
54
57
65
Type
Duct
Inverter heat pump
Model name
ARYG18LHTBP
ARYG24LHTBP
ARYG30LHTBP
Summary of Contents for AOYG12LBLA
Page 27: ... 21 DUCT TYPE ARYG12 54LHTBP 5 2 Models ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP and ARYG54LHTBP ...
Page 110: ... 104 OUTDOOR UNIT AOYG12 54LB 5 Wiring diagrams 5 1 Models AOYG12LBLA and AOYG14LBLA ...
Page 111: ... 105 OUTDOOR UNIT AOYG12 54LB 5 2 Models AOYG18LBCA and AOYG24LBCA 5 3 Model AOYG30LBTA ...
Page 112: ... 106 OUTDOOR UNIT AOYG12 54LB 5 4 Model AOYG36LBTA ...