- 127 -
O
U
T
D
OOR UNIT
AOY
G
12-
54LB
Type of
protection
Protection form
Model
AOYG45LBTA
AOYG54LBTA
Circuit protection
Current fuse
(Filter PCB)
250 V, 30A
250 V, 10A × 2
250V, 3.15 A
Current fuse
(Main PCB)
250 V, 3.15 A
Fan motor
protection
Thermal protection program
Activate
122±9°C
Fan motor stop
Reset
116+10/-9°C
Fan motor restart
Compressor
protection
Terminal protection program
(Compressor temp.)
Activate
108°C
Compressor stop
Reset
80°C
Compressor restart
Thermal protection program
(Discharge temp.)
Activate
110°C
Compressor stop
Reset
After 7 minutes
Compressor restart
High pressure
protection
Pressure switch
Activate
4.2±0.1 MPa
Compressor stop
Reset
3.2±0.15 MPa
Compressor restart
Pressure sensor
Heating
Activate
4.1 MPa
Compressor stop
Reset
After 3 minutes
Compressor restart
Thermal protection
program
(Heat exchanger
temp.)
Cooling
Activate
67°C
Compressor stop
Reset
63°C
Compressor restart
Low pressure
protection
Pressure sensor
Cooling
Activate
0.12 MPa or less (for 5 minutes)
Compressor stop
Reset
0.15 MPa
Compressor restart
Summary of Contents for AOYG12LBLA
Page 27: ... 21 DUCT TYPE ARYG12 54LHTBP 5 2 Models ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP and ARYG54LHTBP ...
Page 110: ... 104 OUTDOOR UNIT AOYG12 54LB 5 Wiring diagrams 5 1 Models AOYG12LBLA and AOYG14LBLA ...
Page 111: ... 105 OUTDOOR UNIT AOYG12 54LB 5 2 Models AOYG18LBCA and AOYG24LBCA 5 3 Model AOYG30LBTA ...
Page 112: ... 106 OUTDOOR UNIT AOYG12 54LB 5 4 Model AOYG36LBTA ...
Page 113: ... 107 OUTDOOR UNIT AOYG12 54LB 5 5 Models AOYG45LBTA and AOYG54LBTA ...